WangText
…02…CPS/TRP/003
…02…CSV/820616…02……02…#
S-FAN UNIT CR 8105S/010--/00
FAQ TEST REPORT…02……02…CAMPS
T̲A̲B̲L̲E̲ ̲O̲F̲ ̲C̲O̲N̲T̲E̲N̲T̲S̲
1 INTRODUCTION ..................................
4
2 APPLICABLE DOCUMENTS ..........................
4
3 TEST EQUIPMENTS ...............................
4
4 TEST CONDITIONS AND MEASURING METHODS .........
5
4.1 RACK CONFIGURATION .........................
5
4.2 CRATE CONFIGURATION ........................
6
4.3 TEMPERATURE MEASURING METHODS ..............
7
5 TEST PROCEDURE .................................
9
5.1 NORMAL CONDITIONS ..........................
9
5.2 VARIATION OF MAINS VOLTAGE .................
9
5.3 VARIATION OF MAINS FREQUENCY ...............
9
6 TEST RESULTS ..................................
10
6.1 NORMAL CONDITIONS ..........................
10
6.2 VARIATION OF MAINS VOLTAGE .................
10
6.3 VARIATION OF MAINS FREQUENCY ...............
12
6.4 CONCLUSION .................................
12
1̲ ̲ ̲I̲N̲T̲R̲O̲D̲U̲C̲T̲I̲O̲N̲
The FAQ test of the S-Fan Unit primary is a test of
the cooling efficiency for variation in mains voltage
in the range 220V + 10%/- 15%, and variation in mains
frequency in the range 50 Hz +/- 10%.
The test is made on an S-Fan and two TDX-Crate Assemblies
in CAMPS Line Termination Racks.
The temperature measuring and test methods are made
according to Temperature requirements for the CR 80,
EDD/005/RSP/0001.
2̲ ̲ ̲A̲P̲P̲L̲I̲C̲A̲B̲L̲E̲ ̲D̲O̲C̲U̲M̲E̲N̲T̲S̲
Temperature Requirements for CR80S
EDD/005/RSP/0001
Measurements of Forced Cooling
Efficiency for CR80M Systems
CSD/008/TRP/0088
3̲ ̲ ̲T̲E̲S̲T̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲S̲
S̲t̲a̲t̲i̲c̲ ̲F̲r̲e̲q̲u̲e̲n̲c̲y̲ ̲S̲t̲a̲b̲i̲l̲i̲z̲e̲r̲
Abacus Controls Inc., Type 1152-3
Modified for variation of frequency
D̲i̲g̲i̲t̲a̲l̲ ̲T̲h̲e̲r̲m̲o̲m̲e̲t̲e̲r̲
Frode Pedersen & Co, Type 204
3 digits, tolerances +/- 1…0e…o…0f… C
Thermocuple Type: Fe/K
P̲o̲w̲e̲r̲ ̲M̲e̲t̲e̲r̲
Laur. Knudsen Mek. Etabl. A/S, Type L9
O̲s̲c̲i̲l̲l̲o̲s̲c̲o̲p̲e̲
Tektronix 465B
4̲ ̲ ̲T̲E̲S̲T̲ ̲C̲O̲N̲D̲I̲T̲I̲O̲N̲S̲ ̲A̲N̲D̲ ̲M̲E̲A̲S̲U̲R̲I̲N̲G̲ ̲M̲E̲T̲H̲O̲D̲S̲
4.1 R̲A̲C̲K̲ ̲C̲O̲N̲F̲I̲G̲U̲R̲A̲T̲I̲O̲N̲
The tested S-Fan Unit and TDX-Crate Assemblies were
located in CAMPS Line Termination Racks (Figure 4.1-1).
The Cable Channel Assemblies between the S-Fan Unit
and the TDX-Crate, and between the two TDX-crates,
act as a chimney for the airflow.
In the FAQ test period the rear doors were locked,
and the front doors were open. During measurements
the front doors were locked for a period, but it seems
not to affect the outlet temperatures.
During test all equipment in the racks was turned on.
