⟦3d87ca900⟧ Wang Wps File
Length: 75786 (0x1280a)
Types: Wang Wps File
Notes: CPS/INM/001 (II)
Names: »2738A «
Derivation
└─⟦74592f894⟧ Bits:30006167 8" Wang WCS floppy, CR 0226A
└─ ⟦this⟧ »2738A «
WangText
:…08…:…0e…: 9…09…9…0e…9
8…0a…8…0d…8…01…8 8…06…7…0c…7…0f…7…02…7…06…6…0b…6…0d…6…06…5…0a…5…02…5 5…07…4…0b……86…1
…02…
…02…
…02…
2738A/ktd
…02…CPS/INM/001
…02…HAU/830620…02……02…#
CAMPS
INSTALLATION
MANUAL
FOR
SITE
01…02……02…CAMPS
4 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲S̲I̲T̲E̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲
4.1 G̲E̲N̲E̲R̲A̲L̲
The following step by step installation procedure contains
a detailed instruction set of how to install the CR
delivered computer racks, frequency stabilizer, supervisory
positions, maintenance position, and user terminals.
The major tasks of the installation sequence are:
4.2 Mechanical rack assembly
4.3 Termination of external power cables and mounting
of conduits
4.4 Installation of external signal cables and
mounting of conduits rack C, D, F and G.
4.5 Remounting of racks
4.6 Installation and termination of internal signal
cables
4.7 Installation of external signal cables
4.8 Connection of internal power cables
4.9 Power up and check out
4.10 Inspection of status LEDs
4.11 Installation of Delta VDU
4.12 Installation of Tracor MSP
4.13 Installation of PTP/PTR
4.14 Test of Supp/User Terminals
4.15 Test of PTP/PTR
4.16 H/W Test Processor/Line term. units
4.17 Inventory check
Throughout the installation instruction, references
are made to the AB-Drawings (Appendix A) and the CAMPS
Hardware Breakdown/Hardware Tree (Doc. CPS/SDS/017).
4.2 M̲E̲C̲H̲A̲N̲I̲C̲A̲L̲ ̲R̲A̲C̲K̲ ̲A̲S̲S̲E̲M̲B̲L̲Y̲
4.2.1 U̲n̲p̲a̲c̲k̲i̲n̲g̲ ̲o̲f̲ ̲R̲a̲c̲k̲s̲
a) Each of the 7 EMI racks for the main site are separately
packed in the original wooden container. The racks
should remain packed during site internal transportation
and only be unpacked close to the installation
site, but if the space along the access route is
limited, the racks can be unpacked before transportation
to the installation site. The racks are unpacked
as follows:
b) Remove the top cover of the wooden container by
demounting the 3 EA 1/4 x 2 1/2" bolts on each
side of the container and the 4EA 1/2 - 13 x 2"
bolts, one in each top corner (see Figure 4.1).
c) The 4 walls of the container are removed by loosening
the 21 EA 1/4 x 2 1/2" bolts on each short side.
d) The rack is bolted to the container bottom in each
corner by a 1/2 - 13 x 2 1/2" bolt.
e) These bolts are removed from under the container
bottom.
Figure 4.1
UNPACKING PROCEDURE - EMI RACK
4.2.2 T̲r̲a̲n̲s̲p̲o̲r̲t̲a̲t̲i̲o̲n̲ ̲t̲o̲ ̲I̲n̲s̲t̲a̲l̲l̲a̲t̲i̲o̲n̲ ̲S̲i̲t̲e̲
a) After unpacking, the front and rear door of the
racks must be removed. Check that serial numbers
in
the racks correspond to the serial numbers of the
doors.
b) Be careful not to damage the gaskets of the doors.
c) Depending on means of transportation, 4 eyelets
can be mounted in the top of the rack in the position
of the removed 4 EA 1/2 - 13 x 2" bolts.
d) 5 terminal tables out of the CR delivered 15 tables
are moved into the CAMPS area for the maintenance
and supervisor positions.
e) The FREQ Stabilizer and the storage cabinet are
moved into the CAMPS area.
f) All terminals (28 VDU and 11 MSP) are distributed
to their respective installation sites, unpacked
and the empties removed.
4.2.3 R̲e̲m̲o̲v̲a̲l̲ ̲o̲f̲ ̲U̲p̲p̲e̲r̲ ̲C̲r̲a̲t̲e̲s̲ ̲a̲n̲d̲ ̲D̲-̲F̲a̲n̲s̲
a) To get access for bolting the single racks into
3 bay and 4 bay units, the upper crate in B, C
and E must be removed.
b) Dismount all connected front and rear cables.
c) Dismount the power cables on the rear side of the
M-fan in rack B and C.
Loosen the 4 6mm front screws and pull out the
fan units from the front of the racks.
d) Loosen the 8 (M-crate) and 4 (S-crate) 6mm front
screws and pull out the crates by the handles from
the front of the racks.
Figure 4.2
MOUNTING OF GASKETS
4.2.4 R̲e̲m̲o̲v̲a̲l̲ ̲o̲f̲ ̲M̲a̲i̲n̲ ̲S̲w̲i̲t̲c̲h̲e̲s̲
a) To get access for bolting the rack in the bottom,
the main switches in rack B, C, E, F, and G must
be removed.
b) Dismount the power cables and the ground wire on
the rear side of the main switches.
c) Loosen the 4 6mm front screws and pull out the
main switches from the front of the racks.
4.2.5 M̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲L̲e̲v̲e̲l̲l̲e̲r̲s̲
The 4 levellers are mounted from under the racks two
by two, by tilting the racks (see AB drawing 115)
The levellers are mounted to a distance of approx.
20 mm between the bottom of the rack and the floor.
4.2.6 M̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲G̲a̲s̲k̲e̲t̲s̲
a) To secure a correct shielding between the racks,
gasket strips must be mounted before bolting the
racks into 3 or 4 BAY units. See fig. 4.2. The
gaskets, having pressure sensitive tape adhesive,
must be applied at room temperature as follows:
b) Clean the mounting surface of old glue, if necessary,
with a laquer thinner (acetone or tri-chlorethylene).
c) Cut and trim the gasket strip with scissors.
d) Peel off the protective paper backing.
e) Be sure that the strip is in correct position and
then press down firmly.
4.2.7 L̲e̲v̲e̲l̲l̲i̲n̲g̲ ̲a̲n̲d̲ ̲B̲o̲l̲t̲i̲n̲g̲ ̲o̲f̲ ̲R̲a̲c̲k̲s̲
C̲A̲U̲T̲I̲O̲N̲: Before tightening the bolts, check that
all gaskets between the racks are
undamaged.
a) The racks are aligned one by one to allow the 1/4-20
x 7/8 LG bolts to pass through the frames of the
cabinets.
b) The single racks A, B, and C are bolted together
to form the 3-bay processor rack assembly.
c) The single racks D, E, F, and G are bolted together
to form the 4-bay line termination rack assembly
(for details ref. AB drawings 110/115).
d) When all bolts are placed (24 bolts between each
pair of racks), the bolts are to be tightened on
opposite sides, alternatively, starting at opposite
ends of the corresponding sides.
C̲A̲U̲T̲I̲O̲N̲:̲ A min. of 50 mm space must be kept between
rack C and rack D.
e) When all bolts have been tightened, the levellers
must again be adjusted to ensure equal distribution
of the floor load.
f) For adjusting the floor levellers use a pipe wrench.
Grip around the lower part of the leveller and
turn it clockwise until the levellers tighten against
the floor.
g) To check that the racks are true to spirit level,
use the spirit leveller on top of the racks.
Readjust if necessary.
4.2.8 M̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲P̲o̲w̲e̲r̲ ̲L̲i̲n̲e̲ ̲F̲i̲l̲t̲e̲r̲s̲ ̲R̲a̲c̲k̲ ̲A̲,̲ ̲B̲,̲ ̲a̲n̲d̲ ̲E̲
a) Place the power line filter (PLF) below the two
knockouts in the top of the rack (see AB drawing
121 in appendix A).
The 2 1/2" male adaptor, welded to the PLF, must
be inserted through the left hand knockout
b) Place the tightening nut from the outside of the
EMI rack.
c) Insert the 2 1/2" to 1 1/2" reducing bushing through
the right hand knockout into the PLF.
d) Mount the 1 1/2" steel tube into the reducing bushing.
It is very important to the shielding effectiveness
that the fittings are fully tightened.
4.2.9 R̲e̲m̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲U̲p̲p̲e̲r̲ ̲C̲r̲a̲t̲e̲s̲ ̲a̲n̲d̲ ̲M̲-̲f̲a̲n̲s̲
a) The upper crates of rack B and C are reinserted
and tightened by the 8 x 6mm front screws.
b) The M-fans of rack B and C are reinserted and tightened
by the 4 x 6mm front screws.
c) The TDX crate of rack E, is reinserted and tightened
by the 4 x 6mm front screws.
All removed signal cables are to be reinstalled during
step 4.6, and the power cables during step 4.8.
4.2.10 R̲e̲m̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲M̲a̲i̲n̲ ̲S̲w̲i̲t̲c̲h̲e̲s̲
a) The main switches are reinserted from the front
of the racks and tightened by the 4 x 6mm front
screws.
b) Reconnect the ground wires to the panel mounting
rails.
The internal power cables are to be reinstalled during
step 4.8.
4.3 INSTALLATION OF EXTERNAL POWER CABLES AND MOUNTING
OF C̲O̲N̲D̲U̲I̲T̲S̲.̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲
C̲A̲U̲T̲I̲O̲N̲
BEFORE TERMINATING THE EXTERNAL POWER CABLES, ENSURE
THAT THE MAIN CIRCUIT BREAKER IN THE CAMPS PDB IS DISCONNECTED.
4.3.1 F̲r̲e̲q̲u̲e̲n̲c̲y̲ ̲S̲t̲a̲b̲i̲l̲i̲z̲e̲r̲
a) Mount the 3 frequency stabilizers from the front
of the rack. The frequency stabilizers are tightened
each by the 8 6mm front screws.
b) Connect the groundwire between the panel mounting
rail and the tagblock TB2 (chassis GND) on the
rear of the frequency stab. (See CAMPS H/W breakdown
page 344).
c) Connect the internal power cables W 501-506 according
to the CAMPS H/W breakdown page 349.
d) Mount the 1 1/2" steel tube and the outer nut from
the top/outside of the rack (see AB drawing 122).
Tighten the steel tube by the inner nut.
Mount the 48mm PVC flexible conduit over the 1
1/2" steel tube and tighten it by the clamp.
e) The other end of the conduit is inserted in the
cable tray above the rack.
f) Power cables Nos. 0, 2, 4, 00, 22 and 44 are pulled
through the conduit into the stabilizer.
g) The cables are dismantled and mounted with cable
shoes.
h) Terminate the cables to the tagblocks of the By-pass
switch panel according to AB drawing no. 122.
For better access to the rear side of the by-pass switch
panel, remove the side panels of the rack.
4.3.2 P̲o̲w̲e̲r̲ ̲C̲a̲b̲l̲e̲s̲ ̲R̲a̲c̲k̲ ̲A̲
a) Mount the 1 1/2" steel tube through the outer nut
and washer into the metallic cable duct above rack
A. Fasten the steel tube by the inner nut from
inside the cable duct (see AB drawing no. 121,
appendix A).
b) The 48 mm metallic conduit is mounted on the fittings
of the J-box (metallic cable duct) and the power
line filter and tightened by the 4 clamps.
c) Power cables Nos. 00, 22 and 44 together with the
insolated ground wire are pulled through the cable
inlet into the power line filter (see AB drawing
121, appendix A).
d) For access to the PLF, remove the metallic cover
fastened by 4 screws during transportation. Remaining
26 screws are shipped attached to the inside wall
of PLF. The cables and the ground wire are dismantled
and terminated with cable shoes. For details of
the connection to the terminal board ref. AB drawing
121, appendix A).
