DataMuseum.dk

Presents historical artifacts from the history of:

CR80 Wang WCS documentation floppies

This is an automatic "excavation" of a thematic subset of
artifacts from Datamuseum.dk's BitArchive.

See our Wiki for more about CR80 Wang WCS documentation floppies

Excavated with: AutoArchaeologist - Free & Open Source Software.


top - download

⟦28da544a0⟧ Wang Wps File

    Length: 99824 (0x185f0)
    Types: Wang Wps File
    Notes: CRT/SDS/001               
    Names: »1203A «

Derivation

└─⟦d04a935aa⟧ Bits:30006049 8" Wang WCS floppy, CR 0078A
    └─ ⟦this⟧ »1203A « 

WangText

…11……00……00……00……00…C…0a……00……00…C…0b…C B…0e…B…07…6…0a…6…0e…6…02…/…01…/…06……1e……0c……1e……02……1d……09……1d……0a……1d……0b……1d……0c……1d……0d……1d……0e……1d……0f……1d……00……1d……01……1d……07……1c……0d……1c……02……1c……06……1b……0c……1b……01……1a……08……1a……00……1a……05……19……0b……19……01……19……07……18……0e……18……01……18……05……17……0a……17……0f……17…
…16……09……16……01……16……07……15……0e……15……05……14……0e……14…
…14… …86…1                                             …02…           …02…   …02…        

…02…CRT/SDS/001

…02…850501…02……02…
CAMPS REMOTE TERMINALS
SYSTEM REQUIREMENT AND DESIGN SPECIFICATION…02…ISSUE 1.1…02…CRT








                    T̲A̲B̲L̲E̲ ̲O̲F̲ ̲C̲O̲N̲T̲E̲N̲T̲S̲



   1  SCOPE .........................................
      7

   2  APPLICABLE DOCUMENTS ..........................
      7

     2.1  APPLICABLE DOCUMENTS ......................
        7
     2.2  REFERENCED DOCUMENTS ......................
        8
     2.3  TERMS .....................................
        8

   3  REQUIREMENTS ..................................
      9

     3.1  SYSTEM DEFINITION .........................
        9
       3.1.1  General Description ...................
          9
       3.1.2  Functional Requirements ...............
          9
         3.1.2.1  Remote Site Connections ...........
           11
         3.1.2.2  Main Site Connections .............
           11

       3.1.3  Design Requirements ...................
         12

     3.2  FUNCTIONAL PRINCIPLE ......................
       12
       3.2.1  Basic Configuration ...................
         12
         3.2.1.1  Main Site Configuration ...........
           12
         3.2.1.2  Remote Site Configuration .........
           13

       3.2.2  Reconfiguration Possibilities .........
         21
         3.2.2.1  Option 1 ..........................
           21
         3.2.2.2  Option 2 ..........................
           21

       3.2.3  Interface Capability ..................
         22
       3.2.4  Specific Equipment Characteristics ....
         24
         3.2.4.1  Crypto/Modem ......................
           24
         3.2.4.2  Medium Speed Printers .............
           24
         3.2.4.3  Visual Display Units ..............
           24

     3.3  PHYSICAL CHARACTERISTICS ..................
       25
       3.3.1  Power Input ...........................
         25
       3.3.2  Environmental Conditions ..............
         25
         3.3.2.1  Temperature and Humidity ..........
           26
         3.3.2.2  Dust and Fumes ....................
           26

     3.4  SECURITY ..................................
       27
       3.4.1  TEMPEST Acceptance ....................
         27

     3.5  CONSTRUCTION REQUIREMENTS .................
       29
       3.5.1  General ...............................
         29


         3.5.1.1  Equipment produced by 
                  Christian Rovsing A/S .............
                   29
         3.5.1.2  Equipment produced by
                  Subcontractors ....................
                   29
         3.5.1.3  Products from other Suppliers .....
           29

       3.5.2  Special Requirements for the
              CRT System ............................
               30
         3.5.2.1  Utility Outlet Sockets ............
           30
         3.5.2.2  Bench Handling ....................
           30
         3.5.2.3  Wiring ............................
           30
         3.5.2.4  Ventilation and Cooling ...........
           31a
         3.5.2.5  Nameplates and Product marking ....
           31a
         3.5.2.6  Safety ............................
           31a
           3.5.2.6.1  Regulations ...................
             31a
           3.5.2.6.2  Personnel Safety ..............
             31b
           3.5.2.6.3  Equipment Safety ..............
             31b
           3.5.2.6.4  Grounding .....................
             31c

     3.6  CRT DOCUMENTATION .........................
       31d
       3.6.1  Headlines to the CRT Equipment
              Handbook ..............................
               31d
       3.6.2  Contents of the CRT Equipment
              Handbook ..............................
               32
         3.6.2.1  Scope of Manual ...................
           32
         3.6.2.2  Introduction ......................
           32
         3.6.2.3  Specifications ....................
           33
         3.6.2.4  Connections .......................
           34
         3.6.2.5  Detailed Functional Description ...
           34
         3.6.2.6  Installation ......................
           34
         3.6.2.7  Operating Instructions ............
           34
         3.6.2.8  Maintenance .......................
           34
         3.6.2.9  Assembly Breakdown ................
           35
         3.6.2.10 Inventory .........................
           35
         3.6.2.11 Spare Parts List ..................
           35
         3.6.2.12 Circuit Boards and Diagrams .......
           35

         3.6.3  Field Modification Documents ........
           35

     3.7  LOGISTIC REQUIREMENTS .....................
       36
       3.7.1  Transportation and Installation .......
         36
         3.7.1.1  Transportation ....................
           36
         3.7.1.2  Installation ......................
           36
           3.7.1.2.1  Equipment installation 
                      at main sites .................
                       36
           3.7.1.2.2  Equipment installation
                      at remote sites ...............
                       37
           3.7.1.2.3  Standards and Security ........
             38
           3.7.1.2.4  Power Supply and Power
                      distribution ..................
                       38


           3.7.1.2.5  Grounding .....................
             39
           3.7.1.2.6  Space and access ..............
             40
           3.7.1.2.7  Site Surveys ..................
             40

       3.7.2  Maintenance and Support ...............
         42
       3.7.3  Spares and Codification ...............
         42
         3.7.3.1  Supply of parts ...................
           42
         3.7.3.2  NATO Codification .................
           42

       3.7.4  Training ..............................
         43

   4  SYSTEM VERIFICATION ...........................
     44

     4.1  TEST AND VERIFICATION METHODS .............
       44
     4.2  VERIFICATION ..............................
       45
       4.2.1  Hardware Verification .................
         45
         4.2.1.1  Production Verification ...........
           45
         4.2.1.2  Factory Acceptance Test ...........
           46

       4.2.2  System Verification ...................
         46
         4.2.2.1  COMSEC on-site verification .......
           46
         4.2.2.2  Site Functional Test ..............
           46

     4.3  FACTORY ACCEPTANCE AND SITE FUNCTIONAL
          TEST DOCUMENTATION ........................
           47
       4.3.1  General ...............................
         47
       4.3.2  Factory Acceptance Test Document ......
         47
       4.3.3  Site Functional Test Document .........
         47
       4.3.4  Test Procedures .......................
         47
       4.3.5  Test Result Forms .....................
         48
       4.3.6  Approval and Delivery .................
         48

   5  SYSTEM DESIGN .................................
     49

     5.1  MAIN SITE EQUIPMENT .......................
       49
       5.1.1  TDX-Crate Assembly ....................
         51
         5.1.1.1  CTX-Crate .........................
           51
         5.1.1.2  BSM-X .............................
           58
           5.1.1.2.1  BSM-X Panel ...................
             58

         5.1.1.3 LTUX-S .............................
           60
           5.1.1.3.1  TDX Bus Interface .............
             60
           5.1.1.3.2  Mechanical and Electrical 
                      Specification .................
                       65
           5.1.1.3.3  User Interface ................
             67
           5.1.1.3.4  V24 Back Panel ................
             67
           5.1.1.3.5  OMDT ..........................
             67
           5.1.1.3.6  V24 Monitor Panel .............
             68



         5.1.1.4  TDX Power Supply ..................
           68
           5.1.1.4.1  Main Power Panel ..............
             69
         5.1.1.5  Opto Power Supply .................
           71

       5.1.2  Adaptor Crate Assembly ................
         71
         5.1.2.1  V28(L/L) Adaptor ..................
           73
         5.1.2.2  V24 Back Panel ....................
           77
         5.1.2.3  Adaptor Power Supply ..............
           77

       5.1.3  Statistical Multiplexer ...............
         77
         5.1.3.1  Statistical Multiplexer
                  Transmission ......................
                   78
         5.1.3.2  Error Control .....................
           78
         5.1.3.3  Buffer Control ....................
           78
         5.1.3.4  Configuration .....................
           79
         5.1.3.5  Channel Interface .................
           79
         5.1.3.6  Mux-Line Interface ................
           79
         5.1.3.7  Power .............................
           80

       5.1.4  Synchroneous Multiplexer...............
           
       5.1.5  Resynchronization Module...............
           
         5.1.5.1  Power Consumption..................
             

     5.2  REMOTE SITE EQUIPMENT .....................
       80
       5.2.1  Statistical Multiplexer ...............
         83
       5.2.2  Opto Crate Assembly ...................
         83
         5.2.2.1  Optical Mux/Demux Tranceiver
                  (OMDT) ............................
                   85
         5.2.2.2  V28 (L/L) Adaptor .................
           86
         5.2.2.3  V24 Back Panel ....................
           86
         5.2.2.4  Opto Power Supply .................
           86
         5.2.2.5  V24 Monitor Panel .................
           87

     5.3  RACK AND SUB-ASSEMBLIES ...................
       88
       5.3.1  CR80S Mechanical System ...............
         91
         5.3.1.1  CTX-Crate .........................
           91
         5.3.1.2  Cooling of CR80S Crates ...........
           94
         5.3.1.3  Cable Channel Assembly ............
           94

       5.3.2  Rack-Mounted Peripherals and
              Special Assemblies ....................
               97
         5.3.2.1  Statistical/Synchroneous Multiplexer
          97
         5.3.2.2  Power Line Filter .................
           97
         5.3.2.3  Mains Switch Assembly .............
           97
         5.3.2.4  Power Distribution Panel ..........
           98
         5.3.2.5  Filter Box Assembly ...............
           98

       5.3.3  EMI Shielded Racks ....................
        100
         5.3.3.1  Stand Alone Racks .................
          102
         5.3.3.2  Multibay Rack-Assembly ............
          102
         5.3.3.3  Power, Heat and Weight ............
          102
         5.3.3.4  Grounding of Racks and Equipment
                  in Racks ..........................
                107


                         1̲ ̲ ̲S̲C̲O̲P̲E̲



         This specification establishes the functional, performance,
         physical design, connectivity, testing and verification
         requirements for CRT (CAMPS REMOTE TERMINALS).

         The document consists of the following five chapters.

         Chapter 1, SCOPE, which introduces the document.

         Chapter 2, APPLICABLE DOCUMENTS, which contains the
         list of documents constituting the requirements baseline.

         Chapter 3, REQUIREMENTS, which defines the performance
         and design for CRT.

         Chapter 4, SYSTEM VERIFICATION, which denotes the responsibility
         during verification test and the associated verification
         documentation.

         Chapter 5, SYSTEM DESIGN, which gives a more detailed
         description of the design including specifications
         and description of the components used to implement
         the design.











                 2̲ ̲ ̲A̲P̲P̲L̲I̲C̲A̲B̲L̲E̲ ̲D̲O̲C̲U̲M̲E̲N̲T̲S̲



2.1      A̲p̲p̲l̲i̲c̲a̲b̲l̲e̲ ̲D̲o̲c̲u̲m̲e̲n̲t̲s̲

         The following documents are applicable to the CRT system
         requirement specification:

         a)  CPS/TCN/024, issue 4
             CRT Design Document, Equipment Breakdown
         b)  AMSG 719B
         c)  AMSG 720A



2.2      R̲E̲F̲E̲R̲E̲N̲C̲E̲D̲ ̲D̲O̲C̲U̲M̲E̲N̲T̲S̲

         a)  CAMPS Maintenance Plan
             CPS/PLN/006, sections 3.4 and 3.5

         b)  CAMPS Transportation Plan
             CPS/PLN/007

         c)  CAMPS Site Design Concept
             CPS/TCN/023, issue 2

         d)  CAMPS Standard Manual
             CPS/STM/001

         e)  CAMPS System Requirement Specification
             CPS/210/SYS/0001

         f)  CCITT Recommendation V24

         g)  CCITT Recommendation V28

         h)  MIL-STD-188C, section 7.2.1



2.3      T̲E̲R̲M̲S̲

         ANALYSIS           See section 4.1b)
         BID 1000           Name for cryptographic equipment
         BPJF               Black Patch Jack Field
         bps                Bit per second
         BSM-X              Bus Switch Module for TDX


         CAMPS              Computer Aided Message Processing
                            System
         CCB                Configuration Control Bus
         CLK                Clock
         COMSEC             Communications Security
         CPU                Central Processing Unit
         CR                 Christian Rovsing A/S
         CRC                Cyclic Redundancy Check
         CRT                C̲A̲M̲P̲S̲ Remote Terminals
         CRYPTO             Cryptographic Equipment
         CTX                CAMPS TDX
         CWR                Civil Work Requirement
         EMI                Electro-Magnetic Interference
         EXAMINATION        See section 4.1 c)
         FIFO               First In First Out register
         HF                 High Frequency
         H/W                Hardware
         I/O                Input/Output
         J                  Joule
         LTUX               Line Termination Unit for TDX
         MAIN SITE          A site, having a CAMPS
         MDF                Main Distribution Frame
         MIL-STD-188C       See Referenced Document
         MODEM              Modulator/Demodulator
         MOTHERBOARD        See section 5.1.1.1
         MSP                Medium Speed Printer
         NRZL               Non-Return-to-Zero-Logic
         OCR                Optical Card Reader
         OMDT               Optical Mux/Demux Transceiver
         ppm                Parts Per Million
         RED AREA           See section 3.4.1 h)
         REMOTE SITE        Site associated to a CAMPS site
                            by a communication link.
         RF                 Radio Frequency
         RPJF               Red Patch Jack Field
         SHAPE              Supreme Headquarters Allied Power
                            Europe
         SPL-D              Split-phase encoded data
         S/W                Software
         TDX                Telecommunication Data Exchange
         TEST               See section 4.1 a)
         VDU                Visual Display Unit
         V.24               See referenced document
         V.28               See referenced document
         V.28(L)            See notes for table 3.2.3-1
         V.28(L/L)          See notes for table 3.2.3-1
         VERIFICATON        See section 4.1
         X-NET              TDX-Bus System
         X-NET TERM         TDX-Bus Termination Module



                     3̲ ̲ ̲R̲E̲Q̲U̲I̲R̲E̲M̲E̲N̲T̲S̲



3.1      S̲Y̲S̲T̲E̲M̲ ̲D̲E̲F̲I̲N̲I̲T̲I̲O̲N̲



3.1.1    G̲e̲n̲e̲r̲a̲l̲ ̲D̲e̲s̲c̲r̲i̲p̲t̲i̲o̲n̲

         The CAMPS Remote Terminals (CRT) system supports the
         capability of moving some terminal operations from
         the main sites to remote locations.

         This does not mean that the max. connectivity of each
         CAMPS-site as specified in ref. e) has been expanded.

         The feature is obtained by means of statistical multiplexers
         and customer supplied crypto/modem lines between main
         and remote sites.

         Thus 8 V24 channels connect each remote site to the
         related main site.

         The CRT equipment is contained in EMI shielded racks.
         At the main sites the CRT rack(s) are bolted to the
         main CAMPS Line Termination racks and form a 4 or 5
         bay configuration, except Site 10 where a stand alone
         rack is used.