Figure 4.1-1…01…CAMPS LINE TERMINATION RACKS
4.2 C̲R̲A̲T̲E̲ ̲C̲O̲N̲F̲I̲G̲U̲R̲A̲T̲I̲O̲N̲
The tested TDX-Crate Assemblies are CAMPS configurations.
Figure 4.2-1 and 4.2-2 show the modules and their location
in the Crate. In front slots without modules, there
is a front blank panel.
Figure 4.2-1
TDX ̲CRATE ASSEMBLY # 2
Figure 4.2-2
TDX-CRATE ASSEMBLY # 1
4.3 T̲E̲M̲P̲E̲R̲A̲T̲U̲R̲E̲ ̲M̲E̲A̲S̲U̲R̲I̲N̲G̲ ̲M̲E̲T̲H̲O̲D̲S̲
The temperature rise is found by measuring the air
outlet temperature over the PCB Modules and from that
subtract the air inlet temperature in front of the
S-Fan Unit.
The S-Fan Unit inlet temperature is the average of
tree measurings, see figure 4.3-1.
Y: 40 +/- 20 mm
Z: 30 +/- 20 mm
X1: 115 +/- 30 mm
X2: 265 +/- 30 mm
X3: 415 +/- 30 mm
Inlet Temperature front T…0f…I…0e… = (T…0f…I1…0e… + T…0f…I2…0e… + T…0f…I3)/3
FIGURE 4.3-1…01…FAN UNIT INLET TEMPERATURE MEASUREMENT POINTS
The outlet temperature is measured over the PCB-Modules
with the sensor placed in the gridholes and in gridlevel.
The temperature measuring is done in 4 points over
the slots in the front Crate, see figure 4.3-2.
FIGURE 4.3-2…01…FRONT MODULE OUTLET TEMPERATURE MEASUREMENT POINTS
Settling time before measurement: Settling time for
temperature sensor + 30 seconds.
5̲ ̲ ̲T̲E̲S̲T̲ ̲P̲R̲O̲C̲E̲D̲U̲R̲E̲
5.1 N̲O̲R̲M̲A̲L̲ ̲C̲O̲N̲D̲I̲T̲I̲O̲N̲S̲
Measure of the inlet and outlet temperatures using
the methods shown in section 4.3 and under the following
conditions:
Mains, Crate, Fan: 220V/50Hz
Conditions mentioned in section 4.1 and 4.2
5.2 V̲A̲R̲I̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲M̲A̲I̲N̲S̲ ̲V̲O̲L̲T̲A̲G̲E̲
Measure of the outlet temperature for Fan Unit voltage
220V - 15% = 187V and 220V + 10% = 242V
Other conditions as under section 5.1.
The temperature measurement is made in 2 points with
high, 2 points with medium and 2 points with low temperature.
Settling time before measurement: 60 minutes.
5.3 V̲A̲R̲I̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲M̲A̲I̲N̲S̲ ̲F̲R̲E̲Q̲U̲E̲N̲C̲Y̲
Measure of the outlet temperature for Fan Unit mains
frequency 50 Hz - 10% = 45 Hz and 50 Hz + 10% = 55
Hz.
Other conditions as under section 5.1.
The temperature measurement is made in 2 points with
high, 2 points with medium, and 2 points with low temperature.
Settling time before measurement: 60 minutes.
6̲ ̲ ̲T̲E̲S̲T̲ ̲R̲E̲S̲U̲L̲T̲S̲
6.1 N̲O̲R̲M̲A̲L̲ ̲C̲O̲N̲D̲I̲T̲I̲O̲N̲S̲
Temperature measuremets made under normal conditions
are shown in figure 6.1-1.