4.3.3 P̲o̲w̲e̲r̲ ̲C̲a̲b̲l̲e̲s̲ ̲R̲a̲c̲k̲ ̲B̲
Repeat step 4.3.2 for power cables No. 6, 7, 8 and
the insolated ground wire in rack B, Power Line Filter.
4.3.4 P̲o̲w̲e̲r̲ ̲C̲a̲b̲l̲e̲s̲ ̲R̲a̲c̲k̲ ̲E̲
Repeat step 4.3.2 for power cables no. 66, 77, 88 and
the insolated ground wire in rack E, Power Line Filter.
4.4 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲E̲X̲T̲E̲R̲N̲A̲L̲ ̲S̲I̲G̲N̲A̲L̲ ̲C̲A̲B̲L̲E̲S̲ ̲A̲N̲D̲ ̲M̲O̲U̲N̲T̲I̲N̲G̲
̲O̲F̲ ̲C̲O̲N̲D̲U̲I̲T̲S̲ ̲A̲T̲ ̲R̲A̲C̲K̲ ̲C̲,̲ ̲D̲,̲ ̲F̲,̲ ̲a̲n̲d̲ ̲G̲.̲
4.4.1 R̲a̲c̲k̲ ̲D̲,̲ ̲S̲u̲p̲.̲/̲M̲a̲i̲n̲t̲.̲/̲U̲s̲e̲r̲ ̲a̲n̲d̲ ̲C̲S̲S̲I̲ ̲P̲o̲s̲.̲ ̲C̲a̲b̲l̲e̲s̲
C̲A̲U̲T̲I̲O̲N̲
Be specially careful when installing the opto fibre
cables. Min. bending radius is 13 mm.
a) Opto cables W811-812/W815-818/W847-850 are installed
in the PVC duct between rack D and the maint./sup.
positions in the CAMPS area. See AB dwg. 110.
b) Mount the fittings for the PVC conduit to the cable
duct above rack D (see AB drawing 116).
c) Mount the fittings for the other end of the PVC
conduit in the left hand knockout of rack D.
d) Mount the 75 mm PVC conduit between the cable duct
and the waveguide.
e) Opto cables W811-812/W815-818/W847-850 are pulled
through the left hand penetration of rack D into
the internal PVC cable duct.
f) Opto cables W811-812 are run through the internal
cable duct and out through the right hand penetration
of rack D.
The opto cables enter rack C together with the
interrack cables and are terminated on the front
side of the adapter crate through the cable channel
assembly. See AB dwg. 117.
g) Opto cables W815-818/W847-850 are run through the
internal cable ducts of the line termination racks
and terminated on the front side of the TDX-crates
according to AB dwg. 125.
h) Opto cables W819-838/W851-854 coming from the user
terminals are pulled through the left hand bottom
penetration and into rack D. The opto cables are
run through the internal cable ducts of the line
termination racks and terminated on the front of
the TDX-crates according to AB dwg. 125.
i) OPTO cables W843 and W859 coming from the CSSI
terminals are pulled through the center penetration
and into rack D.
The cables leave rack D through the right hand
penetration, are run through the internal cable
trays of rack C-B-A and terminated on the front
side of the CSSI Adapter crate in rack A.
j) Repeat step b) through d) for the center knock
out of rack D.
k) Extension opto cables, all marked with room numbers,
are pulled through the center penetration of rack
D. All extension opto cables are left in the bottom
of rack D.
4.4.2 R̲a̲c̲k̲ ̲G̲ ̲N̲A̲E̲W̲ ̲C̲a̲b̲l̲e̲s̲
a) Mount the fittings for the PVC conduit in the cable
tray above rack G.
b) Mount the fittings for the other end of the conduit
in the upper right hand penetration of rack G.
c) Mount the PVC conduit between the cable duct and
the vaweguide.
d) The OPTO cables W839 - 42/W855-58 are pulled through
the right hand penetration of rack G and into the
internal PVC duct.
e) The OPTO cables are run through the internal PVC
duct and terminated on the front side of the adapter
crate in rack G.
4.4.3 C̲a̲b̲l̲e̲ ̲B̲u̲n̲c̲h̲ ̲R̲a̲c̲k̲ ̲C̲ ̲t̲o̲ ̲R̲a̲c̲k̲ ̲D̲
a) Mount the male adapter between the two 90…0e…o…0f… fittings.
Adjust for correct distance between knockouts in
rack C and D (see AB drawing 115/116). Mount the
30 mm male adapter through the knockout into the
90…0e…o…0f… fitting. Tighten fittings by the inner nut.
b) Cables 905-908, The TDX-Bus, are mounted in metallic
zipper-tubing. The zipper-tubing is pulled through
the metallic conduit into Rack C. The Metallic
Part of the zipper-tubing is connected to the panel
mounting rail in rack C.
c) Cables W904 and W909 - 914, stored in rack D during
transportation, are pulled through the metallic
conduit into rack C and distributed according to
AB dwg. 117.
d) Yellow label on cables means pin 1 (ground) connected.
This end must be connected in rack C.
4.4.4 R̲a̲c̲k̲ ̲F̲ ̲(̲L̲S̲M̲/̲O̲t̲h̲e̲r̲ ̲C̲a̲b̲l̲e̲s̲)̲
a) Mount the 2 1/2" steel tube through the outer nut
into the right hand penetration of rack F and the
filter box. Tighten the fitting from inside the
filterbox by the inner nut (see AB drawing 116).
b) Repeat step a) for the left hand penetration of
rack F.
c) Repeat step a) for the other end of the conduit
to be mounted in the ferrous duct above rack F
(see AB drawing 110/116).
d) Mount the 75 mm metallic conduit on the outside
of the steel tubes and tighten it by the clamps.
e) The low speed medium (LSM) cables W855-879 and
W814 for the PTP/PTR are pulled through the waveguide
of the metallic duct, through the left hand pene-
tration of rack F and into the filter box.
f) Other cables: W731 CCIS
W741-744 Colocated TARE
W813+W890 OCR
are pulled through the waveguide of the metallic
duct, through the right hand penetration of rack
F and into the filter box.
g) The metallic cables are now ready for termination.
h) When the metallic cables have been connected by
H/N, see AB drawing 125, the cables will be finally
marked with cable no. Markers.
i) For pin assignment ref. Table 1-2 in Appendix A.
4.5 R̲E̲M̲O̲U̲N̲T̲I̲N̲G̲ ̲O̲F̲ ̲R̲A̲C̲K̲S̲
4.5.1 M̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲D̲i̲s̲k̲ ̲D̲r̲i̲v̲e̲s̲
The 3 separately packed disk drives, 1 MMD for rack
A, 1 SMD for rack B, and 1 MMD for rack C are unpacked
and installed according to the instructions in the
CAMPS Site Level Maintenance Manual.
Ref. doc. CPS/TCM/005.
4.5.2 M̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲F̲l̲o̲p̲p̲y̲ ̲D̲i̲s̲k̲ ̲S̲t̲a̲t̲i̲o̲n̲
a) Remove the front panel located below the watchdog
crate. (Pos. 1A2A6).
b) The floppy disk cabinet containing the two floppy
disk drives is installed on the two slides.
c) The cabinet is locked by mounting and tightening
the front panel by the 6 6mm screws.
4.5.3 M̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲M̲o̲d̲u̲l̲e̲s̲
a) For correct physical positioning of the separately
packed modules, refer to the inventory list. The
inventory list states the serial No. of the unit,
the crate assy No., the slot No. in the crate and
the address of the physical position in the system.
b) The modules are slid into the print guide and when
the edge connector of the print has entered the
connector of the motherboard, the modules are fastened
by the two fixing screws on the front of the modules.
4.6 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲A̲N̲D̲ ̲T̲E̲R̲M̲I̲N̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲I̲N̲T̲E̲R̲N̲A̲L̲ ̲S̲I̲G̲N̲A̲L̲ ̲C̲A̲B̲L̲E̲S̲
4.6.1 I̲n̲t̲e̲r̲n̲a̲l̲ ̲S̲i̲g̲n̲a̲l̲ ̲C̲a̲b̲l̲e̲s̲
a) Tables 4.6.2 through 4.6.19 list all internal signal
cables in the 3-bay processor rack assembly, and
the 4-bay line termination rack assembly, e.g.
also cables not disconnected during transportation.
b) The philosophy is to install/terminate or check
all cables within one crate at a time, starting
with processor crate assy No. 1.
c) The left-hand side of each table states the exact
location of a specific cable to be connected or
checked.
d) The right-hand side "going to/coming from" indicates
the termination point for the other end of the
cable.
e) It is recommended, after having connected one cable
according to the left-hand side of the table, that
the cable is laid down in the cable trays in the
direction of the termination point for the other
end (ref. the right-hand side of the table).
f) The termination at the other end of the cable is
performed when this step in the step-by-step procedure
is reached.
g) The column ILLUS "Cable Illustrations" refers to
the page No. in the CAMPS HARDWARE BREAKDOWN (CPS/SDS/017)
showing the physical cables with types of connectors.
h) The column DIAG "Cable Diagram" refers to the page
No. in the CAMPS HARDWARE BREAKDOWN (CPS/SDS/017)
showing the position of the actual cable in the
system.
i) For details of the interrack cabling see AB drawings
117 and 118.
W̲A̲R̲N̲I̲N̲G̲ :
D̲i̲s̲c̲o̲n̲ Cable has been disconnected.
The cable is not removed
from the rack cable tray
and the connector is to be
found near by the termination
point.
C̲o̲n̲ Cable has not been disconnected.
Check for correct W-number
at b̲o̲t̲h̲ ̲e̲n̲d̲s̲.
I̲ Internal Cable inside the
same rack. Cable must be
connected/checked at b̲o̲t̲h̲
̲e̲n̲d̲s̲ according to the right-
and left-hand part of the
table.
R̲a̲c̲k̲ ̲(̲A̲,̲ ̲B̲,̲ ̲C̲,̲ ̲e̲t̲c̲) Cable has been withdrawn
during transportation and
is now found in e.g. rack
A.