3.1.2    F̲u̲n̲c̲t̲i̲o̲n̲a̲l̲ ̲R̲e̲q̲u̲i̲r̲e̲m̲e̲n̲t̲s̲

         The remote terminal concept shall provide the following
         possibility:

         The transmission shall consist of 8 channels connecting
         each remote site with the related main site.

         The communication between each remote site and its
         main site shall use a single multiplexed link.





3.1.2.1  R̲e̲m̲o̲t̲e̲ ̲S̲i̲t̲e̲ ̲C̲o̲n̲n̲e̲c̲t̲i̲o̲n̲s̲.̲

         A single channel is saved for an OCR-option while the
         7 channels are used as follows:

         a)  Primarily the 7 channels are used for transmission
             of CAMPS-channels (connection to CAMPS expansion
             or CRT LTUX at main site).

             At the remote site 4 of these channels are terminated
             with OMDTs for opto-cable connection to the terminals,
             and 3 are terminated with V28(L/L) adaptors for
             connection with electrical cables (auxiliary channels).

         b)  Secondary (option 1) it shall be possible to implement
             a changed configuration, where the 3 auxiliary
             channels are disconnected from CAMPS at the main
             site and used as separate channels.



3.1.2.2  M̲a̲i̲n̲ ̲S̲i̲t̲e̲ ̲C̲o̲n̲n̲e̲c̲t̲i̲o̲n̲s̲

         At the main site the remote terminal equipment shall
         include one LTUX per remote site (4 channels).

         a)  Primarily these 4 channels are connected to the
             stat.mux. and used for transmission to the remote
             site.

         b)  Secondary (option 2) it shall be possible to implement
             a changed configuration, where the stat. mux. is
             disconnected, and the LTUX channels are used for
             expanding the number of connected terminals in
             the main site. The terminal connection points thus
             made available shall have an optical interface.





3.1.3    D̲e̲s̲i̲g̲n̲ ̲R̲e̲q̲u̲i̲r̲e̲m̲e̲n̲t̲s̲

         a)  The system design shall be such that the same hardware
             can be used to provide the required capability
             at any of the installations.

         b)  The equipment provided at all installations covered
             by this specification shall differ from one another,
             if at all, only in the number of hardware units
             of any given type in each configuration.

         c)  An operating CRT link includes both CR delivered
             and SHAPE supplied equipment. The division of responsibility
             of the equipment is defined by the responsibility
             demarkation line, which will be on the feed-through
             connectors mounted in the filter box. This applies
             both on main sites and remote sites.



3.2      F̲U̲N̲C̲T̲I̲O̲N̲A̲L̲ ̲P̲R̲I̲N̲C̲I̲P̲L̲E̲



3.2.1    B̲a̲s̲i̲c̲ ̲C̲o̲n̲f̲i̲g̲u̲r̲a̲t̲i̲o̲n̲

         Fig. 3.2.1-1 shows the configuration of a typical CRT-link
         between a main site and its related remote site(s).

         All CR supplied CRT-equipment are contained in separate
         racks at the main site and remote site.



3.2.1.1  M̲a̲i̲n̲ ̲S̲i̲t̲e̲ ̲C̲o̲n̲f̲i̲g̲u̲r̲a̲t̲i̲o̲n̲

         a)  The connection to main CAMPS is obtained by means
             of CTX crates, equipped with TDX-modules, connected
             to the TDX-busses of CAMPS.

         b)  The statistical multiplexer multiplexes 8 V24 channels,
             of which normally 4 channels are obtained from
             the CRT-LTUX, 3 are auxiliary channels, which 
             are obtained from CAMPS expansion LTUX, (wherever
             possible), and the last is reserved for a future
             positioning of an OCR at the remote site.



         c)  The stat.mux. takes care of:

             1)  C̲h̲a̲n̲n̲e̲l̲ ̲m̲u̲l̲t̲i̲p̲l̲e̲x̲i̲n̲g̲. Statistical multiplexing
                 gives an improved modem line utilization compared
                 to none or conventional time division multiplexing.

             2)  T̲r̲a̲n̲s̲m̲i̲s̲s̲i̲o̲n̲ ̲e̲r̲r̲o̲r̲ ̲p̲r̲o̲t̲e̲c̲t̲i̲o̲n̲ by means of a
                 cyclic redundancy check and automatic retransmission
                 request on errors.

             3)  T̲r̲a̲f̲f̲i̲c̲ ̲f̲l̲o̲w̲ ̲c̲o̲n̲t̲r̲o̲l̲, which takes care of possible
                 data peak load effects by controlling the sending
                 activities of the data terminal equipment.

         d)  The mux-line of the stat.mux. is connected to a
             feed-through connector in the filter box (responsibilities
             demarkation line).

         e)  The mux. line is connected by customer supplied
             wiring from the filter box to the red patch jack
             field in the crypto room. In the crypto-room customer
             supplied equipment takes care of encryption and
             modulation of information to be transmitted through
             the transmission media to the remote site and the
             reverse function for information received from
             the remote site.



3.2.1.2  R̲e̲m̲o̲t̲e̲ ̲S̲i̲t̲e̲ ̲C̲o̲n̲f̲i̲g̲u̲r̲a̲t̲i̲o̲n̲

         a)  Purchaser supplied equipment performs the same
             function as described in 3.2.1.1.e) on information
             received from/transmitted to the main site, ending
             up with the mux line interface in the filter box.

         b)  The stat.mux demultiplexes the message and the
             channels are connected to V28(L/L) adaptors and
             Opto Mux/Demux Transceivers (OMDT) respectively.

         c)  The output of these devices leaves the EMI shielded
             rack through the filter box.

         d)  The opto channels are connected to

             1)  the CR supplied Delta VDUs and/or

             2)  the CR supplied TRACOR medium speed printers.
















































              FIGURE 3.2.1.1, (sheet 1 of 8)
                  C̲R̲T̲ ̲L̲I̲N̲E̲ ̲C̲O̲N̲F̲I̲G̲U̲R̲A̲T̲I̲O̲N̲

















































          FIGURE 3.2.1.1 (sheet 2 of 8) DETAIL A
          M̲A̲I̲N̲ ̲S̲I̲T̲E̲ ̲C̲O̲N̲F̲I̲G̲U̲R̲A̲T̲I̲O̲N̲,̲ ̲C̲R̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲
       (̲M̲A̲X̲ ̲C̲O̲N̲F̲I̲G̲U̲R̲A̲T̲I̲O̲N̲)̲S̲I̲T̲E̲S̲ ̲2̲,̲ ̲3̲,̲ ̲8̲,̲ ̲9̲,̲ ̲1̲3̲,̲ ̲1̲4̲

















































        FIGURE 3.2.1.1 (sheet 3 of 8) DETAIL A…0e…1…0f…
       M̲A̲I̲N̲ ̲S̲I̲T̲E̲ ̲C̲O̲N̲F̲I̲G̲U̲R̲A̲T̲I̲O̲N̲,̲ ̲C̲R̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲S̲I̲T̲E̲ ̲1̲0̲

















































FIGURE 3.2.1.1 (sheet 4 of 8), detail B…01…M̲A̲I̲N̲ ̲S̲I̲T̲E̲ ̲C̲O̲N̲F̲I̲G̲U̲R̲A̲T̲I̲O̲N̲,̲ ̲C̲R̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲,̲…01…S̲I̲T̲E̲S̲
 ̲5̲,̲ ̲6̲,̲ ̲7̲,̲ ̲1̲1̲,̲ ̲1̲2̲,̲ ̲1̲5̲
















































         FIGURE 3.2.1.1 (Sheet 5 of 8), DETAIl D
          M̲A̲I̲N̲ ̲S̲I̲T̲E̲ ̲C̲O̲N̲F̲I̲G̲U̲R̲A̲T̲I̲O̲N̲,̲ ̲C̲R̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲,̲
                     S̲I̲T̲E̲ ̲4̲ ̲R̲A̲C̲K̲ ̲G̲,̲ ̲H̲















































              FIGURE 3.2.1.1 (Sheet 6 of 8)
 M̲A̲I̲N̲ ̲S̲I̲T̲E̲ ̲C̲O̲N̲F̲I̲G̲U̲R̲A̲T̲I̲O̲N̲,̲ ̲C̲R̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲,̲ ̲S̲I̲T̲E̲ ̲4̲ ̲R̲A̲C̲K̲ ̲I̲,̲ ̲J̲















































FIGURE 3.2.1.1 (sheet 7 of 8), detail E…01…R̲E̲M̲O̲T̲E̲ ̲S̲I̲T̲E̲ ̲C̲O̲N̲F̲I̲G̲U̲R̲A̲T̲I̲O̲N̲,̲ ̲C̲R̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲
 ̲(̲T̲Y̲P̲I̲C̲A̲L̲)̲















































              FIGURE 3.2.1.1 (Sheet 8 of 8)
                R̲E̲M̲O̲T̲E̲ ̲S̲I̲T̲E̲ ̲4̲A̲,̲ ̲4̲C̲,̲ ̲4̲D̲,̲ ̲4̲E̲
            (̲M̲A̲X̲ ̲C̲O̲N̲F̲I̲G̲U̲R̲A̲T̲I̲O̲N̲)̲,̲ ̲C̲R̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲



3.2.2    R̲e̲c̲o̲n̲f̲i̲g̲u̲r̲a̲t̲i̲o̲n̲ ̲P̲o̲s̲s̲i̲b̲i̲l̲i̲t̲i̲e̲s̲.̲



3.2.2.1  O̲p̲t̲i̲o̲n̲ ̲1̲

         a) Purpose: It shall be possible to implement a changed
                     configuration where the 3 auxiliary channels
                     are disconnected from CAMPS at the main
                     site and used for separate channels.

         b) Design:  The option is implemented by addition of
                     V28(L/L) adaptor equipment on the main
                     site.

                     These added adaptors (and crates etc.)
                     may be placed in the rack during normal
                     operation. Thus, a configuration change
                     is implemented by adding the needed cables.



3.2.2.2  O̲p̲t̲i̲o̲n̲ ̲2̲

         a) Purpose: It shall be possible to implement a changed
                     configuration where the stat.mux is disconnected
                     and the LTUX channels are used for expanding
                     the number of connected terminals in the
                     main site. The terminal connection points
                     thus made available shall have an optical
                     interface.

         b) Design:  The option is implemented by adding opto
                     power supplies to the CRT TDX-crates assemblies.
                     The OMDTs can not be placed in the racks
                     during normal operation, so the option
                     may be implemented by transferring the
                     remote site OMDTs to the main site along
                     with the terminals.

                     Thus, a configuration change is implemented
                     by removing the unwanted cables, transferring
                     the OMDTs and adding the needed opto-cables.





3.2.3    I̲n̲t̲e̲r̲f̲a̲c̲e̲ ̲C̲a̲p̲a̲b̲i̲l̲i̲t̲y̲

         Each CRT system shall provide the interface capabilities
         tabulated in table 3.2.3-1.


  ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

 CHANNEL    BAUD-   INTERFACE     SYNC/    ALPHABET   NOTES
            RATE                  ASYNC
  ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

 VDU        1̲2̲0̲0̲
            2400    V24/Opto      Async.   ITA NO.5   1,
                                                      2,
                                                      3
             ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
            ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

            1200    V24/V28(L/L)  Async.   ITA NO.5   2,
                                                      3
  ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

 MSP        1̲2̲0̲0̲
            2400    V24/Opto      Async.   ITA NO.5   1,
                                                      2,
                                                      3
             ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
            ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

            1200    V24/V28(L/L)  Async.   ITA NO.5   2,
                                                      3
  ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

 Auxiliary  1200    V24/V28(L/L)  Async.   ITA NO.5   2,
                                                      3
  ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

 OCR        1200    V24/V28(L/L)  Async.   ITA NO.5   2,
                                                      3
 (Optional)
  ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

 Crypto/    2̲4̲0̲0̲
 Modem      4800    V24/V28(L)    Sync.    Stat. Mux. 1,
                                                      2,
                                                      3
                                           Protocol
  ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲




 Notes: See next page


                  T̲A̲B̲L̲E̲ ̲3̲.̲2̲.̲3̲-̲1̲


                 N̲O̲T̲E̲S̲ ̲F̲O̲R̲ ̲T̲A̲B̲L̲E̲ ̲3̲.̲2̲.̲3̲-̲1̲



         1)  Baud-rate       Underlined baud-rates will be used
                             during acceptance tests.

         2)  Interface

             a)  Opto        Transmision at remote site between
                             the EMI shielded rack and the terminals
                             will be by an optical transmission
                             link.

             b)  V28(L)      Transmision between the Stat. Mux.
                             in the EMI shielded rack and the
                             Crypto equipment (via the BPJF)
                             will be by a V28(L) electrical
                             transmission link. V28(L) is CCITT
                             V28, constrained by MIL-STD-188C
                             (standard low level) except for
                             voltage polarities. Transmission
                             length is up to 15 meters.

             c)  V28(L/L)    Transmission at remote site between
                             the EMI shielded rack and the terminals/auxiliary
                             channels will be by a V28(L/L)
                             electrical transmission link. V28(L/L)
                             equals V28(L), but enables transmission
                             length up to 275 meter.

         3)  Alphabet

             a)  ITA No.5    International Telegraph Alphabet,
                             CCITT recommended, ASCII code.

             b)  Stat. Mux.  Communication between Stat. Muxes
                 Protocol    follows a data protocol unique
                             to the Stat. Muxes.




3.2.4    S̲p̲e̲c̲i̲f̲i̲c̲ ̲E̲q̲u̲i̲p̲m̲e̲n̲t̲ ̲C̲h̲a̲r̲a̲c̲t̲e̲r̲i̲s̲t̲i̲c̲s̲



3.2.4.1  C̲r̲y̲p̲t̲o̲/̲M̲o̲d̲e̲m̲

         1)  I̲n̲t̲e̲r̲f̲a̲c̲e̲:̲      Synchronous V24 interface with
                             speed of 2400 or 4800 bps, supporting
                             the following interchange circuits:

                             101    Protective Ground
                             102    Signal Ground
                             103    Transmitted Data
                             104    Received Data
                             105    Request to Send
                             106    Ready for Sending
                             109    Carrier Detect
                             114    Transmitter signal element
                                    timing
                             115    Receiver Signal element
                                    timing.



3.2.4.2  M̲e̲d̲i̲u̲m̲ ̲S̲p̲e̲e̲d̲ ̲P̲r̲i̲n̲t̲e̲r̲s̲

         CR-supplied TRACOR MSPs model 8000 RO. The Medium Speed
         Printer has an optical or a V28 interface.



3.2.4.3  V̲i̲s̲u̲a̲l̲ ̲D̲i̲s̲p̲l̲a̲y̲ ̲U̲n̲i̲t̲s̲

         CR-supplied Delta Data VDUs model 7260 T. The Visual
         Display Unit has an optical or a V28 Interface.







3.3      P̲H̲Y̲S̲I̲C̲A̲L̲ ̲C̲H̲A̲R̲A̲C̲T̲E̲R̲I̲S̲T̲I̲C̲S̲



3.3.1    P̲o̲w̲e̲r̲ ̲I̲n̲p̲u̲t̲

         The CRT equipment shall be capable of satisfying the
         specified performance requirements when operating with
         the following power input:

         a)  Phases:        Single-phase and ground.

         b)  Voltage:       Nominal value: 220 V AC
                            Tolerances: +10%/-15%
                            Except UKAIR where nominal value
                            is 240 V AC.

         c)  Frequency:     Nominal value: 50 Hz
                            Tolerances: +10/-10%

         d)  Harmonic
             distortion:    Max. 5%

         e)  Transients:    Non-repetitive impulsive interference
                            with a magnitude not to exceed 500
                            volts, pulse rise and fall times
                            not faster than 10 microseconds
                            and a total duration of maximum
                            1 millisecond. The available impulse
                            energy at the equipment power inlet
                            shall not exceed 5J.



