⟦2913ce5b3⟧ Wang Wps File

    Length: 7747 (0x1e43)
    Types: Wang Wps File
    Notes: CPS/TRP/003               
    Names: »2319A «

Derivation

└─⟦81108f261⟧ Bits:30006114 8" Wang WCS floppy, CR 0183A
    └─ ⟦this⟧ »2319A « 

WangText




…02…CPS/TRP/003

…02…CSV/820616…02……02…#
S-FAN UNIT CR 8105S/010--/00
FAQ TEST REPORT…02……02…CAMPS








                    T̲A̲B̲L̲E̲ ̲O̲F̲ ̲C̲O̲N̲T̲E̲N̲T̲S̲



   1  INTRODUCTION ..................................
      4

   2  APPLICABLE DOCUMENTS ..........................
      4

   3  TEST EQUIPMENTS ...............................
      4

   4  TEST CONDITIONS AND MEASURING METHODS .........
      5

     4.1 RACK CONFIGURATION .........................
            5
     4.2 CRATE CONFIGURATION ........................
            6
     4.3 TEMPERATURE MEASURING METHODS ..............
            7

   5 TEST PROCEDURE .................................
        9

     5.1 NORMAL CONDITIONS ..........................
            9
     5.2 VARIATION OF MAINS VOLTAGE .................
            9
     5.3 VARIATION OF MAINS FREQUENCY ...............
            9

   6  TEST RESULTS ..................................
     10

     6.1 NORMAL CONDITIONS ..........................
           10
     6.2 VARIATION OF MAINS VOLTAGE .................
           10
     6.3 VARIATION OF MAINS FREQUENCY ...............
           12
     6.4 CONCLUSION .................................
           12


                     1̲ ̲ ̲I̲N̲T̲R̲O̲D̲U̲C̲T̲I̲O̲N̲



         The FAQ test of the S-Fan Unit primary is a test of
         the cooling efficiency for variation in mains voltage
         in the range 220V + 10%/- 15%, and variation in mains
         frequency in the range 50 Hz +/- 10%.

         The test is made on an S-Fan and two TDX-Crate Assemblies
         in CAMPS Line Termination Racks.

         The temperature measuring and test methods are made
         according to Temperature requirements for the CR 80,
         EDD/005/RSP/0001.




                 2̲ ̲ ̲A̲P̲P̲L̲I̲C̲A̲B̲L̲E̲ ̲D̲O̲C̲U̲M̲E̲N̲T̲S̲



         Temperature Requirements for CR80S
         EDD/005/RSP/0001

         Measurements of Forced Cooling
         Efficiency for CR80M Systems
         CSD/008/TRP/0088




                    3̲ ̲ ̲T̲E̲S̲T̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲S̲



         S̲t̲a̲t̲i̲c̲ ̲F̲r̲e̲q̲u̲e̲n̲c̲y̲ ̲S̲t̲a̲b̲i̲l̲i̲z̲e̲r̲

         Abacus Controls Inc., Type 1152-3
         Modified for variation of frequency

         D̲i̲g̲i̲t̲a̲l̲ ̲T̲h̲e̲r̲m̲o̲m̲e̲t̲e̲r̲

         Frode Pedersen & Co, Type 204
         3 digits, tolerances +/- 1…0e…o…0f… C
         Thermocuple Type: Fe/K



         P̲o̲w̲e̲r̲ ̲M̲e̲t̲e̲r̲

         Laur. Knudsen Mek. Etabl. A/S, Type L9

         O̲s̲c̲i̲l̲l̲o̲s̲c̲o̲p̲e̲

         Tektronix 465B




         4̲ ̲ ̲T̲E̲S̲T̲ ̲C̲O̲N̲D̲I̲T̲I̲O̲N̲S̲ ̲A̲N̲D̲ ̲M̲E̲A̲S̲U̲R̲I̲N̲G̲ ̲M̲E̲T̲H̲O̲D̲S̲



4.1      R̲A̲C̲K̲ ̲C̲O̲N̲F̲I̲G̲U̲R̲A̲T̲I̲O̲N̲

         The tested S-Fan Unit and TDX-Crate Assemblies were
         located in CAMPS Line Termination Racks (Figure 4.1-1).

         The Cable Channel Assemblies between the S-Fan Unit
         and the TDX-Crate, and between the two TDX-crates,
         act as a chimney for the airflow.