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲2̲
P̲R̲O̲C̲E̲S̲S̲O̲R̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲#̲ ̲1̲ ̲R̲A̲C̲K̲ ̲A̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲
I̲l̲l̲u̲s̲ D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲ ̲ ̲
W 1 MIA A1A1A27 J2 CIA-A B A2A1A32 J1
58
63 CON
W 3 CCA A1A1A23 J1 CCA B A2A1A25 J1
58
63 RACK
C
CCBA B A2A4A10 J1
58
63 RACK
C
W 4 TIA A1A1A25 J1 X-NET A A1A1A8 J1
58
63 I
W 5 TIA A1A1A26 J1 X-NET A A1A1A9 J1
58
63 I
W13 MIA A1A1A27 J1 WCA B A2A4A11 J1
60
63 CON
W95 TSP A1A1A24 J1 THERMO A A1A1A10 *
62
68 DISCON
W96 TSP A1A1A24 J2 THERMO A A1A1A9 *
62
68 DISCON
*Part of Unit
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲3̲
A̲D̲A̲P̲T̲E̲R̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲Y̲ ̲R̲A̲C̲K̲ ̲A̲
W29 BP A1A14A25 J1 LIA-N B A2A1A33 J1 60 63 CON
W30 BP A1A14A25 J2 LIA-N B A2A1A33 J3 60 63 CON
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲4
X̲-̲N̲E̲T̲ ̲O̲U̲T̲L̲E̲T̲S̲ ̲R̲A̲C̲K̲ ̲A̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W17 X-NET A1A1A8 1-2 X-NET C A3A3A11 1-2 60 34/63 CON
W18 X-NET A1A1A8 4-5 X-NET C A3A3A11 4-5 60 34/63 CON
W19 X-NET A1A1A9 1-2 X-NET C A3A3A12 1-2 60 34/63 CON
W20 X-NET A1A1A9 4-5 X-NET C A3A3A12 4-5 60 34/63 CON
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲5̲
D̲I̲S̲K̲ ̲D̲R̲I̲V̲E̲ ̲R̲A̲C̲K̲ ̲A̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W 9 DISK 1A1A5 J3 DCA B A2A1A30 J1 59 63 RACK
B
W12 DISK 1A1A5 J2 DCA B A2A1A30 J2 59 63 RACK
B
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲6̲
C̲H̲A̲N̲N̲E̲L̲ ̲U̲N̲I̲T̲ ̲R̲A̲C̲K̲ ̲B̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W 1 CIA-A A2A1A32 J1 MIA A A1A1A27 J2 58 63 RACK
A
W 2 CIA-B A2A1A31 J1 MIA C A3A1A27 J2 58 63 RACK
C
W 3 CCA A2A1A25 J1 CCBA B A2A4A10 J1 58 63 RACK
C
W 3 CCA C A3A1A23 J1 58 63 RACK
C
W 6 SFA A2A1A27 J1 FD B A2A2A5 J2 59 63 I
W 7 DCA A2A1A28 J1 DISK C A3A8 J3 59 63 DISCON
W 8 DCA A2A1A29 J1 DISK B A2A7 IJ3 59 63 I
W 9 DCA A2A1A30 J1 DISK A A1A5 J3 59 63 DISCON
W10 DCA A2A1A28 J2 DISK C A3A8 J2 59 63 DISCON
W11 DCA A2A1A29 J2 DISK B A2A7 IJ2 59 63 I
W12 DCA A2A1A30 J2 DISK A A1A5 J2 59 63 DISCON
W21 LIA A2A1A24 J3 BP8 C A3A5A24 J4 60 63 DISCON
W22 LIA A2A1A24 J1 BP8 C A3A5A24 J3 60 63 DISCON
W23 LIA A2A1A23 J3 BP8 C A3A5A24 J2 60 63 DISCON
W24 LIA A2A1A23 J1 BP8 C A3A5A24 J1 60 63 DISCON
W25 LIA A2A1A22 J1 BP8 C A3A5A25 J2 60 63 DISCON
W26 LIA A2A1A21 J1 BP8 C A3A5A25 J1 60 63 DISCON
W29 LIA A2A1A33 J1 BP A A1A14A25 J1 60 63 DISCON
W30 LIA A2A1A33 J3 BP A A1A14A25 J2 60 63 DISCON
W97 TSP A2A1A26 J1 THERM B A2A11 * 62 68 DISCON
W98 TSP A2A1A26 J2 THERM B A2A10 * 62 68 DISCON
*Part of Unit…86…1 …02… …02… …02… …02… …02… …02…
…02… …02… …02… …02…
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲7̲
W̲A̲T̲C̲H̲D̲O̲G̲ ̲C̲R̲A̲T̲E̲ ̲R̲A̲C̲K̲ ̲B̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W 3 CCBA A2A4A10 J1 CCA B A2A1A25 J1 58 63 RACK
C.
W13 WCA A2A4A11 J1 MIA A A1A1A27 J1 60 63 RACK
A.
W14 WCA A2A4A11 J2 MIA C A3A1A27 J1 60 63 RACK
C.
W27 WCA A2A4A11 J4 BP8 C A3A5A25 J3 60 63 DISCON
W28 WCA A2A4A11 J3 BP8 C A3A5A25 J4 60 63 DISCON
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲8̲
P̲R̲O̲C̲E̲S̲S̲O̲R̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲#̲ ̲2̲ ̲R̲A̲C̲K̲ ̲C̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W 2 MIA A3A1A27 J2 CIA-B B A2A1A31 J1 58 63 DISCON
W 3 CCA A3A1A23 J1 CCB C A3A16 J1 58 63 DISCON
W 3 J1 CCA C A3A1A23 J1 58 63 CON
W14 MIA A3A1A27 J1 WCA B A2A4A11 J2 60 63 DISCON
W15 TIA A3A1A25 J1 X-NET C A3A11 J1 60 63 I
W16 TIA A3A1A26 J1 X-NET C A3A12 J1 60 63 I
W99 TSP A3A1A24 J1 THERM C A3A14 * 62 68 DISCON
W100 TSP A3A1A24 J2 THERM C A3A13 * 62 68 DISCON
*Part of Unit…86…1 …02… …02… …02… …02… …02… …02…
…02… …02… …02… …02…
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲9̲
X̲-̲N̲E̲T̲ ̲O̲U̲T̲L̲E̲T̲S̲ ̲ ̲R̲A̲C̲K̲ ̲C̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W17 X-NET 1A3A11 1-2 X-NET A 1A1A8 1-2 60 34/63 RACK
A
W18 X-NET 1A3A11 4-5 X-NET A 1A1A8 4-5 60 34/63 RACK
A
W19 X-NET 1A3A12 1-2 X-NET A 1A1A9 1-2 60 34/63 RACK
A
W20 X-NET 1A3A12 4-5 X-NET A 1A1A9 4-5 60 34/63 RACK
A
W905 X-NET 1A3A11 1-2 X-NET D 2A1A13 1-2 375 34/63 RACK
D
W906 X-NET 1A3A11 4-5 X-NET D 2A1A13 4-5 375 34/63 RACK
D
W907 X-NET 1A3A12 1-2 X-NET D 2A1A14 1-2 375 34/63 RACK
D
W908 X-NET 1A3A12 4-5 X-NET D 2A1A14 4-5 375 34/63 RACK
D
W904 CCB 1A3A16 J1 CCB D 2A1A19 J1 375
RACK
D
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲1̲0̲
A̲D̲A̲P̲T̲E̲R̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲R̲A̲C̲K̲ ̲C̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W21 BP8 A3A5A24 J4 LIA B A2A1A24 J3 60 63 RACK
B
W22 BP8 A3A5A24 J3 LIA B A2A1A24 J1 60 63 RACK
B
W23 BP8 A3A5A24 J2 LIA B A2A1A23 J3 60 63 RACK
B
W24 BP8 A3A5A24 J1 LIA B A2A1A23 J1 60 63 RACK
B
W26 BP8 A3A5A25 J1 LIA B A2A1A22 J1 60 63 RACK
B
W25 BP8 A3A5A25 J2 LIA B A2A1A21 J1 60 63 RACK
B
W27 BP8 A3A5A25 J3 WCA B A2A4A11 J4 60 63 RACK
B
W28 BP8 A3A5A25 J4 WCA B A2A4A11 J3 60 63 RACK
B
W909 L/L-AD A3A5A9 J1 FILTER F A3A17 J31 375 370 RACK
F
W910 L/L-AD A3A5A10 J1 FILTER F A3A17 J30 375 370 RACK
F
W911 L/L-AD A3A5A14 J1 FILTER F A3A17 J29 375 370 RACK
F
W912 L/L-AD A3A5A15 J1 FILTER F A3A17 J28 375 370 RACK
F
W913 L/L-AD A3A5A16 J1 FILTER F A3A17 J27 375 370 RACK
F
W914 L/L-AD A3A5A17 J1 FILTER F A3A17 J26 375 370 RACK
F
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲1̲1̲
D̲I̲S̲K̲ ̲D̲R̲I̲V̲E̲ ̲R̲A̲C̲K̲ ̲C̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W 7 DISK A3A8 J3 DCA B A2A1A28 J1 59 63 RACK
B
W10 DISK A3A8 J2 DCA B A2A1A28 J2 59 63 RACK
B
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲1̲2̲
R̲A̲C̲K̲ ̲D̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W101 BSM-P A1A1A25 J2 BSM-X E A2A9A25 J2 170 175 RACK
F
W101 BSM-P A1A7A25 J2 BSM-X D A1A9A25 J2 170 175 RACK
F
W101 BSM-P A1A3A25 J2 BSM-X D A1A7A25 J2 170 175 RACK
F
W101 BSM-P A1A9A25 J2 CCB D A1A20 J1 170 175 RACK
F
W104 BSM-X A1A1A3 J1 TDX CNT D A1A1A2 J1 170 175 I
W105 BSM-X A1A9A3 J1 TDX CNT D A1A9A2 J1 170 175 I
W106 TDX CNT A1A1A2 J2 X-NET D A1A15 J1 171 175 I
W107 TDX CNT A1A9A2 J2 X-NET D A1A25 J1 171 175 I
W108 BSM-P A1A1A25 J3 X-NET D A1A13 J1 171 175 CON
W109 BSM-P A1A1A25 J1 X-NET D A1A14 J1 171 175 CON
W110 BSM-P A1A3A25 J3 X-NET D A1A16 J1 171 175 CON
W111 BSM-P A1A3A25 J1 X-NET D A1A17 J1 171 175 CON
W112 BSM-P A1A7A25 J3 X-NET D A1A21 J1 171 175 CON
W113 BSM-P A1A7A25 J1 X-NET D A1A22 J1 171 175 CON
W114 BSM-P A1A9A25 J3 X-NET D A1A23 J1 171 175 CON
W115 BSM-P A1A9A25 J1 X-NET D A1A24 J1 171 175 CON
W141 X-NET A1A14 1-2 X-NET D A1A17 1-2 171 175 CON
W142 X-NET A1A14 4-5 X-NET D A1A17 4-5 171 175 CON
W143 X-NET A1A13 1-2 X-NET D A1A15 1-2 171 175 CON
W144 X-NET A1A13 4-5 X-NET D A1A15 4-5 171 175 CON
W145 X-NET A1A17 1-2 X-NET D A1A22 1-2 171 175 CON
W146 X-NET A1A17 4-5 X-NET D A1A22 4-5 171 175 CON
W148 X-NET A1A15 1-2 X-NET D A1A16 1-2 171 175 CON
W147 X-NET A1A15 4-5 X-NET D A1A16 4-5 171 175 CON
W149 X-NET A1A22 1-2 X-NET D A1A24 1-2 171 175 CON
W150 X-NET A1A22 4-5 X-NET D A1A24 4-5 171 175 CON
W151 X-NET A1A16 1-2 X-NET D A1A21 1-2 171 175 CON
W152 X-NET A1A16 4-5 X-NET D A1A21 4-5 171 175 CON
W153 X-NET A1A24 1-2 X-NET D A1A25 1-2 171 175 CON
W154 X-NET A1A24 4-5 X-NET D A1A25 4-5 171 175 CON
W155 X-NET A1A21 1-2 X-NET D A1A23 1-2 171 175 CON