3.3.2    E̲n̲v̲i̲r̲o̲n̲m̲e̲n̲t̲a̲l̲ ̲C̲o̲n̲d̲i̲t̲i̲o̲n̲s̲

         In designing the equipment to meet the specified requirements
         no account need be taken of catastrophic events such
         as fire, flood, explosion, etc., which are beyond the
         control of an equipment manufacturer.

         The equipment will normally operate within accomodation
         suitable for the operation of equipment produced for
         commercial use.

         After initial adjustments have been made, the equipment
         shall maintain normal operation under all specified
         environmental and power supply conditions.


3.3.2.1  T̲e̲m̲p̲e̲r̲a̲t̲u̲r̲e̲ ̲a̲n̲d̲ ̲H̲u̲m̲i̲d̲i̲t̲y̲

         The equipment shall continue to function when the humidity
         and temperature of its environment are within the ranges
         and cycling specified below.

         The equipment shall continue to operate in a fully
         satisfactory manner even under the worst conditions
         specified below.

         a)  T̲e̲m̲p̲e̲r̲a̲t̲u̲r̲e̲

             Range:              10 to 40 deg.C
             Rate of Change:     max 10 deg. C per hour

         b)  H̲u̲m̲i̲d̲i̲t̲y̲ ̲(̲R̲e̲l̲a̲t̲i̲v̲e̲ ̲H̲u̲m̲i̲d̲i̲t̲y̲ ̲=̲ ̲R̲H̲)̲

             Range:              40 to 90% RH, non-condensing
             Rate of Change:     max. 6% RH per hour, non-condensing.

         c)  A̲l̲t̲i̲t̲u̲d̲e̲

             Range:              Sea level to 2000 meter.



3.3.2.2  D̲u̲s̲t̲,̲ ̲F̲u̲m̲e̲s̲

         The equipment shall be able to operate continuously
         and with normal scheduled preventive maintenance in
         the following air environment:

         a)  A̲i̲r̲ ̲c̲l̲e̲a̲n̲n̲e̲s̲s̲

             Particle size       Max. allowable number
             (microns)           (particles/cubicmeter)
          ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

             greater than 5      4* (10  5)
             greater than 1.5    4* (10  6)
             greater than 1      4* (10  7)

         b)  F̲u̲m̲e̲s̲

             sulphur dioxide max. 14 ppm.


3.4      S̲E̲C̲U̲R̲I̲T̲Y̲

         This section addresses or references all requirements
         related to security.

         In general: Transfer and transmission within the installation
         means transfer and transmission between the components.



3.4.1    T̲E̲M̲P̲E̲S̲T̲ ̲A̲c̲c̲e̲p̲t̲a̲n̲c̲e̲

         The CR delivered components of the CRT equipment at
         the main sites are contained in a 1- or 2-bay rack
         bolted to the CAMPS 3-bay Line Termination Rack Assembly,
         except for UKAIR, where the CRT rack is freestanding.

         The CR delivered components of the CRT equipment at
         the remote sites are contained in an EMI shielded rack,
         except the VDUs and MSPs

         During short periods of corrective and preventive maintenance
         e.g. open back doors, the emanation requirements below
         are degraded.

         Operational procedures are required to ensure that
         the supervisor is currently informed on activities
         concerning corrective and preventive maintenance and
         thus is able to decide whether it is acceptable to
         continue operation or not.

         a)  The E̲M̲I̲ ̲s̲h̲i̲e̲l̲d̲e̲d̲ ̲r̲a̲c̲k̲s̲ used for CR delivered CRT
             equipment are manufactured for the same performance
             as the EMI shielded racks used for CAMPS.

         b)  To meet the i̲n̲s̲t̲a̲l̲l̲a̲t̲i̲o̲n̲ ̲r̲e̲q̲u̲i̲r̲e̲m̲e̲n̲t̲s̲, the equipment,
             including ancillaries and peripherals, must be
             installed in accordance with criteria laid down
             in AMSG 719B. After installation, a COMSEC Radiation
             Survey will be carried out at each location prior
             to operational approval being given. Rectification
             of equipment shortcomings shall be the responsibility
             of the contractor.



         c)  S̲p̲e̲c̲i̲a̲l̲ ̲e̲a̲r̲t̲h̲i̲n̲g̲ ̲a̲r̲r̲a̲n̲g̲e̲m̲e̲n̲t̲s̲, see section 3.7.1.2.5
             a,b,c,d.

         d)  All e̲l̲e̲c̲t̲r̲i̲c̲a̲l̲ ̲i̲n̲t̲e̲r̲c̲o̲n̲n̲e̲c̲t̲i̲o̲n̲s̲,̲ connecting equipment
             inside to equipment outside the EMI shielded rack,
             will be by low level keying systems, V28(L), i.e.
             the electrical interface specification shall comply
             with the V28 recommendation concerning the data
             and control signal voltage polarities, while all
             other characteristics (e.g. currents, rise and
             fall time, impedance, voltage levels) are governed
             by the MIL-STD-188C (Low level) standard digital
             interface specification.

         e)  On send circuits the pulse form shall be measured
             at the connectors of the filter box. Limits shall
             be met at this r̲e̲f̲e̲r̲e̲n̲c̲e̲ ̲p̲l̲a̲n̲e̲ with the circuits
             terminated with loads according to MIL-STD-188C.

         f)  I̲n̲s̲t̲a̲l̲l̲a̲t̲i̲o̲n̲ ̲w̲o̲r̲k̲ will be checked by local COMSEC
             staff to ensure that all installation conforms
             to COMSEC requirements.

         g)  The C̲R̲T̲ ̲s̲t̲a̲t̲.̲m̲u̲x̲ ̲l̲i̲n̲e̲ between the mainsites and
             the remote sites will be equipped with on-line
             synchronous cryptographic equipment to be supplied,
             installed and maintained by the customer.

         h)  The C̲R̲T̲ ̲e̲q̲u̲i̲p̲m̲e̲n̲t̲ will be installed in an area
             designated as a R̲e̲d̲ ̲A̲r̲e̲a̲. Within the Red Area classified
             information may be handled in plain language; the
             transfer of information in an electrical form within
             this area shall be subject to and comply with the
             criteria laid down in AMSG 719B.

         i)  The c̲r̲o̲s̲s̲t̲a̲l̲k̲ ̲a̲t̲t̲e̲n̲u̲a̲t̲i̲o̲n̲ between any circuit carrying
             classified information and any other circuit within
             the installation shall be not less than 100 dB.

         j)  The p̲o̲w̲e̲r̲ ̲s̲u̲p̲p̲l̲y̲ to all the equipment in the Red
             Area will enter via a f̲i̲l̲t̲e̲r̲ or a group of filters
             which will be supplied by the customer. The function
             of these filters is to ensure that no compromising
             signals are able to reach a Black Area via the
             power supply leads. The equipment shall function
             satisfactorily with these filters present in the
             power leads.


3.5      C̲O̲N̲S̲T̲R̲U̲C̲T̲I̲O̲N̲ ̲R̲E̲Q̲U̲I̲R̲E̲M̲E̲N̲T̲S̲



3.5.1    G̲e̲n̲e̲r̲a̲l̲

         The following section defines the general construction
         requirements applicable to CRT.



3.5.1.1  E̲q̲u̲i̲p̲m̲e̲n̲t̲ ̲P̲r̲o̲d̲u̲c̲e̲d̲ ̲b̲y̲ ̲C̲h̲r̲i̲s̲t̲i̲a̲n̲ ̲R̲o̲v̲s̲i̲n̲g̲ ̲A̲/̲S̲

         a)  The CR produced equipment is designed and produced
             according to CR standard, CPS/STM/001 sections
             A-C, A-D and A-E.

         b)  Maintenance of CR standards are performed under
             configuration management and supervised by CRs
             Quality Assurance department.

         c)  All standards and their maintenance may be inspected
             by customers Quality Assurance Representative.



3.5.1.2  E̲q̲u̲i̲p̲m̲e̲n̲t̲ ̲P̲r̲o̲d̲u̲c̲e̲d̲ ̲b̲y̲ ̲S̲u̲b̲c̲o̲n̲t̲r̲a̲c̲t̲o̲r̲s̲

         The CR sub-contractor supplying equipment to CAMPS/CRT
         may propose the use of other standards, on condition
         that adequate documentary evidence is provided to demonstrate
         that the alternative standards are at least equivalent
         in scope and depth of coverage to this requirement
         section.



3.5.1.3  P̲r̲o̲d̲u̲c̲t̲s̲ ̲F̲r̲o̲m̲ ̲O̲t̲h̲e̲r̲ ̲S̲u̲p̲p̲l̲i̲e̲r̲s̲

         a)  Equipment supplied by OEMs not quoted as sub-contractors
             - i.e. standard equipment from stock - is chosen
             in accordance with the requirements stated compared
             to the specification given by the OEMs.



         b)  Quality Assurance shall check and ensure that the
             quality of such equipment fulfil all requirements
             in respect to:

             1)      performance (in accordance with specifications
                     given by manufacturer)

             2)      durability

             3)      stability under extreme working condition

             4)      maintainability



3.5.2    S̲p̲e̲c̲i̲a̲l̲ ̲R̲e̲q̲u̲i̲r̲e̲m̲e̲n̲t̲s̲ ̲f̲o̲r̲ ̲t̲h̲e̲ ̲C̲R̲T̲ ̲S̲y̲s̲t̲e̲m̲

         In this section is mentioned a number of requirements
         special for the CRT project.



3.5.2.1  U̲t̲i̲l̲i̲t̲y̲ ̲O̲u̲t̲l̲e̲t̲ ̲S̲o̲c̲k̲e̲t̲s̲

         Utility outlet sockets for the operation of test equipment
         etc. shall be located in close proximity to all major
         racks or cabinets. Installation of utility outlets
         will be the responsibility of customer.



3.5.2.2  B̲e̲n̲c̲h̲ ̲H̲a̲n̲d̲l̲i̲n̲g̲

         Smaller assemblies and sub-assemblies normally subject
         to bench repair shall be capable of withstanding being
         dropped onto a hard surface on all faces from a 30…0e…0…0f…
         angle, using any one edge of the unit as a pivot, without
         any physical, electrical or electronic damage.



3.5.2.3  W̲i̲r̲i̲n̲g̲

         Wiring shall be identified by colour coding, numbering,
         or by other feasible means such as marking of terminals
         at both ends of lead. All wires shall carry corresponding
         identification numbers. Colour coding for chassis wiring
         shall comform to good engineering practice.


3.5.2.4  V̲e̲n̲t̲i̲l̲a̲t̲i̲o̲n̲ ̲a̲n̲d̲ ̲C̲o̲o̲l̲i̲n̲g̲

         The distributed cooling systems in the CR produced
         equipment may be supplied with air filters of a nominal
         thickness of 2.5 cm. The cooling air should preferably
         be exhausted to the atmosphere at the top of the cabinet.



3.5.2.5  N̲a̲m̲e̲p̲l̲a̲t̲e̲s̲ ̲a̲n̲d̲ ̲P̲r̲o̲d̲u̲c̲t̲ ̲M̲a̲r̲k̲i̲n̲g̲

         a)  A nameplate giving the serial number, SHAPE contract
             number, date of manufacture, manufacturers name
             and address, and principal characteristics where
             appropriate, shall be attached in a prominent position
             on each major assembly.

         b)  Cables and wires or similar connectors shall carry
             a CR parts number. These numbers shall be the same
             numbers as given in the documentation.



3.5.2.6  S̲a̲f̲e̲t̲y̲

         All necessary safeguards shall be taken during the
         design, development, production and installation of
         the equipment to ensure safety of operating and maintenance
         personnel from electrical and mechanical hazards.



3.5.2.6.1    R̲e̲g̲u̲l̲a̲t̲i̲o̲n̲s̲

         a)  The actual site installations in the different
             host nations shall be made in accordance with the
             appropriate National Safety Regulations of the
             country concerned according to installation drawings
             as approved by the purchases.

         b)  The equipment itself and its associated power cabling
             shall comply with the National Safety Regulations
             of the country of origin for the equipment.





3.5.2.6.2    P̲e̲r̲s̲o̲n̲n̲e̲l̲ ̲S̲a̲f̲e̲t̲y̲

         a)  Interlocks or key locks shall be incorporated where
             appropriate to prevent any major assembly carrying
             high tension voltages from being opened by unauthorised
             personnel.

         b)  With the equipment assembled and set up for operation,
             personnel shall be protected from contact with
             potentials in excess of 30 volts to ground, chassis
             or frame, including potentials or charged capacitors.

         c)  Relevant notice and markings on equipment or documents
             are to be provided to draw the attention of operating
             and maintenance personnel to points where dangerous
             voltages may be encountered.

         d)  Where a voltage of 50 or more volts is exposed
             during the maintenance activities a suitable warning
             shall be provided. It should be made according
             to the following principles:

             1) "DANGER (xxx) VOLTS WHEN COVER REMOVED" (in
                aluminium or white lettering l.5 cm high on
                a red background) where (xxx) is the nominal
                voltage.

             2) "DANGER HIGH VOLTAGE (xxx) VOLTS" where (xxx)
                is the nominal voltage.

             3) "CAUTION (xxx) VOLTS. DISCONNECT POWER BEFORE
                REMOVAL OF COVER" where (xxx) is the nominal
                voltage.



3.5.2.6.3    E̲q̲u̲i̲p̲m̲e̲n̲t̲ ̲S̲a̲f̲e̲t̲y̲

         a)  Circuit breakers or switches which operate to make
             or break AC power lines shall make or break all
             conductors at the same time. The neutral wire in
             three-phase circuits shall not pass through any
             fuse.



         b)  Fuses and circuit breakers shall be provided within
             the equipment as required for protection of the
             equipment from damage due to overload. Each major
             assembly shall be individually protected so that
             a fault in one major assembly cannot damage any
             other major assembly.

         c)  All fuses and circuit breakers should be located
             such that they are readily accessible. Fuses shall
             incorporate a visual system of failure indication.



3.5.2.6.4    G̲r̲o̲u̲n̲d̲i̲n̲g̲

         a)  The grounding system shall provide effective protection
             for personnel and material against insulation defects.
             It shall be arranged so that there are four separate
             and isolated ground circuits, namely:

             1) AC power neutral
             2) Equipment frame ground
             3) Signalling and control ground
             4) Secure ground

         b)  The AC power neutral shall provide a return for
             the primary current so that the equipment frame
             ground is used only to establish a safety ground
             and is not used as a normal current grounding element.
             No place in the equipment or power filters shall
             the AC power neutral be connected directly to equipment
             frame ground.

         c)  All panels, drawers and other sub-assemblies, whether
             fixed or removable, shall be fastened, or connected
             to the associated frame, in a manner that ensures
             they are securely grounded.

         d)  The signalling and control ground is to be routed
             via the interconnecting wires and cables as appropriate.

         e)  The cryptographic ground shall conform to the requirements
             of AMSG 719B.





3.6      C̲R̲T̲ ̲D̲O̲C̲U̲M̲E̲N̲T̲A̲T̲I̲O̲N̲

         The hardware documentation developed by CR under this
         contract will be produced in accordance with the requirements
         applicable for CAMPS.

         This section gives a detailed table of contents for
         the CRT Equipment Handbook, which constitutes the CRT
         documentation. Each section of the Equipment Handbook
         contains a short abstract.