         In the FAQ test period the rear doors were locked,
         and the front doors were open. During measurements
         the front doors were locked for a period, but it seems
         not to affect the outlet temperatures.

         During test all equipment in the racks was turned on.



















        Figure 4.1-1…01…CAMPS LINE TERMINATION RACKS


4.2      C̲R̲A̲T̲E̲ ̲C̲O̲N̲F̲I̲G̲U̲R̲A̲T̲I̲O̲N̲

         The tested TDX-Crate Assemblies are CAMPS configurations.

         Figure 4.2-1 and 4.2-2 show the modules and their location
         in the Crate. In front slots without modules, there
         is a front blank panel.
















                       Figure 4.2-1
                  TDX ̲CRATE ASSEMBLY # 2














                       Figure 4.2-2
                  TDX-CRATE ASSEMBLY # 1



4.3      T̲E̲M̲P̲E̲R̲A̲T̲U̲R̲E̲ ̲M̲E̲A̲S̲U̲R̲I̲N̲G̲ ̲M̲E̲T̲H̲O̲D̲S̲

         The temperature rise is found by measuring the air
         outlet temperature over the PCB Modules and from that
         subtract the air inlet temperature in front of the
         S-Fan Unit.

         The S-Fan Unit inlet temperature is the average of
         tree measurings, see figure 4.3-1. 

         Y:   40 +/- 20 mm
         Z:   30 +/- 20 mm
         X1: 115 +/- 30 mm
         X2: 265 +/- 30 mm
         X3: 415 +/- 30 mm


























         Inlet Temperature front T…0f…I…0e… = (T…0f…I1…0e… + T…0f…I2…0e… + T…0f…I3)/3


FIGURE 4.3-1…01…FAN UNIT INLET TEMPERATURE MEASUREMENT POINTS


         The outlet temperature is measured over the PCB-Modules
         with the sensor placed in the gridholes and in gridlevel.
         The temperature measuring is done in 4 points over
         the slots in the front Crate, see figure 4.3-2.



























FIGURE 4.3-2…01…FRONT MODULE OUTLET TEMPERATURE MEASUREMENT POINTS





         Settling time before measurement: Settling time for
         temperature sensor + 30 seconds.



                    5̲ ̲ ̲T̲E̲S̲T̲ ̲P̲R̲O̲C̲E̲D̲U̲R̲E̲



5.1      N̲O̲R̲M̲A̲L̲ ̲C̲O̲N̲D̲I̲T̲I̲O̲N̲S̲

         Measure of the inlet and outlet temperatures using
         the methods shown in section 4.3 and under the following
         conditions:

         Mains, Crate, Fan:             220V/50Hz
         Conditions mentioned in section 4.1 and 4.2



5.2      V̲A̲R̲I̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲M̲A̲I̲N̲S̲ ̲V̲O̲L̲T̲A̲G̲E̲

         Measure of the outlet temperature for Fan Unit voltage
         220V - 15% = 187V and 220V + 10% = 242V

         Other conditions as under section 5.1.

         The temperature measurement is made in 2 points with
         high, 2 points with medium and 2 points with low temperature.
         Settling time before measurement: 60 minutes.



5.3      V̲A̲R̲I̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲M̲A̲I̲N̲S̲ ̲F̲R̲E̲Q̲U̲E̲N̲C̲Y̲

         Measure of the outlet temperature for Fan Unit mains
         frequency 50 Hz - 10% = 45 Hz and 50 Hz + 10% = 55
         Hz.

         Other conditions as under section 5.1.

         The temperature measurement is made in 2 points with
         high, 2 points with medium, and 2 points with low temperature.

         Settling time before measurement: 60 minutes.






                     6̲ ̲ ̲T̲E̲S̲T̲ ̲R̲E̲S̲U̲L̲T̲S̲



6.1      N̲O̲R̲M̲A̲L̲ ̲C̲O̲N̲D̲I̲T̲I̲O̲N̲S̲

         Temperature measuremets made under normal conditions
         are shown in figure 6.1-1.