W156 X-NET A1A21 4-5 X-NET D A1A23 4-5 171 175 CON
W157 X-NET A1A25 4-5 X-NET E A2A14 1-2 171 144/175
RACK
E
W158 X-NET A1A24 1-2 X-NET E A2A14 4-5 171 144/175
RACK
E
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲1̲2
R̲A̲C̲K̲ ̲D̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W159 X-NET A1A23 1-2 X-NET E 2A2A13 1-2 171 144/175
RACK
E
W160 X-NET A1A23 4-5 X-NET E 2A2A13 4-5 171 144/175
RACK
E
W904 CCB A1A20 J1 CCB C 1A3A16 J1 375 175
CON
W905 X-NET A1A13 1-2 X-NET C 1A3A11 1-2 375 143/175
CON
W906 X-NET A1A13 4-5 X-NET C 1A3A11 4-5 375 143/175
CON
W907 X-NET A1A14 1-2 X-NET C 1A3A12 1-2 375 143/175
CON
W908 X-NET A1A14 4-5 X-NET C 1A3A12 4-5 375 143/175
CON
W293 TSP A1A3A22 J1 THERMO D A1A18 * 172 225 I
W294 TSP A1A9A22 J1 THERMO D A1A26 * 172 225 I
* Part of Unit…86…1 …02… …02… …02… …02… …02… …02…
…02… …02… …02… …02……02…
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲1̲3̲
R̲A̲C̲K̲ ̲E̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W101 BSM-P A2A7A25 J2 BSM-P E A2A3A25 J2 170 175 DISCON
W101 BSM-P A2A9A25 J2 BSM-P D A1A1A25 J2 170 175 DISCON
W101 BSM-P A2A1A25 J2 BSM-P F A3A3A25 J2 170 175 DISCON
W101 BSM-P A2A3A25 J2 BSM-P E A2A7A25 J2 170 175 DISCON
W116 BSM-P A2A1A25 J3 X-NET E A2A13 J1 171 175 DISCON
W117 BSM-P A2A1A25 J1 X-NET E A2A14 J1 171 175 DISCON
W118 BSM-P A2A3A25 J3 X-NET E A2A15 J1 171 175 CON
W119 BSM-P A2A3A25 J1 X-NET E A2A16 J1 171 175 CON
W120 BSM-P A2A7A25 J3 X-NET E A2A19 J1 171 175 CON
W121 BSM-P A2A7A25 J1 x-NET E A2A20 J1 171 175 CON
W122 BSM-P A2A9A25 J3 X-NET E A2A21 J1 171 175 CON
W123 BSM-P A2A9A25 J1 X-NET E A2A22 J1 171 175 CON
W161 X-NET A2A14 1-2 X-NET E A2A16 1-2 171 175 CON
W162 X-NET A2A14 4-5 X-NET E A2A16 4-5 171 175 CON
W163 X-NET A2A13 1-2 X-NET E A2A15 1-2 171 175 CON
W164 X-NET A2A13 4-5 X-NET E A2A15 4-5 171 175 CON
W165 X-NET A2A16 1-2 X-NET E A2A20 1-2 171 175 CON
W166 X-NET A2A16 4-5 X-NET E A2A20 4-5 171 175 CON
W167 X-NET A2A15 1-2 X-NET E A2A19 1-2 171 175 CON
W168 X-NET A2A15 4-5 X-NET E A2A19 4-5 171 175 CON
W169 X-NET A2A20 1-2 X-NET E A2A22 1-2 171 175 CON
W170 X-NET A2A20 4-5 X-NET E A2A22 4-5 171 175 CON
W171 X-NET A2A19 1-2 X-NET E A2A21 1-2 171 175 CON
W172 X-NET A2A19 4-5 X-NET E A2A21 4-5 171 175 CON
W173 X-NET A2A22 1-2 X-NET F A3A11 1-2 171 175 RACK
F
W174 X-NET A2A22 4-5 X-NET F A3A11 4-5 171 175 RACK
F
W175 X-NET A2A21 1-2 X-NET F A3A10 1-2 171 175 RACK
F
W176 X-NET A2A21 4-5 X-NET F A3A10 4-5 171 175 RACK
F
W295 TSP A2A3A22 J1 THERMO F A3A17 *
172 225 I
W296 TSP A2A9A22 J1 THERMO F A3A23 *
172 225
I
* Part of Unit
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲1̲4
T̲D̲X̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲6̲ ̲R̲A̲C̲K̲ ̲E̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W279 L/L ADAP A2A7A17 J1 IDF F A3A17
J33 172 191 RACK
F
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲1̲5̲
T̲D̲X̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲7̲ ̲R̲A̲C̲K̲ ̲E̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W201 L/L AD A2A3A7 J1 IDF F A3A17 J1 172 191 RACK
F
W202 L/L AD A2A3A7 J2 IDF F A3A17 J2 172 191 RACK
F
W203 L/L AD A2A3A7 J3 IDF F A3A17 J3 172 191 RACK
F
W204 L/L AD A2A3A7 J4 IDF F A3A17 J4 172 191 RACK
F
W205 L/L AD A2A3A14 J1 IDF F A3A17 J5 172 191 RACK
F
W206 L/L AD A2A3A14 J2 IDF F A3A17 J6 172 191 RACK
F
W207 L/L AD A2A3A14 J3 IDF F A3A17 J7 172 191 RACK
F
W208 L/L AD A2A3A14 J4 IDF F A3A17 J8 172 191 RACK
F
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲1̲6̲
T̲D̲X̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲8̲ ̲R̲A̲C̲K̲ ̲E̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W209 L/L AD A2A1A7 J1 IDF F A3A17 J
9 172 191 RACK
F
W210 L/L AD A2A1A7 J2 IDF F A3A17 J10 172 191 RACK
F
W211 L/L AD A2A1A7 J3 IDF F A3A17 J11 172 191 RACK
F
W212 L/L AD A2A1A7 J4 IDF F A3A17 J12 172 191 RACK
F
W213 L/L AD A2A1A14 J1 IDF F A3A17 J13 172 191 RACK
F
W214 L/L AD A2A1A14 J2 IDF F A3A17 J14 172 191 RACK
F
W215 L/L AD A2A1A14 J3 IDF F A3A17 J15 172 191 RACK
F
W216 L/L AD A2A1A14 J4 IDF F A3A17 J16 172 191 RACK
F
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲1̲7̲
R̲A̲C̲K̲ ̲F̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W101 BSM-P A3A1A25 J2 CCB F A3A16 J1 170 175 CON
W101 BSM-P A3A3A25 J2 BSM-P E A2A1A25 J2 170 175 CON
W102 CCB A3A16 J1 BSM-P G A4A7A25 J1 170 175 RACK
G
W124 BSM-P A3A1A25 J3 X-NET F A3A10 J1 171 175 CON
W125 BSM-P A3A1A25 J1 X-NET F A3A11 J1 171 175 CON
W126 BSM-P A3A3A25 J3 X-NET F A3A12 J1 171 175 CON
W127 BSM-P A3A3A25 J1 X-NET F A3A13 J1 171 175 CON
W173 X-NET A3A11 1-2 X-NET E A2A22 1-2 171 175 RACK
E
W174 X-NET A3A11 4-5 X-NET E A2A22 4-5 171 175 RACK
E
W175 X-NET A3A10 1-2 X-NET E A2A21 1-2 171 175 RACK
E
W176 X-NET A3A10 4-5 X-NET E A2A21 4-5 171 175 RACK
E
W177 X-NET A3A11 1-2 X-NET F A3A13 1-2 171 175 CON
W178 X-NET A3A11 4-5 X-NET F A3A13 4-5 171 175 CON
W179 X-NET A3A10 1-2 X-NET F A3A12 1-2 171 175 CON
W180 X-NET A3A10 4-5 X-NET F A3A12 4-5 171 175 CON
W181 X-NET A3A13 1-2 X-NET G A4A14 1-2 171 175 RACK
G
W182 X-NET A3A13 4-5 X-NET G A4A14 4-5 171 175 RACK
G
W183 X-NET A3A12 1-2 X-NET G A4A13 1-2 171 175 RACK
G
W184 X-NET A3A12 4-5 X-NET G A4A13 4-5 171 175 RACK
G
W297 TSP A3A3A22 J1 THERMO F A3A14 *
172 225 I
* Part of Unit
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲1̲8̲
F̲I̲L̲T̲E̲R̲ ̲B̲O̲X̲ ̲ ̲R̲A̲C̲K̲ ̲F̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W201 IDF 2A3A17 J1 L/L AD E A2A3A7 J1 172 191 CON
W202 IDF 2A3A17 J2 L/L AD E A2A3A7 J2 172 191 CON
W203 IDF 2A3A17 J3 L/L AD E A2A3A7 J3 172 191 CON
W204 IDF 2A3A17 J4 L/L AD E A2A3A7 J4 172 191 CON
W205 IDF 2A3A17 J5 L/L AD E A2A3A14 J1 172 191 CON
W206 IDF 2A3A17 J6 L/L AD E A2A3A14 J2 172 191 CON
W207 IDF 2A3A17 J7 L/L AD E A2A3A14 J3 172 191 CON
W208 IDF 2A3A17 J8 L/L AD E A2A3A14 J4 172 191 CON
W209 IDF 2A3A17 J9 L/L AD E A2A1A7 J1 172 191 CON
W210 IDF 2A3A17 J10 L/L AD E A2A1A7 J2 172 191 CON
W211 IDF 2A3A17 J11 L/L AD E A2A1A7 J3 172 191 CON
W212 IDF 2A3A17 J12 L/L AD E A2A1A7 J4 172 191 CON
W213 IDF 2A3A17 J13 L/L AD E A2A1A14 J1 172 191 CON
W214 IDF 2A3A17 J14 L/L AD E A2A1A14 J2 172 191 CON
W215 IDF 2A3A17 J15 L/L AD E A2A1A14 J3 172 191 CON
W216 IDF 2A3A17 J16 L/L AD E A2A1A14 J4 172 191 CON
W217 IDF 2A3A17 J17 L/L AD F A3A3A7 J1 172 191 CON
W218 IDF 2A3A17 J18 L/L AD F A3A3A7 J2 172 191 CON
W219 IDF 2A3A17 J19 L/L AD F A3A3A7 J3 172 191 CON
W220 IDF 2A3A17 J20 L/L AD F A3A3A7 J4 172 191 CON
W221 IDF 2A3A17 J21 L/L AD F A3A3A14 J1 172 191 CON
W222 IDF 2A3A17 J22 L/L AD F A3A3A14 J2 172 191 CON
W223 IDF 2A3A17 J23 L/L AD F A3A3A14 J3 172 191 CON
W224 IDF 2A3A17 J24 L/L AD F A3A3A14 J4 172 191 CON
W225 IDF 2A3A17 J25 L/L AD F A3A1A14 J1 172 191 CON
W232 IDF 2A3A17 J32 L/L AD F A3A1A10 J1 172 191 CON
W909 IDF 2A3A17 J31 L/L AD C A3A5A9 J1 375 191 CON
W910 IDF 2A3A17 J30 L/L AD C A3A5A10 J1 375 191 CON
W279 IDF 2A3A17 J33 L/L AD E A2A7A17 J1 172 191 CON
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲1̲8̲
F̲I̲L̲T̲E̲R̲ ̲B̲O̲X̲ ̲ ̲R̲A̲C̲K̲ ̲F̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W911 IDF 2A3A17 J29 L/L AD C A3A5A14 J1 375 191 CON
W912 IDF 2A3A17 J28 L/L AD C A3A5A15 J1 375 191 CON
W913 IDF 2A3A17 J27 L/L AD C A3A5A16 J1 375 191 CON
W914 IDF 2A3A17 J26 L/L AD C A3A5A17 J1 375 191 CON
OBSERVE THAT THE YELLOW LABELED END OF THE
CABLES BETWEEN IDF AND THE L/L ADP. MUST BE
CONNECTED AT THE L/L ADP.