3.6.1    H̲e̲a̲d̲l̲i̲n̲e̲s̲ ̲t̲o̲ ̲t̲h̲e̲ ̲C̲R̲T̲ ̲E̲q̲u̲i̲p̲m̲e̲n̲t̲ ̲H̲a̲n̲d̲b̲o̲o̲k̲

         The CRT Equipment Handbook contains the main sections
         as specified below:

         TABLE OF CONTENTS
         LIST OF ILLUSTRATIONS
         LIST OF TABLES



         1   SCOPE OF MANUAL
         2   INTRODUCTION
         3   SPECIFICATIONS
         4   CONNECTIONS
         5   DETAILED FUNCTIONAL DESCRIPTION
         6   INSTALLATION
         7   OPERATING INSTRUCTIONS
         8   MAINTENANCE AND SERVICING
         9   ASSEMBLY BREAK DOWN
         10  INVENTORY
         11  SPARE PARTS LIST
         12  CIRCUIT BOARDS, MODULES AND DIAGRAMS



3.6.2    C̲o̲n̲t̲e̲n̲t̲s̲ ̲o̲f̲ ̲C̲R̲T̲ ̲E̲q̲u̲i̲p̲m̲e̲n̲t̲ ̲H̲a̲n̲d̲b̲o̲o̲k̲

         The specifications and descriptions of the handbook
         shall be preceded by

         a)  TABLE OF CONTENTS
         b)  LIST OF ILLUSTRATIONS
         c)  LIST OF TABLES



3.6.2.1  S̲c̲o̲p̲e̲ ̲o̲f̲ ̲M̲a̲n̲u̲a̲l̲

         This section contains a general overview of the handbook.



3.6.2.2  I̲n̲t̲r̲o̲d̲u̲c̲t̲i̲o̲n̲

         1)  S̲y̲s̲t̲e̲m̲ ̲o̲v̲e̲r̲v̲i̲e̲w̲

             This section gives a general description of the
             CRT system.

         2)  N̲o̲m̲e̲n̲c̲l̲a̲t̲u̲r̲e̲ ̲a̲n̲d̲ ̲a̲b̲b̲r̲e̲v̲i̲a̲t̲i̲o̲n̲s̲

             The terms and abbreviations used in the handbook
             are explained in this section.

         3)  D̲o̲c̲u̲m̲e̲n̲t̲a̲t̲i̲o̲n̲ ̲R̲e̲f̲e̲r̲e̲n̲c̲e̲

             The documents relevant and applicable to the user
             of the handbook are referenced.


         4)  F̲u̲n̲c̲t̲i̲o̲n̲a̲l̲ ̲B̲l̲o̲c̲k̲ ̲D̲i̲a̲g̲r̲a̲m̲

             This section comprises a functional block diagram
             together with a description of the block functions.
             It also describes the units and modules used for
             the implementation of the CRT.

         5)  I̲n̲t̲e̲r̲a̲c̲t̲i̲o̲n̲ ̲w̲i̲t̲h̲ ̲s̲u̲r̲r̲o̲u̲n̲d̲i̲n̲g̲s̲

             This section gives a general overview of the communication
             between CAMPS and Remote Terminals, including the
             VDUs, MSPs, auxilliary V28(L/L) connections and
             OCR.

         6)  I̲/̲O̲ ̲M̲o̲d̲e̲s̲ ̲a̲n̲d̲ ̲F̲o̲r̲m̲a̲t̲s̲

             This section gives a general overview of the modes
             and formats of the data communication of the I/O
             connections.



3.6.2.3  S̲p̲e̲c̲i̲f̲i̲c̲a̲t̲i̲o̲n̲s̲

         1)  O̲p̲e̲r̲a̲t̲i̲o̲n̲a̲l̲ ̲S̲p̲e̲c̲i̲f̲i̲c̲a̲t̲i̲o̲n̲s̲

             a) User Safety and Warnings.
                The user safety precautions and warnings shall
                be explained. These will be placed on the inner
                side of the handbook cover.

             b) Environmental Requirements/Specifications. The
                environmental limits of the equipment are specified
                here.

         2)  S̲y̲s̲t̲e̲m̲ ̲S̲p̲e̲c̲i̲f̲i̲c̲a̲t̲i̲o̲n̲s̲

             a) Electrical Specifications
             b) Mechanical Specifications





3.6.2.4  C̲o̲n̲n̲e̲c̲t̲i̲o̲n̲s̲

         This section includes a drawing, showing the physical
         layout and the interconnections between the racks at
         the Main Site and between the racks and I/O equipment
         at the Remote Site (auxiliary V28(L/L), OCR and opto
         to VDUs and MSPs). It also includes a description of
         the different I/O connectors including pin designation
         and numbering.



3.6.2.5  D̲e̲t̲a̲i̲l̲e̲d̲ ̲F̲u̲n̲c̲t̲i̲o̲n̲a̲l̲ ̲D̲e̲s̲c̲r̲i̲p̲t̲i̲o̲n̲

         This section will describe in detail the function of
         the different modules including references to the relevant
         diagrams and manuals.



3.6.2.6  I̲n̲s̲t̲a̲l̲l̲a̲t̲i̲o̲n̲

         1)  Storage, Transport and Unpacking.
             This section will include a reference to the applicable
             CAMPS procedure concerning storage, transport and
             unpacking.

         2)  Assembly.
             This section gives a detailed description of the
             configuration and the reconfiguration possibilities.



3.6.2.7  O̲p̲e̲r̲a̲t̲i̲n̲g̲ ̲I̲n̲s̲t̲r̲u̲c̲t̲i̲o̲n̲s̲

         This section describes the operating procedures and
         controls, applicable to the CRT and a reference to
         the proper CAMPS Manual.



3.6.2.8  M̲a̲i̲n̲t̲e̲n̲a̲n̲c̲e̲

         This section references the CAMPS Maintenance instructions.





3.6.2.9  A̲s̲s̲e̲m̲b̲l̲y̲ ̲B̲r̲e̲a̲k̲d̲o̲w̲n̲

         This section includes an Assembly Breakdown for the
         CRT equipment.



3.6.2.10 I̲n̲v̲e̲n̲t̲o̲r̲y̲

         This section incorporates a consumerable and item listing.



3.6.2.11 S̲p̲a̲r̲e̲ ̲P̲a̲r̲t̲s̲ ̲L̲i̲s̲t̲

         This section contains the spare parts list for the
         Remote Site equipment, and a reference to the CAMPS
         spare parts list for the Main Site equipment.



3.6.2.12 C̲i̲r̲c̲u̲i̲t̲ ̲B̲o̲a̲r̲d̲s̲ ̲a̲n̲d̲ ̲D̲i̲a̲g̲r̲a̲m̲s̲

         The Preset adjustments and settings are pointed out
         in this section. This section also comprises the diagrams
         and photos of the Circuit Boards.



3.6.3    F̲i̲e̲l̲d̲ ̲M̲o̲d̲i̲f̲i̲c̲a̲t̲i̲o̲n̲ ̲D̲o̲c̲u̲m̲e̲n̲t̲s̲

         All field modification documents generated by CR will
         be submitted to SHAPE logistics function for distribution
         to the respective main sites. The maintenance at of
         the main sites will in turn be responsible for implementation
         of the changes to the remote equipment.





3.7      L̲O̲G̲I̲S̲T̲I̲C̲ ̲R̲E̲Q̲U̲I̲R̲E̲M̲E̲N̲T̲S̲



3.7.1    T̲r̲a̲n̲s̲p̲o̲r̲t̲a̲t̲i̲o̲n̲ ̲a̲n̲d̲ ̲I̲n̲s̲t̲a̲l̲l̲a̲t̲i̲o̲n̲



3.7.1.1  T̲r̲a̲n̲s̲p̲o̲r̲t̲a̲t̲i̲o̲n̲

         The CAMPS Remote Terminal (CRT) Equipment provided
         by CR will be shipped together with CAMPS Main Site
         Equipment as specified in the CAMPS Transportation
         Plan, CPS/PLN/007.

         Packing, marking and shipping documentation will be
         as required for Mainsite Equipment and therefore as
         described in the Transportation Plan.



3.7.1.2  I̲n̲s̲t̲a̲l̲l̲a̲t̲i̲o̲n̲



3.7.1.2.1    E̲q̲u̲i̲p̲m̲e̲n̲t̲ ̲I̲n̲s̲t̲a̲l̲l̲a̲t̲i̲o̲n̲ ̲a̲t̲ ̲M̲a̲i̲n̲ ̲S̲i̲t̲e̲s̲

         a)  At the applicable main sites CR will provide and
             install a CRT-rack (at Proto 2 CRT-racks are required)
             in the CAMPS room. (refer to fig. 3.2.1.1). The
             rack(s) will be bolted to the 3-bay CAMPS line
             termination rack assembly (D,E,F) except at UKAIR,
             where a stand alone rack will be installed. The
             rack(s) will be designated as rack G, (H).

         b)  SHAPE will provide and install the red patch Jack
             field (RPJF), the BID 1000, the black patch Jack
             field (BPJF) and the modem. 

         c)  The signal cable and connections from the filter
             box of rack F to the RPJF, from the RPJF to the
             BID 1000 from the BID 1000 to the BPJF, from the
             BPJF to the modem and from the modem to the Main
             Distribution Frame (MDF) will be provided and installed
             by SHAPE/Host Nation.



             Rack G(H) requires a secure ground and pink power
             from the CAMPS power distribution board. SHAPE/Host
             Nation will provide this power and ground in accordance
             with the Civil Works Requirement (CWR) for each
             site.



3.7.1.2.2    E̲q̲u̲i̲p̲m̲e̲n̲t̲ ̲I̲n̲s̲t̲a̲l̲l̲a̲t̲i̲o̲n̲ ̲a̲t̲ ̲R̲e̲m̲o̲t̲e̲ ̲L̲o̲c̲a̲t̲i̲o̲n̲s̲

         a)  At remote locations CR will provide and install
             a CRT-rack and the contractual specified number
             of   user terminals. This equipment will be installed
             in rooms designated by SHAPE/Local Commands (Refer
             to fig. 3.2.1-1).

         b)  The signal cable and connections from filter box
             of the CRT-rack to the RPJF, from the RPJF to the
             BID 1000, from the BID 1000 to the modem and from
             the modem to the MDF will be provided and installed
             by SHAPE/Host Nation. The connectors to be used
             in the Filter box of the CRT-rack will be provided
             by CR.

         c)  The OCR connection and the auxiliary V28(L/L) connections
             to the filter box of the CRT-rack will  be provided
             and installed by SHAPE/Host Nation.


         d)  SHAPE/Host Nation will run the Opto-cables between
             the CRT-rack and the terminals in conduits or ducts
             provided and installed by SHAPE/Host Nation. The
             Opto-cables will be provided by CR, and terminated
             and connected to the CRT-rack and the terminals
             by CR.

         e)  CR will provide a set of space and power requirements
             for each remote location which will be incorporated
             in the related main site CWR-package.

         f)  The CRT-rack requires a secure ground and pink
             power. SHAPE/Host Nation will provide this power
             and ground in accordance with the CWR. The user
             terminals will be supplied with power (pink or
             black) and ground (secure or safety) from SHAPE/Host
             Nation provided 3-pin outlets in accordance with
             the CWR.





3.7.1.2.3    S̲t̲a̲n̲d̲a̲r̲d̲s̲ ̲a̲n̲d̲ ̲S̲e̲c̲u̲r̲i̲t̲y̲

         a)  The equipment shall operate from mains power installations
             conforming to national regulations concerning power
             and safety.

         b)  CR will ensure that As-To-Be-Built drawings submitted
             to SHAPE will conform to national safety regulation.

         c)  SHAPE will approve the As-To-Be-Built drawings
             for conformance to ACE COMSEC regulations and will
             obtain approval of the completed installation from
             national authorities.

         d)  The CRT installations at main and remote sites
             shall conform with the relevant requirements for
             automatic processing devices contained in the current
             issue of AMSG719B. The AMSG719B requirements have
             been adapted to CAMPS as described in document
             CPS/TCN/023 (CAMPS Site Design Concept)

         e)  Customers local COMSEC staff shall monitor the
             installation works. A final test and inspection
             before each installation becomes operative will
             be carried out by an ACE-COMSEC team.



3.7.1.2.4    P̲o̲w̲e̲r̲ ̲S̲u̲p̲p̲l̲y̲ ̲a̲n̲d̲ ̲P̲o̲w̲e̲r̲ ̲D̲i̲s̲t̲r̲i̲b̲u̲t̲i̲o̲n̲

         a)  220V/50Hz Power supplies will be provided by SHAPE/Host
             Nation at all main and remote sites except UKAIR
             where the nominel voltage is 240V.

         b)  If consistent with national regulations the following
             colour coding shall apply:

             Line:               Brown
             Neutral:            Blue
             Ground:             Yellow/green

             In conformance with national regulations each end
             of the neutral and ground wire shall be clearly
             marked (coloured sleeves or coloured durable adhesive
             tape).



         c)  Protective devices for the mains power installation
             shall be provided by SHAPE/Host Nation.
             Circuit breakers which operate to make or break
             A.C. power lines shall make or break all conductors
             at the same time. The neutral wire shall not pass
             through any fuse. All fuses and circuit breakers
             shall be so located such that they are readily
             accessible.

         d)  Utility outlet sockets for operation of each terminal
             shall be specified in the CWR and provided by SHAPE/Host
             Nation as close as possible to the required installation
             site of a terminal. The outlet sockets shall be
             of a uniform 220V A.C. standard type with ground
             and break of line according to the national standard
             for each installation. The socket shall be of a
             type that only allows the plug to mate in the correct
             orientation.

         e)  Contractor shall provide his requirements for the
             power installation specifying the required number
             of utility outlet sockets as part of the Civil
             Works Requirements Package.

         f)  Customer will provide for Standard Power Cables
             laid in unperforated sheet metal ducts with lids
             or conduits (fixed or flexible) in the room at
             the remote location where the CRT-rack are installed.



3.7.1.2.5    G̲r̲o̲u̲n̲d̲i̲n̲g̲

         a)  CRT at mainsites: The grounding concept for CAMPS
             main sites shall apply. (Ref. CPS/TCN/023).

         b)  CRT-racks at remote locations will be provided
             with a secure ground by SHAPE/Host Nation. The
             ground may be the third wire of a 3wire power-cable
             from the power distribution board to the CRT-rack
             or a separate wire run within the same conduit.



         c)  SHAPE/Host Nation will provide CRT-terminals with
             3pin power outlets, the third wire of which will
             provide either a secure or safety ground. The ground
             wire may be the third wire of a 3wire power cable
             from the power distribution board to the power
             outlet or a separate wire run within the same conduit.

         d)  Both grounds (secure and safety) shall conform
             to national regulations.



3.7.1.2.6    S̲p̲a̲c̲e̲ ̲a̲n̲d̲ ̲A̲c̲c̲e̲s̲s̲

         a)  The space required for the CRT-rack at the remote
             location will be specified by CR as part of the
             CAMPS CWR.

         b)  A minimum floor to ceiling height of 220 cm. without
             a raised floor or 2 meters minimum in case of a
             raised floor will be provided in the room at the
             remote location where the CRT-rack is installed.