6.2 V̲A̲R̲I̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲M̲A̲I̲N̲S̲ ̲V̲O̲L̲T̲A̲G̲E̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲
MEASURED OUTLET AIR TEMPERATURES …0e…o…0f…C
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲
S̲L̲O̲T̲/̲M̲E̲A̲S̲.̲ ̲P̲O̲I̲N̲T̲ ̲ ̲ ̲ ̲1̲7̲0̲V̲ ̲ ̲ ̲ ̲1̲8̲7̲V̲ ̲ ̲ ̲ ̲2̲2̲0̲V̲ ̲ ̲ ̲ ̲2̲4̲2̲V̲ ̲ ̲
̲ ̲2̲7̲0̲V̲
1̲1̲/̲T̲1̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲5̲6̲ ̲ ̲ ̲ ̲ ̲ ̲5̲6̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲5̲5̲ ̲ ̲ ̲ ̲ ̲5̲5̲ ̲ ̲ ̲
̲ ̲ ̲5̲5̲
3̲/̲T̲2̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲5̲ ̲ ̲ ̲ ̲ ̲ ̲4̲5̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲5̲ ̲ ̲ ̲ ̲ ̲4̲4̲ ̲ ̲ ̲
̲ ̲ ̲4̲5̲
2̲0̲/̲T̲3̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲
̲ ̲ ̲4̲1̲
8̲/̲T̲3̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲
̲ ̲ ̲4̲0̲
2̲/̲T̲3̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲
̲ ̲ ̲4̲0̲
5̲/̲T̲2̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲3̲7̲ ̲ ̲ ̲ ̲ ̲ ̲3̲7̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲3̲6̲ ̲ ̲ ̲ ̲ ̲3̲7̲ ̲ ̲ ̲
̲ ̲ ̲3̲7̲
Figure 6.1-1
TEMPERATURE RISE,NORMAL CONDITIONS CAMPS TDX-CRATE ASSEMBLY #2
6.3 V̲A̲R̲I̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲M̲A̲I̲N̲S̲ ̲F̲R̲E̲Q̲U̲E̲N̲C̲Y̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲
MEASURED OUTLET AIR TEMPERATURES …0e…o…0f…C
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲
S̲L̲O̲T̲/̲M̲E̲A̲S̲.̲ ̲P̲O̲I̲N̲T̲ ̲ ̲ ̲ ̲4̲0̲H̲z̲ ̲ ̲ ̲ ̲4̲5̲H̲z̲ ̲ ̲ ̲ ̲5̲0̲H̲z̲ ̲ ̲ ̲ ̲5̲5̲H̲z̲ ̲ ̲
̲ ̲6̲0̲H̲z̲
1̲1̲/̲T̲1̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲5̲7̲ ̲ ̲ ̲ ̲ ̲ ̲5̲6̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲5̲5̲ ̲ ̲ ̲ ̲ ̲5̲4̲ ̲ ̲ ̲
̲ ̲ ̲5̲4̲
3̲/̲T̲2̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲5̲ ̲ ̲ ̲ ̲ ̲ ̲4̲5̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲5̲ ̲ ̲ ̲ ̲ ̲4̲4̲ ̲ ̲ ̲
̲ ̲ ̲4̲3̲
2̲0̲/̲T̲3̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲
̲ ̲ ̲3̲9̲
8̲/̲T̲3̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲2̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲1̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲
̲ ̲ ̲4̲0̲
2̲/̲T̲3̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲0̲ ̲ ̲ ̲ ̲ ̲3̲9̲ ̲ ̲ ̲
̲ ̲ ̲3̲9̲
5̲/̲T̲2̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲3̲6̲ ̲ ̲ ̲ ̲ ̲ ̲3̲7̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲3̲6̲ ̲ ̲ ̲ ̲ ̲3̲7̲ ̲ ̲ ̲
̲ ̲ ̲3̲7̲
6.4 C̲O̲N̲C̲L̲U̲S̲I̲O̲N̲
Variation in mains voltage in the range 220V + 10%/-15%
has no effect on the cooling efficiency.
Variation in mains frequency in the range 50Hz +/-
10% affect the highest outlet temperatures with about
+/- 1…0e…o…0f…C.
The conclusion of these measurements must be that variations
in mains supply in the range 220V + 10%/-15%, 50Hz
+/- 10% only have a negligible effect on the S-Fan
units cooling effieciency.