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲1̲9̲
T̲D̲X̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲9̲ ̲ ̲R̲A̲C̲K̲ ̲F̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W217 L/L AD A3A3A7 J1 IDF F A3A17 J17 172 191 RACK
F
W218 L/L AD A3A3A7 J2 IDF F A3A17 J18 172 191 RACK
F
W219 L/L AD A3A3A7 J3 IDF F A3A17 J19 172 191 RACK
F
W220 L/L AD A3A3A7 J4 IDF F A3A17 J20 172 191 RACK
F
W221 L/L AD A3A3A14 J1 IDF F A3A17 J21 172 191 RACK
F
W222 L/L AD A3A3A14 J2 IDF F A3A17 J22 172 191 RACK
F
W223 L/L AD A3A3A14 J3 IDF F A3A17 J23 172 191 RACK
F
W224 L/L AD A3A3A14 J4 IDF F A3A17 J24 172 191 RACK
F
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲2̲0̲
T̲D̲X̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲1̲0̲ ̲ ̲R̲A̲C̲K̲ ̲F̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W225 L/L AD A3A1A14 J1 IDF F A3A17 J25 172 191 RACK
F
W232 L/L AD A3A1A10 J1 IDF F A3A17 J32 172 191 RACK
F
T̲a̲b̲l̲e̲ ̲4̲.̲6̲.̲2̲1̲
R̲A̲C̲K̲ ̲G̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W102 BSM-P A4A9A25 J2 BSM-P F A3A16 J2 170 175 RACK
F
W128 BSM-P A4A9A25 J3 X-NET G A4A13 J1 171 175 CON
W129 BSM-P A4A9A25 J1 X-NET G A4A14 J1 171 175 CON
W181 X-NET A4A14 1-2 X-NET F A3A14 1-2 171 175 RACK
F
W182 X-NET A4A14 4-5 X-NET F A3A14 4-5 171 175 RACK
F
W183 X-NET A4A13 1-2 X-NET F A3A13 1-2 171 175 RACK
F
W184 X-NET A4A13 4-5 X-NET F A3A13 4-5 171 175 RACK
F
W298 TSP A4A7A22 J1 THERMO G A4A15 * 172 225 I
* Part of Unit…86…1 …02… …02… …02… …02…
4.7 T̲E̲R̲M̲I̲N̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲E̲X̲T̲E̲R̲N̲A̲L̲ ̲S̲I̲G̲N̲A̲L̲ ̲C̲A̲B̲L̲E̲S̲
a) All external opto fibre cables located on the
front of the TDX- and Adapter crates are cut,
withdrawn to the rear of the rack and terminated
with special opto connectors. For details of
opto termination procedures ref. Doc. No. 4.
b) All external metallic cables located in the
filter box (ref. 4.4) can now be terminated
and connected in the filter box by host nation
technicians.
For distribution of the metallic cables inside
the filter box see AB drawing 125.
c) When terminated, all opto fibre cables are distributed
through the internal cables channels of the
racks and out through the cable channel assy
below the TDX and adapter crates (see AB drawings
117/125)
C̲A̲U̲T̲I̲O̲N̲
Be specially careful when installing the opto
fibre cables. Min. bending radius is 13mm.
d) The opto fibre cables are connected to the opto
T/R adapters from the front of the TDX crates
according to tables 4.7.2 through 4.7.7 (ref.
AB drawing 125/102).
…86…1 …02… …02… …02… …02…
T̲a̲b̲l̲e̲ ̲4̲.̲7̲.̲1̲
A̲D̲A̲P̲T̲E̲R̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲R̲A̲C̲K̲ ̲A̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ T̲e̲r̲m̲i̲n̲a̲l̲ L̲o̲c̲a̲t̲i̲o̲n̲
N̲o̲t̲e̲s̲ ̲ ̲
W843 OPTO T/R 1A1A4A9 VDU ROOM
D-206
CSSI
W859 OPTO T/R 1A1A14A10 MSP ROOM
D-206
CSSI
T̲a̲b̲l̲e̲ ̲4̲.̲7̲.̲2̲
A̲D̲A̲P̲T̲E̲R̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲R̲A̲C̲K̲ ̲C̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ T̲e̲r̲m̲i̲n̲a̲l̲ ̲ L̲o̲c̲a̲t̲i̲o̲n̲
N̲o̲t̲e̲s̲ ̲ ̲
W811 OPTO T/R 1A3A5A7 VDU MAINT.
POS.
CAMPS
AREA
W812 OPTO T/R 1A3A5A8 MSP MAINT.
POS.
CAMPS
AREA
T̲a̲b̲l̲e̲ ̲4̲.̲7̲.̲3̲
S̲T̲X̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲#̲ ̲1̲ ̲R̲A̲C̲K̲ ̲D̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ T̲e̲r̲m̲i̲n̲a̲l̲ ̲ L̲o̲c̲a̲t̲i̲o̲n̲
N̲o̲t̲e̲s̲ ̲ ̲
W815 OPTO T/R 2A1A9A10 VDU ROOM H
-
102 SUP.
P
W819 OPTO T/R 2A1A9A9 VDU ROOM B
-
307 USER
P
W822 OPTO T/R 2A1A9A17 VDU ROOM H
-
122 USER
P
W824 OPTO T/R 2A1A9A16 VDU ROOM D
-
332 USER
P
W827 OPTO T/R 2A1A9A8 VDU ROOM D
-
124 USER
P
W830 OPTO T/R 2A1A9A15 VDU ROOM A
-
315 USER
P
W833 OPTO T/R 2A1A9A7 VDU ROOM E
-
322 USER
P
W836 OPTO T/R 2A1A9A14 VDU ROOM A
-
112 USER
P
T̲a̲b̲l̲e̲ ̲4̲.̲7̲.̲4̲
C̲T̲X̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲#̲ ̲2̲ ̲R̲A̲C̲K̲ ̲D̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ T̲e̲r̲m̲i̲n̲a̲l̲ ̲ L̲o̲c̲a̲t̲i̲o̲n̲
N̲o̲t̲e̲s̲ ̲ ̲
W816 OPTO T/R 2A1A7A10 VDU ROOM H
-
102 SUP.
P
W820 OPTO T/R 2A1A7A9 VDU ROOM G
-
231 USER
P
W823 OPTO T/R 2A1A7A17 VDU ROOM C
-
301A USER
P
W825 OPTO T/R 2A1A7A16 VDU ROOM C
-
208A USER
P
W828 OPTO T/R 2A1A7A8 VDU ROOM B
-
211A USER
P
W831 OPTO T/R 2A1A7A15 VDU ROOM H
-
219 USER
P
W834 OPTO T/R 2A1A7A7 VDU ROOM H
-
313A USER
P
W837 OPTO T/R 2A1A7A14 VDU ROOM H
-
219A USER
P
T̲a̲b̲l̲e̲ ̲4̲.̲7̲.̲5̲
C̲T̲X̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲#̲ ̲3̲ ̲R̲A̲C̲K̲ ̲D̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ T̲e̲r̲m̲i̲n̲a̲l̲ ̲ L̲o̲c̲a̲t̲i̲o̲n̲
N̲o̲t̲e̲s̲ ̲ ̲
W817 OPTO T/R 2A1A3A10 VDU ROOM H
-
102 SUP.
P
W818 OPTO T/R 2A1A3A17 VDU ROOM H
-
102 SUP.
P
W821 OPTO T/R 2A1A3A9 VDU ROOM E
-
233 USER
P
W826 OPTO T/R 2A1A3A16 VDU ROOM H
-
215A USER
P
W829 OPTO T/R 2A1A3A8 VDU ROOM A
-
309 USER
P
W832 OPTO T/R 2A1A3A15 VDU ROOM H
-
218 USER
P
W835 OPTO T/R 2A1A3A7 VDU ROOM A
-
112 USER
P
W838 OPTO T/R 2A1A3A14 VDU ROOM D
-
206 USER
P
T̲a̲b̲l̲e̲ ̲4̲.̲7̲.̲6̲
C̲T̲X̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲#̲ ̲5̲ ̲R̲A̲C̲K̲ ̲E̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ T̲e̲r̲m̲i̲n̲a̲l̲ ̲ L̲o̲c̲a̲t̲i̲o̲n̲
N̲o̲t̲e̲s̲ ̲ ̲
W847 OPTO T/R 2A2A9A10 MSP ROOM H
-
102 SUP.
P
W848 OPTO T/R 2A2A9A9 MSP ROOM H
-
102 SUP.
P
W849 OPTO T/R 2A2A9A17 MSP ROOM H
-
102 SUP.
P
W850 OPTO T/R 2A2A9A16 MSP ROOM H
-
102 SUP.
P
W851 OPTO T/R 2A2A9A8 MSP ROOM A
-
112 USER
P
W852 OPTO T/R 2A2A9A7 MSP ROOM A
-
112 USER
P
W853 OPTO T/R 2A2A9A15 MSP ROOM A
-
112 USER
P
W854 OPTO T/R 2A2A9A14 MSP ROOM A
-
112 USER
P
T̲a̲b̲l̲e̲ ̲4̲.̲7̲.̲7̲
C̲T̲X̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲#̲ ̲1̲1̲ ̲R̲A̲C̲K̲ ̲G̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ T̲e̲r̲m̲i̲n̲a̲l̲ ̲ L̲o̲c̲a̲t̲i̲o̲n̲
N̲o̲t̲e̲s̲ ̲ ̲
W839 OPTO T/R 2A4A9A10 VDU ROOM K-108 NAEW
W840 OPTO T/R 2A4A9A9 VDU ROOM K-117 NAEW
W841 OPTO T/R 2A4A9A8 VDU
W842 OPTO T/R 2A4A9A7 VDU
W855 OPTO T/R 2A4A9A17 MSP
W856 OPTO T/R 2A4A9A16 MSP ROOM K-117 NAEW
W857 OPTO T/R 2A4A9A15 MSP
W858 OPTO T/R 2A4A9A14 MSP
4.8 C̲O̲N̲N̲E̲C̲T̲I̲O̲N̲ ̲O̲F̲ ̲I̲N̲T̲E̲R̲N̲A̲L̲ ̲P̲O̲W̲E̲R̲ ̲C̲A̲B̲L̲E̲S̲
a) Tables 5.8.2 through 5.8.8 list all internal power
cables in the processor racks and the line termination
racks.
b) Use the tables as an installation step by step
procedure and as a checkout of cables already installed
(see AB drawings 117, 118, and 120).
c) All power plugs connected to fans and crates must
be secured by the connector spring mounted on the
male connector.
U̲N̲D̲E̲R̲ ̲N̲O̲T̲E̲S̲ ̲P̲L̲E̲A̲S̲E̲ ̲N̲O̲T̲E̲:̲
I̲ INTERNAL CABLE
Both ends of the cable must
be connected/checked in this
step (ref. left a̲n̲d̲ right
hand side of the table).
C̲O̲N̲ Cable has not been disconnected.
Check for correct W-number.
D̲I̲S̲C̲O̲N̲ Cable has been disconnected.
The cable is not removed from
the rack cable tray. The connector
is to be found near by the
termination point.
R̲A̲C̲K̲ ̲(̲A̲,̲ ̲B̲,̲ ̲C̲,̲ ̲E̲T̲C̲)̲ Cable has been withdrawn during
transportation and is now
found in e.g. rack A.