         The following dimensions are required as the minimum
         envelope along the equipment access route of any site:

         Height      1.70 meters
         Width       0.65 meters
         Length      3.70 meters



3.7.1.2.7    S̲i̲t̲e̲ ̲S̲u̲r̲v̲e̲y̲s̲

         a)  Immediately following contract award CR will perform
             formal site surveys at each remote terminal site,
             if appropriate. A site survey questionnaire will
             be completed by each site and submitted to CR.
             If the questionnaire is considered complete, a
             site survey may not be necessary.

         b)  If a survey is considered necessary, subject to
             coordination with CR, SHAPE will arrange a visit
             ot the site. The purpose of the site survey is
             to ensure that the contractor has collected the
             necessary information to prepare CWR and As-To-Be-Built
             drawings.



         c)  SHAPE representatives will assist contractor to
             collect the relevant information to be used to
             prepare the site for installation of the CRT equipment.
             At least one of SHAPE representatives on each site
             survey team will be authorized to make decisions
             and to sign a survey protocol on behalf of SHAPE.

         d)  S̲i̲t̲e̲ ̲D̲o̲c̲u̲m̲e̲n̲t̲a̲t̲i̲o̲n̲

             1) During the site survey, the contractor will
                gather all information needed for preparation
                of Civil Works Requirements, As-To-Be-Built
                drawings, and As-Built drawings. The contractor
                will also provide general CRT system information
                to the Host Nation to support the Host Nation's
                preliminary design of site preparation works.

             2) It is anticipated that the contractor will be
                required to make only one site survey at each
                site. It is the responsibility of SHAPE that
                all necessary information is available to the
                contractor. If one or more subsequent site visits
                are required because of a contractor omission
                during the original site survey such visit(s)
                shall be the responsibility of the contractor.
                If subsequent survey effort is required because
                of a failure by SHAPE or the site users to fulfil
                their obligations such survey effort shall not
                be carried out before a mutual agreement between
                the contractor and SHAPE has been reached.

             3) The contractor's planning baseline for preparation
                of Civil Works Requirements is the site survey,
                or site survey questionnaire. If SHAPE advises
                the contractor of site modifications accomplished
                after the site survey, the contractor will incorporate
                these changes into his Civil Works Requirements
                provided that he is notified of the changes
                no later than 3 months prior to either the contractually
                specified submission date or the actual submission
                date, whichever is later.

             4) The approved Civil Works Requirements are the
                Contractor's planning baseline for his preparation
                of As-To-Be-Built drawings. SHAPE is responsible
                to ensure that any site modifications made after
                Civil Works Requirements approval are identified
                to the contractor for his incorporation into
                the


                As-To-Be-Built Drawings. The contractor shall
                incorporate these changes in the As-To-Be-Built
                drawings provided the changes are identified
                to the contractor no later than 2 1/2 months
                prior to either the contractually specified
                submission date or the actual submission date,
                whichever is later.



3.7.2    M̲a̲i̲n̲t̲e̲n̲a̲n̲c̲e̲ ̲a̲n̲d̲ ̲S̲u̲p̲p̲o̲r̲t̲

         If an error is detected at the remote site, the user
         may replace a suspected terminal with a spare one.
         The same applies for the Statistical Multiplexer. If
         the fault cannot be rectified by the user at the remote
         site, the maintenance personnel at the corresponding
         main site must be called upon. Preventive maintenance
         must likewise be carried out by personnel from the
         main site and/or remote site.



3.7.3    S̲p̲a̲r̲e̲s̲ ̲a̲n̲d̲ ̲C̲o̲d̲i̲f̲i̲c̲a̲t̲i̲o̲n̲



3.7.3.1  S̲u̲p̲p̲l̲y̲ ̲o̲f̲ ̲P̲a̲r̲t̲s̲

         The current maintenance philosophy is based on one
         spare statistical multiplexer available at the remote
         terminal location. These units can be replaced by the
         user.

         Contractor will not specify any spareparts for the
         remote terminal location.



3.7.3.2  N̲A̲T̲O̲ ̲C̲o̲d̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

         Subassemblies will be codified in accordance with the
         CRT contract.





3.7.4    T̲r̲a̲i̲n̲i̲n̲g̲

         In accordance with CR's proposals and Letter of Intent
         from customer no formal training is contemplated on
         CRT equipment.











                  4̲ ̲ ̲S̲Y̲S̲T̲E̲M̲ ̲V̲E̲R̲I̲F̲I̲C̲A̲T̲I̲O̲N̲



         This section specifies the quality assurance provisions
         applicable to verify the equipment. It also identifies
         the associated verification documentation.



4.1      T̲E̲S̲T̲ ̲A̲N̲D̲ ̲V̲E̲R̲I̲F̲I̲C̲A̲T̲I̲O̲N̲ ̲M̲E̲T̲H̲O̲D̲S̲

         The unit verification requirements will be met by one
         of the following methods:

         a)  T̲e̲s̲t̲

             This method is a functional verification, such
             as actual operation wherein the element of verification
             is instrumented, measured, or displayed directly.

             All hardware shall be tested to demonstrate its
             proper functioning, its interfaces and its performance.

         b)  A̲n̲a̲l̲y̲s̲i̲s̲

             This method is a non-functional verification, such
             as deduction or translation of data, review of
             analytical data, or performance of a detailed analysis.

             The aim of the analysis is to discover:

             1) Misinterpretations of the approved specification
                or the design.

             2) Errors, omission or inconsistencies in the above
                or in the documentation.

             3) Nonconformance to the agreed standards.

         c)  E̲x̲a̲m̲i̲n̲a̲t̲i̲o̲n̲/̲I̲n̲s̲p̲e̲c̲t̲i̲o̲n̲

             This method is a non-functional verification, such
             as visual inspection of the physical characteristics
             of the item or of the documentation associated
             with the item.


4.2      V̲E̲R̲I̲F̲I̲C̲A̲T̲I̲O̲N̲

         a)  The verification efforts are divided into hardware
             and system verification.

         b)  The verification will be divided into two classes
             which are

             I       -           Internal verification
             II      -           External verification

         c)  Only class II verifications shall be approved by
             SHAPE.

         d)  Class I verifications shall be approved by CR's
             internal QA only, but may be inspected by SHAPE's
             QAR.

         e)  The verification efforts shall be divided into
             the verification type defined below.

         f)  H̲A̲R̲D̲W̲A̲R̲E̲ ̲V̲e̲r̲i̲f̲i̲c̲a̲t̲i̲o̲n̲


             C̲l̲a̲s̲s̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲V̲e̲r̲i̲f̲i̲c̲a̲t̲i̲o̲n̲ ̲T̲y̲p̲e̲ ̲

             I       Production Verification
             II      Factory Acceptance Test


         g)  S̲Y̲S̲T̲E̲M̲ ̲V̲e̲r̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

             C̲l̲a̲s̲s̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲V̲e̲r̲i̲f̲i̲c̲a̲t̲i̲o̲n̲ ̲T̲y̲p̲e̲ ̲

             II      Comsec On-site Verification
             II      Site Functional Test



4.2.1    H̲a̲r̲d̲w̲a̲r̲e̲ ̲V̲e̲r̲i̲f̲i̲c̲a̲t̲i̲o̲n̲



4.2.1.1  P̲r̲o̲d̲u̲c̲t̲i̲o̲n̲ ̲V̲e̲r̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

         The production verification which is internal (class
         I) is the verification to be performed on each unit,
         module and subsystem following manufacture to ensure
         that all items are in accordance with product specification
         prior to system integration.


4.2.1.2  F̲a̲c̲t̲o̲r̲y̲ ̲A̲c̲c̲e̲p̲t̲a̲n̲c̲e̲ ̲T̲e̲s̲t̲

         When a CRT-link has been integrated at the factory,
         a test will be carried out to verify that all hardware
         fulfils the functional specifications. This is an external
         verification (class II).



4.2.2    S̲y̲s̲t̲e̲m̲ ̲V̲e̲r̲i̲f̲i̲c̲a̲t̲i̲o̲n̲



4.2.2.1  C̲O̲M̲S̲E̲C̲ ̲O̲n̲-̲S̲i̲t̲e̲ ̲V̲e̲r̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

         a)  When the CRT equipment has been installed on-site,
             a COMSEC verification will be performed by the
             ACE COMSEC authorities.

         b)  Customer will conduct the verification and Christian
             Rovsing A/S test engineers will assist in operating
             the system. The COMSEC on-site verification is
             a formal verification (class II). The verification
             shall take place in conjunction with the Site functional
             test.



4.2.2.2  S̲i̲t̲e̲ ̲F̲u̲n̲c̲t̲i̲o̲n̲a̲l̲ ̲T̲e̲s̲t̲

         a)  Site functional test is the act whereby SHAPE will
             acknowledge by protocol that CR has fully demonstrated
             that a CRT-link is complete and ready for initial
             operation and will take place when the following
             requirements have been met:

         1)  Completion of an agreed Site functional test

         2)  Verification of the site inventory

         3)  If applicable, availability of a mutually agreed
             discrepancy list showing the agreed date for clearance
             of each listed discrepancy.





4.3      F̲A̲C̲T̲O̲R̲Y̲ ̲A̲C̲C̲E̲P̲T̲A̲N̲C̲E̲ ̲A̲N̲D̲ ̲S̲I̲T̲E̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲A̲L̲ ̲T̲E̲S̲T̲ ̲D̲O̲C̲U̲M̲E̲N̲T̲A̲T̲I̲O̲N̲



4.3.1    G̲e̲n̲e̲r̲a̲l̲

         The quality and quantity of documentation produced
         and delivered by contractor for Factory Acceptance
         and Site functional tests is determined solely by the
         extent to which customer and contractor have agreed
         to test the equipment (i.e. requirements stated in
         this Requirements and Design Specification).

         Documentation for class I test (contractor's internal
         verification) will be developed for in-house use only.



4.3.2    F̲a̲c̲t̲o̲r̲y̲ ̲A̲c̲c̲e̲p̲t̲a̲n̲c̲e̲ ̲T̲e̲s̲t̲ ̲D̲o̲c̲u̲m̲e̲n̲t̲

         Factory Acceptance Test Document shall contain the
         procedures for the tests, that have to be performed
         on each equipment and its associated accessories, following
         manufacture, to ensure that all items to be delivered
         are in accordance with the requirements of the contract,
         prior to shipment from the factory.



4.3.3    S̲i̲t̲e̲ ̲F̲u̲n̲c̲t̲i̲o̲n̲a̲l̲ ̲T̲e̲s̲t̲ ̲D̲o̲c̲u̲m̲e̲n̲t̲

         This document shall contain all test procedures and
         inspections that are necessary to verify that the equipment
         has been correctly installed and to demonstrate that
         the remote terminals are able to communicate with CAMPS.
         It shall also contain a check list of all items that
         should be supplied under terms of the contract such
         as accessories, spare parts, tools, test equipment
         and documentation.



4.3.4    T̲e̲s̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲s̲

         Each procedure shall, where applicable, include as
         a minimum the following:



         a)  The title of the proposed procedure and a list
             of all required test equipment, where applicable.

         b)  Required test limits, where applicable.

         c)  A detailed step-by-step procedure written so that
             the procedure can be understood by technician.

         d)  A block diagram of the required test set-up if
             more than two test connections are involved.



4.3.5    T̲e̲s̲t̲ ̲R̲e̲s̲u̲l̲t̲ ̲F̲o̲r̲m̲s̲

         The Test Results Forms to be used in conjunction with
         the test procedures may be part of the test procedure
         itself. They shall contain as a minimum a space for
         inclusion of:

         a)  Test location and date

         b)  Equipment type and serial number(s)

         c)  Test procedure reference number and issue number

         d)  Type of test equipment employed

         e)  Test Results

         f)  Comments

         g)  Signatures of official representatives of the contractor
             and the customer.



4.3.6    A̲p̲p̲r̲o̲v̲a̲l̲ ̲a̲n̲d̲ ̲D̲e̲l̲i̲v̲e̲r̲y̲

         A copy of each class II test document complete with
         samples of the associated test result forms, shall
         be submitted to SHAPE for approval at least thirty
         days before the scheduled date for commencement of
         the associated tests. Submittal will take place only,
         if SHAPE has not previously approved the document.
         SHAPE and the contractor shall mutually agree on any
         changes to the scope and content during the period
         between submission of the test procedures and the scheduled
         date for commencement of the associated tests.


                     5̲ ̲ ̲S̲Y̲S̲T̲E̲M̲ ̲D̲E̲S̲I̲G̲N̲



         This chapter presents a more detailed description of
         the different H/W assemblies which have been identified
         in chapter 3.

         To provide a more comprehensive understanding of the
         Remote Terminals System, each of the assemblies are
         broken down into basic functional elements (i.e. crate,
         buses and modules), and each of these is given a detailed
         functional/mechanical description. The equipment is
         divided in two major assemblies:

         1)  The main site equipment
         2)  The remote site equipment



5.1      M̲A̲I̲N̲ ̲S̲I̲T̲E̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲

         The aim of the equipment positioned at the mainsite
         is to collect the datachannels for connection to the
         remote site and perform the necessary multiplexing/demultiplexing
         to enable communication via a single data link.

         The datachannels may originate from

         1)  A LTUX belonging to the CRT equipment and connected
             to the TDX-bus of CAMPS

         2)  CAMPS data channel expansion capacity (Expansion
             LTUXs)

         3)  Separate channels interfaced via the CAMPS filterbox

         4)  A single data channel reserved for future connection
             to a LTUX capable of handling an OCR

         For the purpose of point 3) above a low-level signal
         adaption capability is necessary.

         The major functional subassemblies used on the Main
         Site are shown in fig. 5.1-1::

         1)  TDX crate assembly
         2)  Adaptor crate assembly
         3)  Statistical Multiplexer


5.1.1    T̲D̲X̲ ̲C̲r̲a̲t̲e̲ ̲A̲s̲s̲e̲m̲b̲l̲y̲

         The TDX modules, the LTUX-S and the BSM-X, are housed
         in a standard CR80S 19" CTX Crate.

         Besides the TDX modules the TDX Crate Assembly houses
         the Power Supply modules, and when reconfiguration
         option 2 is implemented, the OMDTs will be placed in
         the TDX Crate Assembly.

         The position of the modules in the TDX Crate Assembly
         is restricted to the positions indicated in fig. 5.1.1-1.



5.1.1.1  C̲T̲X̲-̲C̲r̲a̲t̲e̲

         The CTX Crate consists of a front crate and a rear
         crate. On the back panel of the front crate is a bus
         motherboard (Printed Circuit board) for module interconnection
         and also edgeconnectors for the front crate mounted
         modules.Refer to section 5.3.1.1 for further mechanical
         specifications.

         The CTX motherboard connector signals are shown in
         fig. 5.1.1-2 (4 sheets).

         All signals in the V24/V28 I/O area (refer to fig.
         5.1.1-2 conform with the CCITT V28 electrical specifications,
         with the exception of the supply voltage connections.

         The Supply Voltage is an ac voltage with the following
         specification.

         Voltage:                9 V…0f…RMS…0e…

         Max. Current:           4.2 A

         The remaining Motherboard signals TDX-TX-DATA, TDX-TX-EN,
         TDX-REC-1, and TDX-REC-2 conform to the following specification:



         Drivers:

         2,4V = V…0f…OH…0e…= 5V
         OV   = V…0f…OL…0e…= 0.5 V
                I…0f…OHMax …0e…= 15mA
                I…0f…OLMax …0e…= 24mA

         Receivers:

         2V =   V…0f…IH…0e… = 5V
         OV =   V…0f…IL…0e… = 0,8 V
                I…0f…IL…0e… = 0,2 mA
                I…0f…IH…0e… = 0,02 mA




































         Notes: 1)   The V24 Monitors form part of the maintenance
                     equipment, and are only mounted during
                     maintenance operation.

                2)   The OMDTs belong to the Remote Site Equipment,
                     and are only mounted when reconfiguration
                     option 2 is implemented.



