FIGURE 5.3.3.3-1…01…S̲t̲a̲r̲t̲-̲u̲p̲ ̲C̲u̲r̲r̲e̲n̲t̲s̲,̲ ̲D̲e̲f̲i̲n̲i̲t̲i̲o̲n̲s̲…86…1         …02…   …02…  …02…    …02…           …02…           
                    





                CONSUMPTION USE  START      HEAT     AIRFLOW  WEIGHT
                ---------------- CURRENT    DISSIPA- M…0e…3…0f…/S     KG
                POWER, CURREN,   AMP        TION W
                KVA    A
                 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
                ̲ ̲ ̲

Main Site Equip.

  Rack G        0,80   3,7       4,0        750      0.06     450

  Rack H        1,00   4,5       4,8        900      0.06     460

Remote Site Equip.

  Rack          0,45   2,0       2,3        500      0,06     450
























FIGUE 5.3.3.3-2…01…I̲N̲D̲I̲V̲I̲D̲U̲A̲L̲ ̲R̲A̲C̲K̲S̲,̲ ̲P̲O̲W̲E̲R̲ ̲A̲N̲D̲ ̲W̲E̲I̲G̲H̲T̲…01…T̲Y̲P̲I̲C̲A̲L̲ ̲V̲A̲L̲U̲E̲S̲…86…1         …02…   …02…  …02…    …02…           …02…       
                        
5.3.3.4         G̲r̲o̲u̲n̲d̲i̲n̲g̲ ̲o̲f̲ ̲R̲a̲c̲k̲s̲ ̲a̲n̲d̲ ̲E̲q̲u̲i̲p̲m̲e̲n̲t̲ ̲i̲n̲ ̲R̲a̲c̲k̲s̲

                The panel mounting rails in the racks are mounted insulated.
                Thus, all equipment in one rack is grounded together,
                but basicallyinsulated from the exterior rack.

                A ground-wire connects the rack-mounted equipment to
                the rack in one point. This point is connected to the
                exterior ground wire connection point.

                When more racks are joined to form a multi-bay rack
                assembly, thy are connected around the joining perimeters
                to form one continuous cabinet. In the cabinet the
                rack mounted equipment is connected to one common point.
                This point is connected to the exterior ground wire
                connection point of the cabinet.