T̲a̲b̲l̲e̲ ̲4̲.̲8̲.̲2̲
R̲A̲C̲K̲ ̲A̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W40 PROC. A1A1 J1 PDP A A1A12 J1 61 63 CON/I
W41 PROC. A1A1 J2 PDP A A1A12 J7 61 63 CON/I
W42 M-FAN. A1A2 J1 PDP A A1A12 J2 61 63 CON/I
W43 M-FAN. A1A2 J2 PDP A A1A12 J6 61 63 CON/I
W44 PDP. A1A12 J3 CHAN B A2A1 J1 61 63 RACK
B
W47 PDP. A1A12 J4 M-FAN B A2A2 J2 61 63 RACK
B
W53 DISK. A1A5 J1 MAINS A A1A7 J3 61 63 DISCON/I
W58 PDP. A1A17 J3 ADAP-P C A3A5A23 J1 61 63 RACK
C.
W59 MAINS. A1A7 J4 PLF A A1A13 J5 61 63 CON/I
W60 PLF. A1A13 J3 MAINS B A2A9 J4 61 63 RACK
B.
W61 PLF. A1A13 J1 MAINS C A3A10 J4 61 63 RACK
C.
W62 MAINS. A1A7 J1 PLF B A2A13 J5 61 63 CON
W68 MAINS. A1A7 J2 PDP A A1A12 * 61 63 CON
W39 PDP A1A12 J5 PDP A A1A17 * 61 63 CON/I
W38 PDP A1A17 J1 S-FAN A A1A16 * 61 63 CON/I
W37 PDP A1A17 J2 ADAP-P A A1A14A22 J1 61 63 CON/I
W88 DISK A1A5 * CU B A2A1 * 62 57 DISC
* Part of Unit…86…1 …02… …02… …02… …02… …02… …02…
…02… …02… …02… …02…
T̲a̲b̲l̲e̲ ̲4̲.̲8̲.̲3̲
R̲A̲C̲K̲ ̲B̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W44 CHAN A2A1 J1 PDP A A1A12 J3 61 63 DISCON
W45 CHAN A2A1 J2 PDP C A3A15 J3 61 63 DISCON
W46 M-FAN A2A2 J1 PDP C A3A15 J4 61 63 DISCON
W47 M-FAN A2A2 J2 PDP A A1A12 J4 61 63 DISCON
W52 MAINS A2A9 J2 WD B A2A4 J1 61 63 DISCON/I
W54 DISK A2A7 J1 PDP B A2A12 J2 61 63 DISCON/I
W56 FD A2A6 J1 PDP B A2A12 J1 61 63 CON/I
W60 MAINS A2A9 J4 PLF A A1A13 J3 61 63 DISCON
W62 PLF A2A13 J5 MAINS A A1A7 J1 61 63 RACK
A.
W63 MAINS A2A9 J1 PLF B A2A13 J3 61 63 DISCON/I
W64 PLF A2A13 J1 MAINS C A3A10 J1 61 63 RACK
C.
W67 MAINS A2A9 J3 PDP B A2A12 * 61 63 DISCON
W88 CU A2A1 1) DISK A A1A5 2) 62 57 DISCON
W89 CU A2A1 1) DISK B A2A7 2) 62 57 DISCON/I
W90 CU A2A1 1) DISK C A3A8 2) 62 57 DISCON
* Part of Unit
1) DC Groundwire terminated to CU Crate right
hand rear side above CIA-A
2) DC Groundwire terminated to rear side of disks.…86…1
…02… …02… …02… …02… …02… …02… …02… …02… …02… …02…
T̲a̲b̲l̲e̲ ̲4̲.̲8̲.̲4̲
R̲A̲C̲K̲ ̲C̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W45 PDP A3A15 J3 CHAN B A2A1 J2 61 63 RACK
B
W46 PDP A3A15 J4 M-FAN B A2A2 J1 61 63 RACK
B
W48 PROC A3A1 J1 PDP C A3A15 J1 61 63 DISCON/I
W49 PROC A3A1 J2 PDP C A3A15 J7 61 63 DISCON/I
W50 M-FAN A3A2 J1 PDP C A3A15 J2 61 63 DISCON/I
W51 M-FAN A3A2 J2 PDP C A3A15 J6 61 63 DISCON/I
W55 DISK A3A8 J1 MAINS C A3A10 J3 61 63 DISCON/I
W57 ADAP-P A3A5A22 J1 PDP C A3A17 J2 61 63 I
W58 ADAP-P A3A5A23 J1 PDP A A1A17 J3 61 63 DISCON
W61 MAINS A3A10 J4 PLF A A1A13 J1 61 63 DISCON
W64 MAINS A3A10 J1 PLF B A2A13 J1 61 63 DISCON
W65 PDP A3A15 J5 PDP C A3A17 * 61 63 CON
W66 MAINS A3A10 J2 PDP C A3A15 * 61 63 DISCON
W69 PDP A3A17 J1 S-FAN C A3A7 * 61 63 CON
W90 DISK A3A8 * CU B A2A1 * 62 57 DISCON
Part ofs Unit
T̲a̲b̲l̲e̲ ̲4̲.̲8̲.̲5̲
R̲A̲C̲K̲ ̲D̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W301 ASSY 4 A1A1 J15 PDP D A1A19 J3 173 208 CON/I
W302 ADAP-P A1A1A20 J1 PDP D A1A19 J4 173 208 CON/I
W303 ASSY 3 A1A3 J15 PDP D A1A19 J1 173 208 CON/I
W304 ADAP-P A1A3A20 J1 PDP D A1A19 J2 173 208 CON/I
W305 ASSY 2 A1A7 J15 PDP D A1A27 J3 173 208 CON/I
W306 ADAP-P A1A7A20 J1 PDP D A1A27 J4 173 208 CON/I
W307 ASSY 1 A1A9 J15 PDP D A1A27 J1 173 208 CON/I
W308 ADAP-P A1A9A20 J1 PDP D A1A27 J2 173 208 CON/I
W331 MAINS A1A12 J4 PLF E A2A26 J2 173 208 CON
W332 MAINS A1A12 J1 PLF E A2A26 J4 173 208 CON
W351 PDP A1A19 J5 S-FAN D A1A5 * 173 208 CON
W352 MAINS A1A12 J2 PDP D A1A19 * 173 208 CON
W353 PDP A1A27 J5 S-FAN D A1A11 * 173 208 CON
W354 MAINS A1A12 J3 PDP D A1A27 * 173 208 CON
T̲a̲b̲l̲e̲ ̲4̲.̲8̲.̲6̲
R̲A̲C̲K̲ ̲E̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W309 ASSY 8 A2A1 J15 PDP E A2A18 J3 173 208 DISCON/I
W310 ADAP-P A2A1A20 J1 PDP E A2A18 J4 173 208 DISCON/I
W311 ASSY 7 A2A3 J15 PDP E A2A18 J1 173 208 CON/I
W312 ADAP-P A2A3A20 J1 PDP E A2A18 J2 173 208 CON/I
W313 ASSY 6 A2A7 J15 PDP E A2A24 J3 173 208 CON/I
W314 ADAP-P A2A7A20 J1 PDP E A2A24 J4 173 208 CON/I
W315 ASSY 5 A2A9 J15 PDP E A2A24 J1 173 208 CON/I
W316 ADAP-P A2A9A20 J1 PDP E A2A24 J2 173 208 CON/I
W331 PLF A2A26 J2 MAINS D A1A12 J4 173 208 RACK
D.
W332 PLF A2A26 J4 MAINS D A1A12 J1 173 208 RACK
D.
W333 MAINS A2A12 J4 PLF E A2A26 J6 173 208 DISCON/I
W334 MAINS A2A12 J1 PLF E A2A26 J1 173 208 DISCON/I
W335 PLF A2A26 J3 MAINS F A3A9 J1 173 208 RACK
F
W336 PLF A2A26 J5 MAINS G A4A12 J4 173 208 RACK
G
W355 PDP A2A18 J5 S-FAN E A2A5 * 173 208 CON
W356 MAINS A2A12 J2 PDP E A2A18 * 173 208 DISCON
W357 PDP A2A24 J5 S-FAN E A2A11 * 173 208 CON
W358 MAINS A2A12 J3 PDP E A2A24 * 173 208 DISCON
*Part of Unit…86…1 …02… …02… …02… …02… …02… …02…
…02… …02… …02… …02…
T̲a̲b̲l̲e̲ ̲4̲.̲8̲.̲7̲
R̲A̲C̲K̲ ̲F̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W317 ASSY10 A3A1 J15 PDP F A3A15 J3 173 208 CON/I
W318 ADAP-P A3A1A20 J1 PDP F A3A15 J4 173 208 CON/I
W319 ASSY 9 A3A3 J15 PDP F A3A15 J1 173 208 CON/I
W320 ADAP-P A3A3A20 J1 PDP F A3A15 J2 173 208 CON/I
W335 MAINS A3A9 J1 PLF E A2A26 J3 173 208 DISCON
W360 PDP A3A15 J5 S-FAN F A3A5 * 173 208 CON
W361 MAINS A3A9 J2 PDP F A3A15 * 173 208 DISCON
* Part of Unit…86…1 …02… …02… …02… …02… …02… …02…
…02… …02… …02… …02…
T̲a̲b̲l̲e̲ ̲4̲.̲8̲.̲8̲
R̲A̲C̲K̲ ̲G̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W321 ASSY11 A4A9 J15 PDP G A4A16 J3 173 208 CON/I
W322 ADAP-P A4A9A20 J1 PDP G A4A16 J4 173 208 CON/I
W336 MAINS A4A12 J4 PLF E A2A26 J5 173 208 DISCON
W364 PDP A4A16 J5 S-FAN G A4A11 * 173 208 CON
W365 MAINS A4A12 J3 PDP G A4A16 * 173 208 DISCON
*Part of Unit…86…1 …02… …02… …02… …02…
4.9 P̲O̲W̲E̲R̲ ̲U̲P̲ ̲A̲N̲D̲ ̲C̲H̲E̲C̲K̲ ̲O̲U̲T̲
Before powering up, verify that a̲l̲l̲ ̲s̲w̲i̲t̲c̲h̲e̲s̲ on a̲l̲l̲
e̲q̲u̲i̲p̲m̲e̲n̲t̲ are i̲n̲ ̲p̲o̲s̲i̲t̲i̲o̲n̲ ̲o̲f̲f̲ or O.
4.9.1 G̲r̲o̲u̲n̲d̲i̲n̲g̲s̲
a) Measure with an Ohm-meter that no short circuit
exists between the safety ground (cabinets)
and the lines in the power line filters.
b) Remount the lits of the power line filters
by the 30 screws.
c) Start the powering up in the below sequence,
starting at the CAMPS power distribution board
(PDB):
4.9.2 C̲A̲M̲P̲S̲ ̲P̲D̲B̲
T̲U̲R̲N̲ ̲O̲N̲: Main circuit breaker
T̲U̲R̲N̲ ̲O̲N̲: Miniature circuit breakers
C̲H̲E̲C̲K̲O̲U̲T̲: No fuses in the CAMPS PDB blown due
to short circuit in the installation.
4.9.3 F̲r̲e̲q̲u̲e̲n̲c̲y̲ ̲S̲t̲a̲b̲i̲l̲i̲z̲e̲r̲s̲ ̲a̲n̲d̲ ̲D̲i̲s̲k̲ ̲D̲r̲i̲v̲e̲s̲
To examine that the 3 disk drives are supplied from
3 separate phases via the frequency stabilizers proceed
in the below sequence:
a) F̲r̲e̲q̲u̲e̲n̲c̲y̲ ̲S̲t̲a̲b̲i̲l̲i̲z̲e̲r̲ ̲#̲1̲/̲D̲i̲s̲k̲ ̲#̲1̲ ̲(̲M̲M̲D̲)̲ ̲R̲A̲C̲K̲ ̲A̲
1) T̲U̲R̲N̲ ̲O̲N̲: Input power switch on front of
the stabilizer (A1A3)(see CAMPS
H/W Breakdown page 214).