  FIGURE 5.1.1-1…01…T̲D̲X̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲E̲M̲B̲L̲Y̲,̲…01…M̲A̲X̲.̲ ̲C̲O̲N̲F̲I̲G̲U̲R̲A̲T̲I̲O̲N̲



































]











FIGURE 5.1.1-2 (sheet 1 of 4)…01…C̲T̲X̲ ̲M̲O̲T̲H̲E̲R̲B̲O̲A̲R̲D̲ ̲C̲O̲N̲N̲E̲C̲T̲O̲R̲ ̲P̲I̲N̲S̲,̲ ̲P̲O̲S̲.̲ ̲1̲
 ̲&̲ ̲2̲















































FIGURE 5.1.1-2 (sheet 2 of 4)…01…C̲T̲X̲ ̲M̲O̲T̲H̲E̲R̲B̲O̲A̲R̲D̲ ̲C̲O̲N̲N̲E̲C̲T̲O̲R̲ ̲P̲I̲N̲S̲,̲…01…P̲O̲S̲.̲ ̲3̲,̲4̲,̲5̲,̲6̲,̲1̲1̲,̲1̲2̲,̲
 ̲1̲3̲ ̲&̲ ̲1̲4̲















































FIGURE 5.1.1-2 (sheet 3 of 4)…01…C̲T̲X̲ ̲M̲O̲T̲H̲E̲R̲B̲O̲A̲R̲D̲ ̲C̲O̲N̲N̲E̲C̲T̲O̲R̲ ̲P̲I̲N̲S̲,̲ ̲P̲O̲S̲.̲ ̲7̲
 ̲&̲ ̲1̲5̲















































FIGURE 5.1.1-2 (sheet 4 of 4)…01…C̲T̲X̲ ̲M̲O̲T̲H̲E̲R̲B̲O̲A̲R̲D̲ ̲C̲O̲N̲N̲E̲C̲T̲O̲R̲ ̲P̲I̲N̲S̲,̲…01…P̲O̲S̲.̲ ̲8̲,̲ ̲9̲,̲ ̲1̲0̲,̲
 ̲1̲6̲,̲ ̲1̲7̲ ̲&̲ ̲1̲8̲


5.1.1.2  B̲S̲M̲-̲X̲

         The BSM-X, the TDX Bus Switching and Monitoring module
         provide two interface functions:

         -   Interfaces the dualized TDX buses of CAMPS to the
             TDX Crate Assy. Single TDX Bus structure through
             a Bus switch circuitry.

         -   Interfaces the CAMPS CCB (Configuration Control
             Bus) to the TDX Crate Assy control and monitoring
             facilities through an addressable serial/parallel
             conversion circuitry.

         The addressable serial/parallel conversion circuitry
         (An addressable UART) is the TDX Crate Assy interface
         to the CAMPS Watchdog.

         Fig. 5.1.1.2-1 shows the BSM-X principle diagram.

         The Bus switch circuitry, selecting one of the dualized
         TDX buses as the internal TDX bus, is controlled either
         by the CAMPS Watchdog Processor or by a switch on the
         BSM-X front panel. The source of control is selected
         via another front panel mounted switch selecting either
         Automatic mode, enabling Watchdog Processor control,
         or Manual mode enabling manual TDX bus selection.

         The BSM-X is a standard CR80S front crate module occupying
         1 crate position.

         P̲o̲w̲e̲r̲ ̲C̲o̲n̲s̲u̲m̲p̲t̲i̲o̲n̲

         +   5V: 2A
         +   12V:    0,15A
         -   12V:    0,15A



5.1.1.2.1    B̲S̲M̲-̲X̲ ̲P̲a̲n̲e̲l̲

         External connections (CCB, TDX Bus # 1 and # 2) are
         provided via the BSM-X Panel, a front panel in the
         rear crate. Flatcables connect the BSM-X panel connections
         to the CTX motherboard. The BSM-X panel is a CR80S
         rear crate module occupying 2 crate positions.















































                FIGURE 5.1.1.2-1…01…T̲H̲E̲ ̲B̲S̲M̲-̲X̲


5.1.1.3  L̲T̲U̲X̲-̲S̲

         The LTUX-S is the standard interface to the TDX bus.
         The LTUX-S provides 4 V24/V28 communication channels.
         On the front panel are four switches that can be used
         to enable/disable each of the four communication channels.

         The LTUX-S is built around a standard microprocessor
         using standard microprocessor interface LSIs as interface
         between the TDX bus and the user applications.



5.1.1.3.1    T̲D̲X̲ ̲B̲u̲s̲ ̲I̲n̲t̲e̲r̲f̲a̲c̲e̲

         The LTUX-S provides up to 16 full duplex individual
         logical channels between the user application and the
         TDX bus. The microprocessor supports both application
         processing of the TDX interface, TDX protocol and TDX
         channel set-up. The sum of bandwidth assigned to the
         logic channels through the LTUX-S is dynamically changeable
         by the CAMPS System.

         Overleaf is found the block diagram of the LTUX-S,
         fig. 5.1.1.3.1-1.

         The TDX bus signals are buffered, by bus receivers
         and a tri-statable driver, before they are routed to/from
         the code converter circuit. In this circuit the incoming
         SPL-D data stream is converted to NRZL data and a clock
         (CLK). The outgoing data stream is converted to SPL-D
         code synchronized to CLK. When an incoming frame is
         received, the State Controller gets a request from
         the serial to parallel converter and the contents of
         the frame is routed byte by byte to FIFO 1.

         During this transfer some of the bytes in the frame
         are checked or compared "on the fly" by the State Controller.
         The contents of the MUX no. field, indicating the next
         device to transmit, is compared with the device number
         (set on a DIL-switch), and if equal and no CRC errors
         are detected the transmitter part is activated and
         a frame will be transmitted when bit 241 of the incoming
         data stream has been reached.















































              FIGURE 5.1.1.3.1-1…01…T̲H̲E̲ ̲L̲T̲U̲X̲-̲S̲


         The contents of the DEVICE NO. field, indicating the
         destinee of the frame, is compared to the device number,
         and if equal the contents of FIFO 1 is transferred
         to FIFO 2. If FIFO 2 is not empty this transfer is
         cancelled and FIFO 1 is cleared to be ready for the
         next incoming frame. When the transfer from FIFO 1
         to FIFO 2 has succeeded the LTUX-S CPU is interrupted.
         The interrupt routine (FRAME-routine) transfers the
         frame from FIFO 2 to a free ringbuffer within the CPU
         memory space, and the Incoming Scan routine transfers
         the frame from the ringbuffer to a data buffer associated
         to one out of ten protocol descriptors identified by
         the CR-ID block in the incoming frame and simultaneously
         executes the TDX protocol on the frame. Via the protocol
         descriptor the frame is fetched by either the System
         S/W (channel 0-1) or by Application S/W (channel 2-15).
         Transfer is shown schematically on fig. 5.1.1.3.1-2
         (2 sheets).

         When the transmitter part of the State Controller has
         been activated by an incoming frame, it starts to send
         the start-FLAG followed by the frame which is transferred
         byte by byte from FIFO 3 to the parallel to serial
         converter. After the last byte an end-FLAG is generated,
         the CPU is interrupted and will now move the next outgoing
         frame from a channel buffer in the memory to FIFO 3.
         If no frame is available the CPU does nothing and the
         next time the transmitter is activated FIFO 3 will
         be empty and no frame is transmitted.

         The frame to be transmitted comes from a data buffer
         fetched, via a protocol descriptor, by the Outgoing
         Scan routine and routed to FIFO 3 directly while executing
         the TDX protocol on the frame.

         The processor part consists of a PROM-memory area,
         a data memory area, serial input/output interface circuits
         for four V24 channels, a timer and interrupt control
         circuit and an I/O port used for reading a mode select
         switch (DIL-switch) and for control of the State Controller.
         The mode select switch can be used by the Application
         S/W. For example to determine characteristics of the
         V24 channels such as:

         -   baudrate

         -   V24 protocol















































  FIGURE 5.1.1.3.1-2 (Sheet 1 of 2)…01…L̲T̲U̲X̲-̲S̲ ̲D̲A̲T̲A̲ ̲T̲R̲A̲N̲S̲F̲E̲R̲















































  FIGURE 5.1.1.3.1-2 (Sheet 2 of 2)…01…L̲T̲U̲X̲-̲s̲ ̲D̲A̲T̲A̲ ̲T̲R̲A̲N̲S̲F̲E̲R̲


         The timer circuit has one software controlled timer
         with interrupt access to the CPU. It handles one external
         interrupt from the State Controller and it controls
         two baud rate generators set up by software.



5.1.1.3.2    M̲e̲c̲h̲a̲n̲i̲c̲a̲l̲ ̲a̲n̲d̲ ̲E̲l̲e̲c̲t̲r̲i̲c̲a̲l̲ ̲S̲p̲e̲c̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

         The LTUX-S is a standard CR80S module placed in the
         TDX Crate Assembly. The LTUX-S bus connector layout
         is shown on fig. 5.1.1.3.2-1.

         P̲o̲w̲e̲r̲ ̲C̲o̲n̲s̲u̲m̲p̲t̲i̲o̲n̲ ̲o̲f̲ ̲t̲h̲e̲ ̲L̲T̲U̲X̲-̲S̲

         +  5 Volt:                 3 A
         + 12 Volt:              0,15 
         - 12 Volt:              0,15 A















































     FIGURE 5.1.1.3.2-1…01…L̲T̲U̲X̲-̲S̲ ̲B̲U̲S̲ ̲C̲O̲N̲N̲E̲C̲T̲O̲R̲ ̲L̲A̲Y̲-̲O̲U̲T̲


5.1.1.3.3    U̲s̲e̲r̲ ̲I̲n̲t̲e̲r̲f̲a̲c̲e̲

         The 4 asynchronous V24 channels of the LTUX-S will
         normally be connected to the Statistical Multiplexer
         via a V24 Back Panel (type BP 8).

         If reconfiguration option 2 is implemented the OMDTs
         from the Remote Site will be moved to the Main Site
         and installed in the TDX-crate assembly, after disconnection
         of the Statistical Multiplexers. In this case the four
         V24 channels will be interfaced to the VDUs and MSPs,
         moved from the Remote to the Main Site installation,
         via the moved OMDTs.

         For maintenance purposes, it is possible to monitor
         the V24 channels by aid of a V24 Monitor Panel (not
         installed, part of CAMPS Maintenance equipment).



5.1.1.3.4    V̲2̲4̲ ̲B̲a̲c̲k̲ ̲P̲a̲n̲e̲l̲

         External V24/V28 connections to/from the TDX-crate
         assembly are provided via the V24 Back Panel, where
         four 25 pole connectors are situated (CANNON DB25 or
         equivalent)

         A flatcable connects the V24 circuits connections to
         the LTUX-S motherboard connector. A strapping field
         on the back panel may be used for DTE to/from DCE conversion.

         The V24 Back Panel is a CR80S rear crate module occupying
         4 crate positions.



5.1.1.3.5    O̲M̲D̲T̲

         The OMDTs will only be mounted in the TDX-crate assembly
         if reconfiguration option 2 is implemented.

         For a description of the OMDT refer to section 5.2.2.1.





5.1.1.3.6    V̲2̲4̲ ̲M̲o̲n̲i̲t̲o̲r̲ ̲P̲a̲n̲e̲l̲

         The V24 Monitor Panel is part of CAMPS Maintenance
         Equipment and only used during Maintenance Operations.
         The V24 Monitor Panel may be inserted in crate position
         # 5 or 6 and 13 or 14 to monitor the V24 traffic on
         the LTUX in position # 3 respectively # 11.

         The V24 Monitor Panel is a standard CR80S front crate
         module occupying 2 crate positions.



5.1.1.4  T̲D̲X̲ ̲P̲o̲w̲e̲r̲ ̲S̲u̲p̲p̲l̲y̲

         The TDX power supply is a standard CR80S module. The
         TDX Power Supply, as seen from fig. 5.1.1.4-1, provides
         3 regulated power outputs:

         -   +  5 Volt
         -   + 12 Volt
         -   - 12 Volt

         The +5 Volt power supply is a 20 KHz push-pull converter
         operating direcly on the rectified mains voltage.

         The +12 Volt and -12 Volt power supplies are fed from
         a full wave rectified transformer output.

         The +12 Volt power supply is regulated by a conventional
         PWM (Pulse Width Modulated) regulator.

         The -12 Volt power supply is regulated by a PWM regulator.

         E̲l̲e̲c̲t̲r̲i̲c̲a̲l̲ ̲S̲p̲e̲c̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

         Maximum load:

         +  5 Volt:  32 A
         + 12 Volt:  2,8A
         - 12 Volt:  1,2A

         Noise & ripple:         Better than 60 mV…0f…pp…0e…
         Input Voltage:          220V…0f…ac…0e…+10/-15%
                      50 Hz + 30/-10%


5.1.1.4.1    M̲a̲i̲n̲ ̲P̲o̲w̲e̲r̲ ̲P̲a̲n̲e̲l̲

         The TDX Power Supply is interfaced to the Main Power
         via the Main Power Panel, which contains a mains switch,
         fuse and some HF-filtering components.

         The Main Power Panel is a CR80S rear crate module occupying
         2 crate positions.















































            FIGURE 5.1.1.4-1…01…T̲D̲X̲ ̲P̲O̲W̲E̲R̲ ̲S̲U̲P̲P̲L̲Y̲


5.1.1.5  O̲p̲t̲o̲ ̲P̲o̲w̲e̲r̲ ̲S̲u̲p̲p̲l̲y̲

         The Opto Power Supply is identical to the Adaptor Power
         Supply. Refer to section 5.1.2.3 for a description.



5.1.2    A̲d̲a̲p̲t̲o̲r̲ ̲C̲r̲a̲t̲e̲ ̲A̲s̲s̲e̲m̲b̲l̲y̲

         The Adaptor Crate Assembly contains the V28(L/L) adaptors
         to be used when reconfiguration option 1 is implemented.
         On site 10, the V28(L/L) adaptors are also used to
         interface the CAMPS Expansion LTUX channels to the
         Remote Terminal System.

         Besides the V28(L/L) adaptors, the Adaptor Crate Assembly
         contains the Adaptor Power Supply. These modules are
         housed in CTX-crate. Refer to section 5.1.1.1 for a
         description of the CTX-crate. The position of the modules
         in the Adaptor Crate is depicted in fig. 5.1.2-1.















































 FIGURE 5.1.2-1…01…A̲D̲A̲P̲T̲O̲R̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲E̲M̲B̲L̲Y̲,̲ ̲M̲A̲X̲ ̲C̲O̲N̲F̲I̲G̲U̲R̲A̲T̲I̲O̲N̲


5.1.2.1  V̲2̲8̲ ̲(̲L̲/̲L̲)̲ ̲A̲d̲a̲p̲t̲o̲r̲

         The V28 (L/L) adaptor Type 1 converts standard CCITT
         V24/V28 signal levels within 4 data channels to V24/V28(L/L)
         signals, and vice versa.

         Fig. 5.1.2.1-1 shows the V28 (L/L) Adaptor, block diagram.
         The V28(L/L) adaptor is a standard CR80S module occupying
         2 crate positions.

         a)  I̲n̲t̲e̲r̲f̲a̲c̲e̲ ̲S̲p̲e̲c̲i̲f̲i̲c̲a̲t̲i̲o̲n̲s̲

             1)  S̲t̲a̲n̲d̲a̲r̲d̲ ̲V̲2̲8̲ ̲I̲n̲t̲e̲r̲f̲a̲c̲e̲

                 The standard V28 side of the V28(L/L) adaptor
                 performs as a DCE and conforms with CCITT recommendation
                 V28. The following interchange circuits (ref.
                 CCITT V24) are provided for each of the four
                 data channels:

                 102 Signal ground
                 103 Transmitted data
                 104 Received data
                 105 Request to Send
                 107 Data Set Ready
                 108/2 Data terminal ready

                 The V28 side of the adaptor interfaces to the
                 motherboard. The pin allocation is shown in
                 fig. 5.1.2.1-2.