6.2      V̲A̲R̲I̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲M̲A̲I̲N̲S̲ ̲V̲O̲L̲T̲A̲G̲E̲

          ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
         ̲ ̲ ̲ ̲ ̲ ̲

               MEASURED OUTLET AIR TEMPERATURES …0e…o…0f…C         
            
          ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
         ̲ ̲ ̲ ̲ ̲ ̲

         S̲L̲O̲T̲/̲M̲E̲A̲S̲.̲ ̲P̲O̲I̲N̲T̲ ̲ ̲ ̲ ̲1̲7̲0̲V̲ ̲ ̲ ̲ ̲1̲8̲7̲V̲ ̲ ̲ ̲ ̲2̲2̲0̲V̲ ̲ ̲ ̲ ̲2̲4̲2̲V̲ ̲ ̲
         ̲ ̲2̲7̲0̲V̲

         1̲1̲/̲T̲1̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲5̲6̲ ̲ ̲ ̲ ̲ ̲ ̲5̲6̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲5̲5̲ ̲ ̲ ̲ ̲ ̲5̲5̲ ̲ ̲ ̲
         ̲ ̲ ̲5̲5̲

         3̲/̲T̲2̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲5̲ ̲ ̲ ̲ ̲ ̲ ̲4̲5̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲5̲ ̲ ̲ ̲ ̲ ̲4̲4̲ ̲ ̲ ̲
         ̲ ̲ ̲4̲5̲

         2̲0̲/̲T̲3̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲
         ̲ ̲ ̲4̲1̲

         8̲/̲T̲3̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲
         ̲ ̲ ̲4̲0̲

         2̲/̲T̲3̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲
         ̲ ̲ ̲4̲0̲

         5̲/̲T̲2̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲3̲7̲ ̲ ̲ ̲ ̲ ̲ ̲3̲7̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲3̲6̲ ̲ ̲ ̲ ̲ ̲3̲7̲ ̲ ̲ ̲
         ̲ ̲ ̲3̲7̲



















































                       Figure 6.1-1
TEMPERATURE RISE,NORMAL CONDITIONS CAMPS TDX-CRATE ASSEMBLY #2


6.3      V̲A̲R̲I̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲M̲A̲I̲N̲S̲ ̲F̲R̲E̲Q̲U̲E̲N̲C̲Y̲

          ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
         ̲ ̲ ̲ ̲ ̲ ̲

                 MEASURED OUTLET AIR TEMPERATURES …0e…o…0f…C       
            
          ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
         ̲ ̲ ̲ ̲ ̲ ̲

         S̲L̲O̲T̲/̲M̲E̲A̲S̲.̲ ̲P̲O̲I̲N̲T̲ ̲ ̲ ̲ ̲4̲0̲H̲z̲ ̲ ̲ ̲ ̲4̲5̲H̲z̲ ̲ ̲ ̲ ̲5̲0̲H̲z̲ ̲ ̲ ̲ ̲5̲5̲H̲z̲ ̲ ̲
         ̲ ̲6̲0̲H̲z̲

         1̲1̲/̲T̲1̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲5̲7̲ ̲ ̲ ̲ ̲ ̲ ̲5̲6̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲5̲5̲ ̲ ̲ ̲ ̲ ̲5̲4̲ ̲ ̲ ̲
         ̲ ̲ ̲5̲4̲

         3̲/̲T̲2̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲5̲ ̲ ̲ ̲ ̲ ̲ ̲4̲5̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲5̲ ̲ ̲ ̲ ̲ ̲4̲4̲ ̲ ̲ ̲
         ̲ ̲ ̲4̲3̲

         2̲0̲/̲T̲3̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲
         ̲ ̲ ̲3̲9̲

         8̲/̲T̲3̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲2̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲
         ̲ ̲ ̲4̲0̲

         2̲/̲T̲3̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲ ̲ ̲3̲9̲ ̲ ̲ ̲
         ̲ ̲ ̲3̲9̲

         5̲/̲T̲2̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲3̲6̲ ̲ ̲ ̲ ̲ ̲ ̲3̲7̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲3̲6̲ ̲ ̲ ̲ ̲ ̲3̲7̲ ̲ ̲ ̲
         ̲ ̲ ̲3̲7̲


6.4      C̲O̲N̲C̲L̲U̲S̲I̲O̲N̲

         Variation in mains voltage in the range 220V + 10%/-15%
         has no effect on the cooling efficiency.

         Variation in mains frequency in the range 50Hz +/-
         10% affect the highest outlet temperatures with about
         +/- 1…0e…o…0f…C.

         The conclusion of these measurements must be that variations
         in mains supply in the range 220V + 10%/-15%, 50Hz
         +/- 10% only have a negligible effect on the S-Fan
         units cooling effieciency.