Set the rotary switch on the by-pass
panel to position "frequency stabilizer".
2) C̲H̲E̲C̲K̲: Input power and fault lamp lit.
Wait 2-3 seconds for fault lamp
to extinguish. "Power out" lamp
lit.
3) T̲U̲R̲N̲ ̲O̲N̲: Power switch 1 (left hand) on the
front of the main switch located
in the bottom of rack A.
4) C̲H̲E̲C̲K̲: "Power on" lamp lit on main switch.
5) T̲U̲R̲N̲ ̲O̲N̲:̲ Rear power switch disk drive No.
1 located in rack A.
6) C̲H̲E̲C̲K̲: Disk running and "ready" lamp in
front of disk lit (wait for
30 sec.).
7) T̲U̲R̲N̲ OFF: Miniature circuit breaker (CAMPS
PDB) corresponding to power circuit
no. 1 for freq. stab. 1 and disk
1 (see ATBB drawing 120).
8) C̲H̲E̲C̲K̲: Disk 1 and freq. stab. 1 powered
down.
9) Leave the miniature circuit breaker in position
OFF.
b) F̲r̲e̲q̲u̲e̲n̲c̲y̲ ̲S̲t̲a̲b̲i̲l̲i̲z̲e̲r̲ ̲#̲2̲ ̲a̲n̲d̲ ̲D̲i̲s̲k̲ ̲#̲2̲ ̲(̲S̲M̲D̲)̲
Repeat step 5.9.3a-1 through a-4 for frequency
stab. #2 (A1A5) and disk drive #2 (rack B).
5) T̲U̲R̲N̲ ̲O̲N̲:̲ Rear switches "AC power" and "power
supply".
6) C̲H̲E̲C̲K̲:̲ Disk running. (No ready lamp if
no disc pack mounted).
Proceed by repeating step 4.9.3a-7 thru a-9 for
circuit no. 2.
c) F̲r̲e̲q̲u̲e̲n̲c̲y̲ ̲S̲t̲a̲b̲i̲l̲i̲z̲e̲r̲ ̲#̲3̲ ̲a̲n̲d̲ ̲D̲i̲s̲k̲ ̲#̲3̲ ̲(̲M̲M̲D̲)̲
Repeat step 5.9.3 a-1 through a-9 for frequency
stab. #3 (A1A7), circuit no. 3, and disk drive
#3 (rack C).
d) Turn on the 3 miniature circuit breakers in the
CAMPS PDB one by one.
e) Check that all frequency stabilizers and disks
are operating.
f) By-pass the freq. stab. by positioning the switches
on the by-pass switch panel in the right hand position.
C̲H̲E̲C̲K̲:̲ All disk drives running.
g) T̲U̲R̲N̲ ̲O̲F̲F̲: Miniature circuit breaker in CAMPS
PDB for circuit no. 1, 2 and 3.
4.9.4 M̲a̲i̲n̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲a̲c̲k̲ ̲A̲ ̲S̲w̲i̲t̲c̲h̲ ̲2̲ ̲C̲i̲r̲c̲u̲i̲t̲ ̲N̲o̲.̲ ̲4̲
1) T̲U̲R̲N̲ ̲O̲N̲: Power switch No. 2 (right hand) on
front of the main switch in rack A.
2) C̲H̲E̲C̲K̲: "Power on" lamps lit.
3) T̲U̲R̲N̲ ̲O̲N̲:̲ Supply A (right hand) and supply B
(left hand) on the rear of the D-fan
located in rack A (A1A2).
4) C̲H̲E̲C̲K̲:̲ Fan running/green lamp in front lit.
5) T̲U̲R̲N̲ ̲O̲N̲:̲ Power supply A (right hand) and power
supply B (left hand) on the rear of
the processor crate in rack A (A1A1).
6) C̲H̲E̲C̲K̲:̲ Green "power on" lamp above switches
lit.
7) T̲U̲R̲N̲ ̲O̲N̲:̲ Power supply A (left hand) and power
supply B (right hand) from the front
of the processor crate.
8) C̲H̲E̲C̲K̲:̲ All 5 power indicator lamps lit on
front of the power supplies.
(All 10 lamps lit when A o̲r̲ B in
poss. on).
9) T̲U̲R̲N̲ ̲O̲N̲:̲ Supply A (right hand) on the rear of
the D-fan located in rack B.
10) C̲H̲E̲C̲K̲:̲ Fan running/corresponding green lamp
in front lit.
11) T̲U̲R̲N̲ ̲O̲N̲:̲ Power supply B (left hand) on the rear
of the channel unit crate in rack B
(A2A1).
12) C̲H̲E̲C̲K̲:̲ Green "power on" lamp above switch
lit.
13) T̲U̲R̲N̲ ̲O̲N̲:̲ Power supply B (right hand) from the
front of the CU.
14) C̲H̲E̲C̲K̲:̲ All 5 power indicator lamps lit on
front of the power supply.
15) T̲U̲R̲N̲ ̲O̲N̲:̲ Power switch on adapter power supply,
right hand part on the rear of the
adapter crate in rack C (A3A5A23).
16) C̲H̲E̲C̲K̲:̲ "Power on" lamps lit on left hand section
of the adapter crate (2 L/L adapters
and 2 Opto T/R)
17) T̲U̲R̲N̲ ̲O̲N̲:̲ Power switch on rear side of S-Fan
located below the adapter crate in
rack A.
18) C̲H̲E̲C̲K̲ S-Fan Running
19) T̲U̲R̲N̲ ̲O̲N̲:̲ Power switch on adapter power supply,
right hand part on the rear of the
adapter crate in rack A.
20) C̲H̲E̲C̲K̲:̲ "Power on" lamps lit on the two OPTO
T/R.
21) T̲U̲R̲N̲ ̲O̲F̲F̲:̲ Miniature circuit breaker in CAMPS
PDB corresponding to power circuit
for main switch in rack A. Leave the
circuit breaker in position OFF.
4.9.5 M̲a̲i̲n̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲a̲c̲k̲ ̲B̲ ̲S̲w̲i̲t̲c̲h̲ ̲2̲ ̲C̲i̲r̲c̲u̲i̲t̲ ̲N̲o̲.̲ ̲5̲
1) T̲U̲R̲N̲ ̲O̲N̲: Right hand power switch on front of
the mains switch in rack B.
2) C̲H̲E̲C̲K̲: Green "power on" lamp above switch
lit.
3) T̲U̲R̲N̲ ̲O̲N̲: Switch on power supply located on the
rear of the watchdog crate (A2A4).
4) C̲H̲E̲C̲K̲:̲ Green "Power on" lamp above switch
lit.
Fans running (build-in fans right hand
side of the crate).
5) T̲U̲R̲N̲ ̲O̲F̲F̲:̲ Miniature circuit breaker in CAMPS
PDB corresponding to power circuit
for switch 1 in main switch rack B.
Leave the miniature circuit breaker
in position OFF.
4.9.6 M̲a̲i̲n̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲a̲c̲k̲ ̲B̲ ̲S̲w̲i̲t̲c̲h̲ ̲1̲ ̲C̲i̲r̲c̲u̲i̲t̲ ̲N̲o̲.̲ ̲2̲
Left hand power switch on front of the main switch
in rack B is in position ON. Turn on the mini circuit
breaker in CAMPS PDB for circuit No. 2.
1) T̲U̲R̲N̲ ̲O̲N̲:̲ Main switch on the rear side of floppy
disk station.
2) C̲H̲E̲C̲K̲:̲ "Power on" lamp lit and blower inside
both floppy disk drives running.
(Power on lamp lit behind the PDP).
3) T̲U̲R̲N̲ ̲O̲F̲F̲:̲ CAMPS PDB mini circuit breaker circuit
No. 2.
4.9.7 M̲a̲i̲n̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲a̲c̲k̲ ̲C̲ ̲S̲w̲i̲t̲c̲h̲ ̲2̲ ̲C̲i̲r̲c̲u̲i̲t̲ ̲N̲o̲.̲ ̲6̲
S-FAN will be in poss. on and starts running.
Repeat step 5.9.4 item 1 thru 8 for the main switch
and equipment in rack C (right hand switch).
9) T̲U̲R̲N̲ ̲O̲N̲:̲ Supply A (right hand) on the rear of
the D-fan in rack B.
10) C̲H̲E̲C̲K̲:̲ Fan running/green lamp in front of
fan lit.
11) T̲U̲R̲N̲ ̲O̲N̲:̲ Power supply A (right hand) on the
rear of the channel unit crate in rack
B.
12) C̲H̲E̲C̲K̲:̲ Green "power on" lamp above switch
lit.
13) T̲U̲R̲N̲ ̲O̲N̲:̲ Power supply A (left hand) from the
front of the CU.
14) C̲H̲E̲C̲K̲:̲ All 5 power indicator lamps lit on
front of the power supply.
15) T̲U̲R̲N̲ ̲O̲N̲:̲ Power switch on adapter power supply,
left hand part on the rear of the adapter
crate in rack C (A3A5A22).
16) C̲H̲E̲C̲K̲:̲ "Power on" lamps lit on right hand
section of the adapter crate (4 L/L
adapters)
17) T̲U̲R̲N̲ ̲O̲F̲F̲:̲ Miniature circuit breaker in CAMPS
PDB corresponding to power circuit
for switch 2 in main switch rack C.
4.9.8 M̲a̲i̲n̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲a̲c̲k̲ ̲D̲ ̲S̲w̲i̲t̲c̲h̲ ̲1̲ ̲C̲i̲r̲c̲u̲i̲t̲ ̲N̲o̲.̲ ̲7̲
1) T̲U̲R̲N̲ ̲O̲N̲:̲ Power switch No. 1 (left hand) on front
of the main switch in rack D.
2) C̲H̲E̲C̲K̲:̲ Green "power on" lamp above switch
lit.
3) T̲U̲R̲N̲ ̲O̲N̲:̲ Power switch on the rear main power
panel of TDX crate assy #1 (2A1A9).
Power switch on the front of the main
power supply TDX crate assy #1.
4) C̲H̲E̲C̲K̲:̲ +/-12V and 5V lamps on main power supply
lit.
5) T̲U̲R̲N̲ ̲O̲N̲:̲ Power switch on the rear adapter power
supply TDX crate assy #1.
6) C̲H̲E̲C̲K̲:̲ Green power lamps on all adapter modules
in TDX crate assy #1 lit.
7) T̲U̲R̲N̲ ̲O̲N̲:̲ Rear power switch on S-fan located
below TDX crate assy #1.
8) C̲H̲E̲C̲K̲:̲ Fan running
9) Repeat step 5.9.8 item 3 thru 6 for TDX crate assy
#2 (2A1A7).
4.9.9 M̲a̲i̲n̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲a̲c̲k̲ ̲E̲ ̲S̲w̲i̲t̲c̲h̲ ̲2̲ ̲C̲i̲r̲c̲u̲i̲t̲ ̲N̲o̲.̲ ̲7̲
1) T̲U̲R̲N̲ ̲O̲N̲:̲ Power switch No. 2 (right hand) on
front of the main switch in rack E.
2) Repeat step 5.9.8 item 3 through 8 for TDX crate
assy #7 (2A2A9) and the S-Fan (2A2A11).
3) Repeat step 5.9.8 item 3 through 6 for TDX crate
assy #8 (2A2A7).
4) T̲U̲R̲N̲ ̲O̲F̲F̲:̲ Miniature circuit breaker in CAMPS
PDB corresponding to power circuit
for PLF line 7.