             2)  L̲o̲w̲ ̲L̲e̲v̲e̲l̲ ̲I̲n̲t̲e̲r̲f̲a̲c̲e̲

                 On the front panel, 4 V24 connectors type D-25
                 are situated, forming the low level Interface.

                 Electrically, the Low Level Interface conforms
                 with MIL-STD-188C, except for polarity (see
                 below).

                 The waveshaping performed on the interchange
                 circuits is according to the requirement at
                 1200 bps, which is the maximum bit rate supported
                 by the module. The V28(L/L) Adaptor is capable
                 of driving a cable length of up to 275 meters.


                Functionally the interchange signals correspond
                to CCITT V24. The adaptor will be strapped to
                perform as DCE or a DTE device.

                The polarity of the interchange circuits 103
                and 104 may be reversed by use of a strap. This
                enables the user to select signal polarity according
                to MIL-STD-188C or V28 on the Low Level Interface.

         b)  P̲o̲w̲e̲r̲ ̲S̲u̲p̲p̲l̲y̲ ̲R̲e̲q̲u̲i̲r̲e̲m̲e̲n̲t̲s̲

             The V28(L/L) adaptor, type 1 shall be powered from
             a 2 x 9V AC power source:

                A̲C̲ ̲P̲o̲w̲e̲r̲ ̲R̲e̲q̲u̲i̲r̲e̲m̲e̲n̲t̲s̲

                Supply voltage: 2 x 9V AC + 10%/- 15%
                Frequency: 50 Hz + 10%/- 10%
                Current consumption: Max 2,1 A/module




















































        FIGURE 5.1.2.1-1…01…V̲2̲8̲(̲L̲/̲L̲)̲ ̲A̲d̲a̲p̲t̲o̲r̲,̲ ̲T̲y̲p̲e̲ ̲1̲
                      B̲L̲O̲C̲K̲ ̲D̲I̲A̲G̲R̲A̲M̲















































FIGURE 5.1.2.1-2…01…V̲2̲8̲(̲L̲/̲L̲)̲ ̲A̲D̲A̲P̲T̲O̲R̲ ̲T̲Y̲P̲E̲ ̲1̲…01…B̲U̲S̲ ̲C̲O̲N̲N̲E̲C̲T̲O̲R̲ ̲L̲A̲Y̲O̲U̲T̲


5.1.2.2  V̲2̲4̲ ̲B̲a̲c̲k̲ ̲P̲a̲n̲e̲l̲

         The V24 Back Panel is used to interface four standard
         V24/V28 data channels to the motherboard of the Adaptor
         Crate Assembly.

         The V24 Back Panel is identical with the Back Panel
         used in the TDX-crate assembly. Ref. to section 5.1.1.3.4.



5.1.2.3  A̲d̲a̲p̲t̲o̲r̲ ̲P̲o̲w̲e̲r̲ ̲S̲u̲p̲p̲l̲y̲

         The Adaptor Power Supply is a CR80S rear module occupying
         8 crate positions. The Adaptor Power Supply provides
         the necessary power to supply adaptors for 8 channels,
         implemented by any combination of V28(L/L) adaptors
         and OMDTs.

         The module provides 2 x 9V AC outputs.

         E̲l̲e̲c̲t̲r̲i̲c̲a̲l̲ ̲S̲p̲e̲c̲i̲f̲i̲c̲a̲t̲i̲o̲n̲ ̲(̲e̲a̲c̲h̲ ̲o̲u̲t̲p̲u̲t̲)̲:̲

         Output voltage: 9V AC + 10%/- 15%
         Output frequency: 50 Hz + 10%/- 10%
         Harmonic Distortion: max. 5%
         Maximum Load: 4,2 A



5.1.3    S̲t̲a̲t̲i̲s̲t̲i̲c̲a̲l̲ ̲M̲u̲l̲t̲i̲p̲l̲e̲x̲e̲r̲

         The CR supplied statistical multiplexer features full
         duplex statistical multiplexing of 8 V24 channels,
         with variable length block transmission, dynamic bandwidth
         assignment and error control.

         It is housed in a 19" rack-mount case 2U high (8,9
         cm).

         The status display is visible through the front panel
         and all switches are front accessible after removal
         of the front panel.





5.1.3.1  S̲t̲a̲t̲i̲s̲t̲i̲c̲a̲l̲ ̲M̲u̲l̲t̲i̲p̲l̲e̲x̲e̲r̲ ̲T̲r̲a̲n̲s̲m̲i̲s̲s̲i̲o̲n̲

         The transmission between the statistical multiplexers
         is carried out by a special statistical multiplexer
         serial communication protocol.

         The channel interface control signals are transmitted
         via the protocol in form of a special control character,
         generated each time one of the control signals changes
         from On to Off or vice-versa. Two interface control
         signals may be transmitted in each direction per channel.

         The transmisson of variable length data blocks according
         to the loading of the individual channels, allows the
         stat. mux. to take account of average traffic loading
         on the mux-line, since it can make use of its buffer
         storage to accomodate temporary peak loading on individual
         channels.



5.1.3.2  E̲r̲r̲o̲r̲ ̲C̲o̲n̲t̲r̲o̲l̲

         Retransmisson on error is implemented automatically
         between the stat. muxes using a full-duplex go-back-n-automatic-retransmission-request
         (ARQ) scheme. The transmitting stat. mux. appends a
         cyclic redundancy check (CRC) scheme. The transmitting
         stat. mux. appends a cyclic redundancy check (CRC)
         character to each transmitted data-block in the protocol.
         This CRC is re-calculated to check the block errors
         at the receiving stat. mux.



5.1.3.3  B̲u̲f̲f̲e̲r̲ ̲C̲o̲n̲t̲r̲o̲l̲

         The buffer capacity (approximately 15K bytes) is allocated
         dynamically to the channels as required, rather than
         being fixed portions.

         However, buffer overflow may occur, either because
         of excessive retransmissions or prolonged peak channel
         activity. If a buffer overflow is about to occur, the
         stat. mux terminates the flow of data into its buffer,
         by dropping the circuit 106 control signal on the V24
         channels to the associated equipment.



5.1.3.4  C̲o̲n̲f̲i̲g̲u̲r̲a̲t̲i̲o̲n̲

         All configuration parameters are switch selected using
         DIP switches to configure the units. To further simplify
         system configuration, switch selection of configuration
         parameters is required at one site only. This is done
         by switch selection of master and slave on each unit.
         All configuration data is then automatically down-line
         loaded from the master to the slave unit, at power-up
         or reconfiguration of channels.



5.1.3.5  C̲h̲a̲n̲n̲e̲l̲ ̲I̲n̲t̲e̲r̲f̲a̲c̲e̲

         The Channel interfaces are CCITT V24/CCITT V28 serial
         asynchronous full duplex interfaces available on female
         (DCE) standard D-25 S connectors.

         The available interchange circuits are:

         102    Signal Ground
         103    Transmitted Data
         104    Received Data
         105    Request to Send
         106    Ready for sending
         107    Data set ready
         108.2  Data Terminal ready



5.1.3.6  M̲u̲x̲-̲L̲i̲n̲e̲ ̲I̲n̲t̲e̲r̲f̲a̲c̲e̲

         The mux-line interface is a CCITT V24/special V28(L)
         serial synchronous full-duplex interface available
         on a male (DTE) standard D-25P connector.

         The special V28(L) interface is implemented on a MIL-STD-188C
         interface with CCITT V28 voltage polarities.



         The available interchange circuits are:

         102    Signal Ground
         103    Transmitted Data
         104    Received Data
         105    Request to Send
         106    Ready for sending
         109    Received line signal detector
         114    Transmitter signal element timing
         115    Receiver signal element timing



5.1.3.7  P̲o̲w̲e̲r̲

         The stat. mux. is connected to 220 V AC mains. The
         power consumption is less than 150 watts.



5.1.4    S̲y̲n̲c̲h̲r̲o̲n̲e̲o̲u̲s̲ ̲M̲u̲l̲t̲i̲p̲l̲e̲x̲e̲r̲

         The CR supplied synchroneous multiplexer is a 2 channel
         data concentator feature full duplex multiplexing of
         2 statistical multiplexer and operate as the CR supplied
         Statistical Multiplexer.

         It is housed in a 19" rack-mont case 2U high (8,9 cm).



5.1.5.1  R̲e̲s̲y̲n̲c̲h̲r̲o̲n̲i̲z̲a̲t̲i̲o̲n̲ ̲M̲o̲n̲d̲u̲l̲e̲

         The Resynchronization mondule consist of two functionally
         independent circuits each controlling one HOST-CRYPTO
         v24-interface channel. Each channel has the ability
         of initially synchronizing and resynchronizing its
         V24 line.



5.1.5.2  P̲o̲w̲e̲r̲

         The Resync. mondule is placed in front of a CTX-Crate
         and the power consumption is typical 19 watts.



5.2      R̲E̲M̲O̲T̲E̲ ̲S̲I̲T̲E̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲

         The aim of the equipment positioned at the remote site
         is to distribute the datachannels to the terminals
         connected at the remote site, and to perform the multiplexing/demultiplexing
         to enable communication with the main site via a single
         modem Line.


         The terminals to be connected at the remote site can
         be divided in the following categories:

         1)  VDUs

         2)  MSPs

         3)  Other equipment connected to separate channels

         4)  A single datachannel reserved for a future connection
             to an OCR.

         Of the 8 datachannels normally 4 are terminated in
         an optical link to the terminals, and 4 are terminated
         in a V28(L/L) connection to the terminals.

         The data channels are fed through a filter box when
         leaving the CAMPS Remote Terminal Rack.

         The major functional subassemblies used on the Remote
         Site are shown in figure 5.2-1:

         1)  Statistical Multiplexer

         2)  Opto Crate Assembly
















































FIGURE 5.2-1…01…C̲A̲M̲P̲S̲ ̲R̲E̲M̲O̲T̲E̲ ̲T̲E̲R̲M̲I̲N̲A̲L̲S̲…01…R̲E̲M̲O̲T̲E̲ ̲S̲I̲T̲E̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲ ̲(̲T̲Y̲P̲I̲C̲A̲L̲)̲…01…F̲r̲o̲n̲t̲ ̲e̲l̲e̲v̲a̲t̲i̲o̲n̲,̲
 ̲d̲o̲o̲r̲ ̲r̲e̲m̲o̲v̲e̲d̲


5.2.1    S̲t̲a̲t̲i̲s̲t̲i̲c̲a̲l̲ ̲M̲u̲l̲t̲i̲p̲l̲e̲x̲e̲r̲

         The Statistical Multiplexer used on the remote site
         is identical with the Statistical Multiplexer used
         on main site. Refer to section 5.1.3 for a description.

         The Remote site stat. mux forms a pair together with
         the corresponding stat. mux on main site; in this pair
         one shall be set as Master, and one as Slave.



5.2.2    O̲p̲t̲o̲ ̲C̲r̲a̲t̲e̲ ̲A̲s̲s̲e̲m̲b̲l̲y̲

         The Opto Crate assembly contains the V28(L/L) Adaptors
         and OMDTs which perform the signal adaption on the
         datachannels to be connected with the terminal equipment.
         Furthermore the Opto Crate assembly contains an Opto
         Power Supply.

         These modules are housed in a CTX crate. Refer to section
         5.1.1.1 for a description of the CTX-crate.

         The position of the modules in the Opto Crate Assembly
         is depicted in fig. 5.2.2-1.



5.2.3    S̲y̲n̲c̲h̲r̲o̲n̲e̲o̲u̲s̲ ̲M̲u̲l̲t̲i̲p̲l̲e̲x̲e̲r̲

         The sync. mux. used on the remote site is identical
         with the sync. mux. used on main site. Refer to section
         5.1.4 for a description.









































         Note:  The V24 monitors form part of the maintenance
                equipment and are only mounted during maintenance
                operation.

            FIGURE 5.2.2-1…01…O̲P̲T̲O̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲E̲M̲B̲L̲Y̲


5.2.2.1  O̲p̲t̲i̲c̲a̲l̲ ̲M̲u̲x̲/̲D̲e̲m̲u̲x̲ ̲T̲r̲a̲n̲s̲c̲e̲i̲v̲e̲r̲ ̲(̲O̲M̲D̲T̲)̲

         a)  The OMDTs are one channel units, delivered in 3
             versions serving the same functions but in different
             shape to fit the housing equipment:

             One type for Delta 7260T VDU (OM-1),
             One type for CTX crate mounting (OM-2), and
             One type for Tracor 8000 RO MSP (OM-3).

         b)  The OMDT interfaces one V24/V28 channel. It converts
             the electrical information to infra-red light pulses
             in a serial protocol ready for opto-cable transmission
             and vice-versa.

             In the protocol, data and control bits are multiplexed
             together, added with frame synchronization, converted
             to Manchester code and send off as light pulses.

             Reversely the receiver detects the light pulses,
             makes electrical output which is decoded and demultiplexed.

             The OMDT performs as a DCE on the electrical side.
             The following interchange circuits are supported

             102     Signal Ground
             103     Transmitted Data
             104     Received Data
             105     Request to Send
             106     Ready for sending
             107     Data set ready
             108.2   Data Terminal ready

         c)  P̲o̲w̲e̲r̲ ̲S̲u̲p̲p̲l̲y̲ ̲R̲e̲q̲u̲i̲r̲e̲m̲e̲n̲t̲s̲

             1) The OMDT OM-1 shall be powered from a 110 V
                AC power source.

                A̲C̲ ̲P̲o̲w̲e̲r̲ ̲R̲e̲q̲u̲i̲r̲e̲m̲e̲n̲t̲s̲

                Supply voltage:        110 VAC + 20%/-18%
                Frequency:             50 Hz + 10%/-10%
                Current Consumption:   max 0,25 A/module



             2) The OMDT OM-2 shall be powered from a 2 x 9V
                AC power source:

                A̲C̲ ̲p̲o̲w̲e̲r̲ ̲r̲e̲q̲u̲i̲r̲e̲m̲e̲n̲t̲s̲

                Supply voltage:        2 x 9 V AC + 10%/-15%
                Frequency:             50 Hz + 10%/-10%
                Current Consumption:   max. 1A/module

             3) The OMDT OM-3 shall be powered from a 10 V AC
                power source.

                A̲C̲ ̲P̲o̲w̲e̲r̲ ̲R̲e̲q̲u̲i̲r̲e̲m̲e̲n̲t̲s̲

                Supply voltage:        10 V AC + 10%/-15%
                Frequency:             50 Hz + 10%/-10%
                Current Consumption:   max 0,30 A/module



5.2.2.2  V̲2̲8̲(̲L̲/̲L̲)̲ ̲A̲d̲a̲p̲t̲o̲r̲

         For a description of the V28 (L/L) Adaptor refer to
         section 5.1.2.1.



5.2.2.3  V̲2̲4̲ ̲B̲a̲c̲k̲ ̲P̲a̲n̲e̲l̲

         The V24 Back Panel is used to interface four V24/V28
         data channels to the motherboard of the Opto Crate
         assembly. The V24 Back Panel is identical with the
         V24 Back Panel used on the Main Site. Refer to section
         5.1.1.3.4 for a description.



5.2.2.4  O̲p̲t̲o̲ ̲P̲o̲w̲e̲r̲ ̲S̲u̲p̲p̲l̲y̲

         The Opto Power Supply is identical with the Adaptor
         Power Supply used on the Main Site. Refer to section
         5.1.2.3.



5.2.2.5  V̲2̲4̲ ̲M̲o̲n̲i̲t̲o̲r̲ ̲P̲a̲n̲e̲l̲

         The V24 Monitor Panel is part of CAMPS Maintenance
         equipment, and only used during maintenance operations.


         The V24 monitor Panel may be inserted in crate position
         # 5 or 6 and 13 or 14 to monitor the V24 traffic between
         Statistical Multiplexer and Terminal equipment.
         The V24 Monitor Panel is a standard CR80 S front crate
         module occupying 2 crate positions.



5.3      R̲A̲C̲K̲ ̲A̲N̲D̲ ̲S̲U̲B̲-̲A̲S̲S̲E̲M̲B̲L̲I̲E̲S̲

         This section describes the design of the racks used
         for CRT including:

         a)  The CR80S mechanical system

         b)  Other rack mounted equipment

         c)  The EMI shielded racks.

         The figures 5.3-1 and 5.3-2 identify the assemblies
         placed in the racks on main- and remote sites respectively.















































FIGURE 5.3-1 (Sheet 1 of 2)…01…C̲A̲M̲P̲S̲ ̲R̲E̲M̲O̲T̲E̲ ̲T̲E̲R̲M̲I̲N̲A̲L̲S̲…01…M̲A̲I̲N̲ ̲S̲I̲T̲E̲ ̲4̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲…01…(̲M̲A̲X̲ ̲C̲O̲N̲F̲I̲G̲U̲R̲A̲T̲I̲O̲N̲)̲…01…F̲r̲o̲n̲t̲
 ̲e̲l̲e̲v̲a̲t̲i̲o̲n̲,̲ ̲d̲o̲o̲r̲s̲ ̲r̲e̲m̲o̲v̲e̲d̲














































FIGURE 5.3-1 (Sheet 2 of 2)…01…C̲A̲M̲P̲S̲ ̲R̲E̲M̲O̲T̲E̲ ̲T̲E̲R̲M̲I̲N̲A̲L̲S̲…01…M̲A̲I̲N̲ ̲S̲I̲T̲E̲ ̲4̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲…01…(̲M̲A̲X̲ ̲C̲O̲N̲F̲I̲G̲U̲R̲A̲I̲T̲O̲N̲)̲…01…F̲r̲o̲n̲t̲
 ̲e̲l̲e̲v̲a̲t̲i̲o̲n̲,̲ ̲d̲o̲o̲r̲s̲ ̲r̲e̲m̲o̲v̲e̲d̲















































FIGURE 5.3-2…01…C̲A̲M̲P̲S̲ ̲R̲E̲M̲O̲T̲E̲ ̲T̲E̲R̲M̲I̲N̲A̲L̲S̲…01…R̲E̲M̲O̲T̲E̲ ̲S̲I̲T̲E̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲ ̲(̲T̲Y̲P̲I̲C̲A̲L̲)̲…01…F̲r̲o̲n̲t̲ ̲e̲l̲e̲v̲a̲t̲i̲o̲n̲,̲
 ̲d̲o̲o̲r̲ ̲r̲e̲m̲o̲v̲e̲d̲


5.3.1    C̲R̲8̲0̲S̲ ̲M̲e̲c̲h̲a̲n̲i̲c̲a̲l̲ ̲S̲y̲s̲t̲e̲m̲

         This section describes the parts that forms the CR80
         S mechanical system.



5.3.1.1  C̲T̲X̲ ̲C̲r̲a̲t̲e̲

         Fig. 5.3.1-1 shows the crate layout. The Crate assembly
         is for 19" rack mounting.

         Figure 5.3.1-2 shows a standard CR80S module, which
         is inserted in the front crate. A PCB connector is
         placed on the rear edge of each module. 

         A motherboard placed on the rear of the front crate
         provides the interconnections between the modules and
         carries rear crate connectors for connection of signal
         and power cables.

         Back panel subassemblies, such as Main Power Panel,
         Adaptor power supply, V24 Back Panel and BSM-X panel
         are mounted on the front of the rear crate. These Back
         Panel Subassemblies are connected to the motherboard
         rear crate connectors by cables.

         Some front crate modules carry signal connectors on
         the front panel.















































                FIGURE 5.3.1-1…01…C̲R̲8̲0̲S̲ ̲C̲R̲A̲T̲E̲















































                      FIGURE 5.3.1-2
                    F̲U̲N̲C̲T̲I̲O̲N̲A̲L̲ ̲M̲O̲D̲U̲L̲E̲


5.3.1.2  C̲o̲o̲l̲i̲n̲g̲ ̲o̲f̲ ̲C̲R̲8̲0̲S̲ ̲C̲r̲a̲t̲e̲s̲

         The TDX, Opto and Adaptor Crate assemblies are cooled
         by the CR80S fan assembly, see fig. 5.3.1-3.

         The fan assembly is used for cooling of two CR80 S
         crates placed one above the other with the fan assembly
         placed below as shown on fig. 5.3.1-4.

         The air intake is at the front of the fan assembly
         and air is blown up through the front crate of the
         CR80S crates.

         The output air stream is directed backwards and will
         leave the rack through perforations in the top plate
         cover of the rack.



5.3.1.3  C̲a̲b̲l̲e̲ ̲C̲h̲a̲n̲n̲e̲l̲ ̲A̲s̲s̲e̲m̲b̲l̲y̲

         Beneath each CR80S crate a Cable Channel Assembly is
         placed. The purpose of this assembly is to guide cables
         from the front to the rear side of the rack, without
         disturbing the effectiveness of the cooling.

         The height of the Cable Channel Assembly is 1U.

















































            FIGURE 5.3.1-3…01…C̲R̲8̲0̲ ̲S̲ ̲F̲A̲N̲ ̲A̲S̲S̲E̲M̲B̲L̲Y̲















































          FIGURE 5.3.1-4…01…A̲I̲R̲F̲L̲O̲W̲ ̲I̲N̲ ̲C̲R̲8̲0̲S̲ ̲C̲R̲A̲T̲E̲S̲


5.3.2    R̲a̲c̲k̲-̲M̲o̲u̲n̲t̲e̲d̲ ̲P̲e̲r̲i̲p̲h̲e̲r̲a̲l̲s̲ ̲a̲n̲d̲ ̲S̲p̲e̲c̲i̲a̲l̲ ̲A̲s̲s̲e̲m̲b̲l̲i̲e̲s̲

         This section describes the configuration items of the
         Main site racks (fig. 5.3-1) and remote site racks
         (fig. 5.3-2), which are not included in the CR80S system
         (see sections 5.3.1).



5.3.2.1  S̲t̲a̲t̲i̲s̲t̲i̲c̲a̲l̲/̲S̲y̲n̲c̲h̲r̲o̲n̲e̲o̲u̲s̲ ̲M̲u̲l̲t̲i̲p̲l̲e̲x̲e̲r̲

         Physical Dimensions:

         The stat. mux. is housed in a 19" rack mounting box,
         2U high.

         The rack mounting box measures:

         Width:      483 mm
         Height:      89 mm
         Depth:      279 mm
         Weight:     less than 10 kgs.

         For further description see section 5.1.3/5.1.4.



5.3.2.2  P̲o̲w̲e̲r̲ ̲L̲i̲n̲e̲ ̲F̲i̲l̲t̲e̲r̲

         The power supply lines are entering the racks through
         power line filters for protection against noise and
         spikes on the power lines.

         A power line filter is designed as a box placed on
         the inside surface of the rack wall and forming a cavity
         in the EMI surface.

         Power line filters used for CRT are placed in CAMPS
         Line Termination Rack E in multibay configurations.
         On remote sites and mainsite 10, a powerline filter
         is included in the stand alone rack.



5.3.2.3  M̲a̲i̲n̲s̲ ̲S̲w̲i̲t̲c̲h̲ ̲A̲s̲s̲e̲m̲b̲l̲y̲

         a)  The main switch assembly are placed in the front,
             bottom position of all racks.



             Power switches and elapsed time indicators are
             placed on the front panel. The mains switch is
             a dual single-phase assembly sourced from the Power
             Line Filter.

         b)  On Main Site 10 (UKAIR) the Main Switch Assembly
             performs a step-down transformation from 240 VAC
             to 220 VAC.



5.3.2.4  P̲o̲w̲e̲r̲ ̲D̲i̲s̲t̲r̲i̲b̲u̲t̲i̲o̲n̲ ̲P̲a̲n̲e̲l̲

         The power distribution panels branches the power lines
         into the number of power input sources required by
         the assemblies of the rack.



5.3.2.5  F̲i̲l̲t̲e̲r̲ ̲B̲o̲x̲ ̲A̲s̲s̲e̲m̲b̲l̲y̲

         All V24 channels to external equipment are passed through
         the Filter Box facility of CAMPS Line termination rack
         F in multi-bay configurations. On remote sites and
         main site 10 a filter box is included in the stand
         alone rack. The principle of the Filter Box design
         is shown on fig. 5.3.2-1.

         The Filter Box forms a cavity in the EMI shielding
         surface of the rack.

         Electrical cables are conducted from the assemblies
         containing V28(L) adapters to a position at the Filter
         Box, where a feed through connector, containing RF-filters,
         passes the signals through the EMI shield, formed by
         the rack.

         Opto cables are passed through the waveguide of the
         Filter Box in the stand alone racks.

         All signal cables are leaving the rack through the
         attached cable duct.

         A cover has to be removed to get access to the connectors
         of the external electrical cables.




















































      FIGURE 5.3.2-1…01…F̲I̲L̲T̲E̲R̲ ̲B̲O̲X̲…01…P̲R̲I̲N̲C̲I̲P̲L̲E̲S̲ ̲O̲F̲ ̲D̲E̲S̲I̲G̲N̲


5.3.3    E̲M̲I̲ ̲S̲h̲i̲e̲l̲d̲e̲d̲ ̲R̲a̲c̲k̲s̲

         A CRT Main Site Installation includes 1 or 2 Racks,
         named Rack G and H. The CRT Remote Site Installation
         includes a single rack. 

         The Racks serve 2 major tasks.

         a)  They contain a 19" Rack-system for mounting of
             assemblies, units, and cables.

         b)  The rack assemblies provide an EMI shielding to
             reduce electromagnetic radiation from the enclosed
             equipment.

         Fig. 5.3.3-1 shows a single rack. The max. dimensions
         shown give the maximum envelope of the rack.

         The rack has 2 doors, a front door and a rear door.
         The front door allows full access to the mounted equipment.

         Front and rear door are of equal size and are hinged
         at the same side of the rack.

         The doors and the cabinet are made of steel.

         Two perforated areas in the front door allow air intake
         for cooling of equipment. The top cover plate of the
         cabinet is perforated to allow output of cooling airflow.

         The gaps between doors and cabinet are blocked by gaskets
         of conducting material.

         The tightness of these gaskets is important for TEMPEST
         performance. The gaskets are wear-out items with a
         3 to 5 year service lifetime.

         The 19" panel mounting rail system included in the
         cabinet is mounted on insulation blocks and the mounted
         equipment is thus galvanically insulated from the EMI
         Shield.

         The "useful depth" of the rack is the distance between
         the mounting surfaces of the front and rear mounting
         rails. The useful depth is 101 cm.















































        FIGURE 5.3.3-1…01…S̲I̲N̲G̲L̲E̲ ̲E̲M̲I̲-̲R̲A̲C̲K̲,̲ ̲D̲I̲M̲E̲N̲S̲I̲O̲N̲S̲


5.3.3.1  S̲t̲a̲n̲d̲ ̲A̲l̲o̲n̲e̲ ̲R̲a̲c̲k̲s̲

         The stand alone racks are used on all Remote Sites
         and on Main Site 10 (UKAIR).

         The stand alone racks have side walls welded to the
         cabinet to form one continuous EMI shield, when doors
         are closed.

         The stand alone racks have provisions for 6 knock-outs
         in the top cover plate. All cabling (power and data
         channels) will enter the stand alone racks in the top.
         A schematic of the top cover plate is shown in fig.
         5.3.3-2.



5.3.3.2  M̲u̲l̲t̲i̲-̲B̲a̲y̲ ̲R̲a̲c̲k̲-̲A̲s̲s̲e̲m̲b̲l̲y̲

         At all main sites, except no. 10, the racks containing
         the CRT main site equipment will be connected to the
         CAMPS Line Termination Rack Assembly to form a multi-bay
         rack. These multi-bay racks consist of single racks,
         bolted together with conducting gaskets inserted. No
         side walls are mounted between neighbouring racks.
         When the doors are closed the multi-bay rack forms
         one continuous EMI shield. The racks to be assembled
         in a multi-bay configuration have provisions for 3
         knock outs in the top cover plate and  3 in the bottom.
         However they will not be used in the standard CRT design,
         as the cabling normally will enter through the CAMPS
         Line Termination Racks.



5.3.3.3  P̲o̲w̲e̲r̲,̲ ̲H̲e̲a̲t̲,̲ ̲a̲n̲d̲ ̲W̲e̲i̲g̲h̲t̲

         In fig. 5.3.3.3-1 is shown the phases of Start-up.

         a)  Initial peak period.

             In the initial period the current is defined by
             initial currents due to saturation in transformers
             and load currents for capacitors.

             Period length and current waveform are depending
             on the characteristics of the power source as well.



             Peak current values of 10-50 times the current
             value in use and a period length less than 100
             ms are expected.

             The power line filters inserted on the power lines
             entering the equipment room will influence the
             initial peak period.

         b)  S̲t̲a̲r̲t̲ ̲P̲e̲r̲i̲o̲d̲

             The start period is defined by the start-up of
             AC-motors in the racks.

             AC-motors are used in Fan assemblies.

             The start period will be in the range 2-20 secs.

         c)  U̲s̲e̲ ̲P̲e̲r̲i̲o̲d̲ 

             Use period characteristics are the characteristics
             of the equipment in normal use after termination
             of start-up phenomena.

         The power and weight data of the individual racks are
         tabulated in fig. 5.3.3.3-2.

         The values shall be considered as typical.















































     FIGURE 5.3.3.3-1…01…S̲t̲a̲r̲t̲-̲u̲p̲ ̲C̲u̲r̲r̲e̲n̲t̲s̲,̲ ̲D̲e̲f̲i̲n̲i̲t̲i̲o̲n̲s̲







                CONSUMPTION USE  START      HEAT     AIRFLOW  WEIGHT
                ---------------- CURRENT    DISSIPA- M…0e…3…0f…/S     KG
                POWER, CURRENT,  AMP        TION W
                KVA    A
                 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
                ̲ ̲ ̲

Main Site Equip.

  Rack G, J     0,80   3,7       4,0        750      0.06     450

  Rack H, I     1,00   4,5       4,8        900      0.06     460

Remote Site Equip.

  Rack          0,45   2,0       2,3        500      0,06     450
























FIGURE 5.3.3.3-2…01…I̲N̲D̲I̲V̲I̲D̲U̲A̲L̲ ̲R̲A̲C̲K̲S̲,̲ ̲P̲O̲W̲E̲R̲ ̲A̲N̲D̲ ̲W̲E̲I̲G̲H̲T̲…01…T̲Y̲P̲I̲C̲A̲L̲ ̲V̲A̲L̲U̲E̲S̲


5.3.3.4  G̲r̲o̲u̲n̲d̲i̲n̲g̲ ̲o̲f̲ ̲R̲a̲c̲k̲s̲ ̲a̲n̲d̲ ̲E̲q̲u̲i̲p̲m̲e̲n̲t̲ ̲i̲n̲ ̲R̲a̲c̲k̲s̲

         The panel mounting rails in the racks are mounted insulated.
         Thus, all equipment in one rack is grounded together,
         but basically insulated from the exterior rack.

         A ground-wire connects the rack-mounted equipment to
         the rack in one point. This point is connected to the
         exterior ground wire connection point.

         When more racks are joined to form a multi-bay rack
         assembly, they are connected around the joining perimeters
         to form one continuous cabinet. In the cabinet the
         rack mounted equipment is connected to one common point.
         This point is connected to the exterior ground wire
         connection point of the cabinet.