4.9.10 M̲a̲i̲n̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲a̲c̲k̲ ̲E̲ ̲S̲w̲i̲t̲c̲h̲ ̲1̲ ̲C̲i̲r̲c̲u̲i̲t̲ ̲N̲o̲.̲ ̲9̲
1) T̲U̲R̲N̲ ̲O̲N̲:̲ Power switch No. 1 (left hand) on front
of the main switch in rack E.
2) Repeat step 5.9.8 item 3 through 8 for TDX crate
assy #5 (2A2A9) and the S-fan (2A2A11).
3) Repeat step 5.9.8 item 3 through 6 for TDX crate
assy #6 (2A2A7).
4.9.11 M̲a̲i̲n̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲a̲c̲k̲ ̲G̲ ̲S̲w̲i̲t̲c̲h̲ ̲1̲ ̲C̲i̲r̲c̲u̲i̲t̲ ̲N̲o̲.̲ ̲9̲
1) T̲U̲R̲N̲ ̲O̲N̲:̲ Power switch No. 1 (left hand) on front
of the main switch in rack G.
2) Repeat step 5.9.8 item 3 through 8 for TDX crate
assy #11 (2A4A7) and the S-fan (2A4A11).
3) T̲U̲R̲N̲ ̲O̲F̲F̲:̲ Miniature circuit breaker in CAMPS
PDB corresponding to power circuit
for PLF line 9.
4.9.12 M̲a̲i̲n̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲a̲c̲k̲ ̲D̲ ̲S̲w̲i̲t̲c̲h̲ ̲2̲ ̲C̲i̲r̲c̲u̲i̲t̲ ̲N̲o̲.̲ ̲8̲
1) T̲U̲R̲N̲ ̲O̲N̲:̲ Power Switch No. 2 (right hand) on
the front of the main switch in rack
D.
2) Repeat step 5.9.8 item 3 through 8 for TDX crate
assy #3 (2A1A3) and the S-fan (2A1A5).
3) Repeat step 59.8 item 3 through 6 for TDX crate
assy #4 (2A1A1).
4.9.13 M̲a̲i̲n̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲a̲c̲k̲ ̲F̲ ̲S̲w̲i̲t̲c̲h̲ ̲2̲ ̲C̲i̲r̲c̲u̲i̲t̲ ̲N̲o̲.̲ ̲8̲
1) T̲U̲R̲N̲ ̲O̲N̲: Power switch No. 2 (right hand) on
the front of the main switch in rack
F.
2) Repeat step 5.9.8 item 3 through 8 for TDX crate
assy #9 (2A3A3) and the S-fan (2A3A5).
3) Repeat step 5.9.8. item 3 through 6 for TDX crate
#10 (2A3A1).
4.9.14 T̲U̲R̲N̲ ̲O̲N̲:̲ All the miniature circuit breakers in the
CAMPS PDB switched off in step 5.9.4, 5.9.5,
5.9.7, 5.9.9, and 5.9.11.
4.9.15 V̲e̲r̲i̲f̲y̲ ̲S̲u̲p̲p̲l̲y̲ ̲V̲o̲l̲t̲a̲g̲e̲ ̲o̲n̲ ̲P̲U̲ ̲C̲r̲a̲t̲e̲s̲
All voltages used in the processor units are verified
by a digital multimeter.
The measurement is carried out on the front panel of
the crate configuration adapter (CCA) located on the
rear side of the PU crates (1A1A23 and 1A3A23, Ref.
figure 4.3). The voltages are checked to be within
below limits:
5V = 5.1 - 5.3V
+12V = 12.1 - 12.5V
-12V = 12.1 - 12.5V
+24V = 22.8 - 25.2V
-24V = 22.8 - 25.2V
FIGURE 4.3
CCA FRONT PANEL
VOLTAGE MEASUREMENT PLUGS
4.9.16 V̲e̲r̲i̲f̲y̲ ̲S̲u̲p̲p̲l̲y̲ ̲V̲o̲l̲t̲a̲g̲e̲ ̲o̲n̲ ̲C̲U̲ ̲C̲r̲a̲t̲e̲
All voltages used in the channel unit are verified
by a digital multimeter. The measurements are carried
out on the front panel of the CCA located on the rear
side of the CU crate (1A2A1A25, Ref. figure 4.3). The
voltages are checked to be within below limits:
+24V = 22.8 - 25.2V
+12V = 12.6 - 12.8V
+5V = 5.4 - 5.72V
-12V = 12.6 - 12.8V
-24V = 22.8 - 25.2V
4.10 I̲N̲S̲P̲E̲C̲T̲I̲O̲N̲ ̲O̲F̲ ̲S̲W̲I̲T̲C̲H̲ ̲S̲E̲T̲T̲I̲N̲G̲S̲ ̲A̲N̲D̲ ̲S̲T̲A̲T̲U̲S̲ ̲L̲E̲D̲S̲
In order to receive a preliminary impression on the
condition of the system after powering up use the below
tables for a visual check of the status LEDs.
If any discrepancies, refer to the CAMPS SITE LEVEL
Maintenance Manual, Doc. CPS/TCM/005.
4.10.1 S̲w̲i̲t̲c̲h̲ ̲S̲e̲t̲t̲i̲n̲g̲s̲
Before checking the status LEDs, all switches must
be placed in correct positions:
U̲N̲I̲T̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲S̲W̲I̲T̲C̲H̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲N̲O̲R̲M̲A̲L̲ ̲P̲O̲S̲S̲
MAP S2 MAIN/NRM NRM
S3 DIS/EN EN
CUCP CU BUS A AUTO
CU BUS B -
DISK CTRL 1 -
DISK CTRL 2 -
DISK CTRL 3 -
LTU 1-5 -
ST.FD. CTLR -
CCBA S1 EN/DIS EN
BSM-X S1 BUS BUS 2
S2 AUTO/MAN/OFF MAN
LTUX-S CH1-CH4 ON
CCA RESET DOWN
After power up press MC ON PROC 1 and 2.
4.10.2 L̲E̲D̲ ̲I̲n̲d̲i̲c̲a̲t̲o̲r̲s̲
The following table list the normal condition of the
equipment LED indicators.
UNIT LED NORM. CONDITION NOTE
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
M̲A̲P̲ POWER ON
TEST OFF ON
FOR
APP.
10
SEC.
AFTER
POWER
UP
P. FAIL OFF
NO CPU OFF BLINKING
A
FEW
SEC.
AFTER
TEST
OFF
CB DMA OFF
DC DMA OFF
PUDIS OFF ON
=
SWITCH
S3
IN
POSS.
DIS.
INH OFF ON
=
SWITCH
S2
IS
OR
HAS
BEEN
IN
POSS.
MAINT.
HALT OFF ON
=
SWITCH
S2
IN
POSS.
MAINT.
MAINT OFF ON
=
SWITCH
S2
IN
POSS.
MAINT.
C̲P̲U̲/̲C̲A̲C̲H̲E̲ POWER ON
CACHE OFF ON
TEST OFF ON
FOR
APP.
1
SEC.
AFTER
POWER
UP
R̲A̲M̲ POWER ON
S̲T̲I̲ POWER ON
TEST OFF ON
FOR
APP.
10
SEC.
AFTER
POWER
UP
BUSY OFF
HIDMA OFF
P.ERR OFF
C.ERR OFF
M.ERR OFF
RX STAT OFF
M̲I̲A̲ POWER ON
ENABLE ON OFF = SWITCH S3 ON
MAP IN POSS. DIS.
T̲I̲A̲ POWER ON
TEST ON (OFF WHEN INITIALIZED)
UNIT LED NORM. CONDITION NOTE
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
C̲C̲A̲ POWER ON
BUSY OFF
M̲B̲T̲ POWER ON
D̲I̲S̲K̲ ̲C̲T̲R̲L̲ POWER ON
TEST OFF ON
FOR
APP.
10
SEC.
AFTER
POWER
UP
ABUS OFF
BBUS OFF
BUSY OFF
S̲T̲.̲F̲D̲.̲C̲T̲R̲L̲ POWER ON
TEST ON
ABUS OFF
BBUS OFF
BUSY ON
FRONT LED OFF
C̲U̲C̲P̲ POWER ON
AUTO CTRL ON
DIS (A OR B) OFF
BUS A AUTO ON
BUS B AUTO ON
L̲T̲U̲ POWER ON
TEST OFF ON
FOR
APP.
10
SEC.
AFTER
POWER
UP
BUS A OFF
BUS B OFF
BOOTL. ON …86…1 …02…
…02… …02… …02…
UNIT LED NORM. CONDITION NOTE
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
C̲I̲A̲-̲A̲/̲B̲ POWER ON
P.FAIL OFF
W̲C̲A̲ POWER ON
ENABLE ON OFF:
SWITCH
S1
IN
POSS.
DIS
D̲C̲A̲ POWER ON
B̲S̲M̲-̲X̲ POWER ON
EXT.POWER ON
BUS 1 OFF
BUS 2 ON
AUTO OFF OFF:
S2
IN
POSS.
MAN.
OR
OFF
MAN ON ON:
S2
IN
POSS.
MAN.
OR
OFF
C̲T̲X̲.̲C̲O̲N̲T̲ POWER ON
TEST OFF ON
FOR
APP.
10
SEC.
AFTER
POWER
UP
REC.ST. OFF
TR.ST. OFF
FUSE OFF
O̲P̲T̲O̲ ̲T̲/̲R̲ POWER ON
RCVL ON RED
LIGHT
(NO
TERM.
CONN)
RTS ON
CTS OFF
SYNC ON RED
LIGHT
(NO
TERM.
CONN)
L̲/̲L̲ ̲A̲D̲A̲P̲ POWER ON
L̲T̲U̲X̲-̲S̲ POWER ON
TEST OFF ON
FOR
APP.
10
SEC.
AFTER
POWER
UP
TDX.ST OFF
CH 1-4 ON OFF:
SWITCH
1-4
OFF
UNIT LED NORM. CONDITION NOTE
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
M̲M̲D̲ READY ON
FAULT/CLEAR OFF
WRITE PROT. OFF ON:
SWITCH
ACTIVATED
S̲M̲D̲ START ON
READY ON
FAULT OFF
PROT. OFF ON:
SWITCH
ACTIVATED
W̲D̲ ̲C̲R̲A̲T̲E̲ POWER ON TERMINATOR BOARD
INSIDE CRATE
4.11 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲D̲E̲L̲T̲A̲ ̲V̲D̲U̲
a) The terminals are distributed to the installation
sites according to AB drawings 102, 105, and 110.
b) Supervisory and maintenance terminals must be placed
on CR provided tables.
c) For two of the SUP. POSS. in the CAMPS area, a
table mounted PDP must be installed.
4.11.1 P̲o̲w̲e̲r̲ ̲P̲l̲u̲g̲ ̲C̲o̲n̲n̲e̲c̲t̲i̲o̲n̲s̲
Power plug connections must be exchanged to fit host
nation provided power outlets.
P̲O̲W̲E̲R̲ ̲C̲O̲R̲D̲ ̲F̲R̲O̲M̲ ̲D̲E̲L̲T̲A̲ 3̲-̲P̲I̲N̲N̲E̲D̲ ̲P̲L̲U̲G̲
Brown Phase
Blue Neutral
Green/Yellow Ground
4.11.2 T̲e̲r̲m̲i̲n̲a̲t̲i̲o̲n̲ ̲o̲f̲ ̲O̲p̲t̲o̲ ̲C̲a̲b̲l̲e̲s̲
a) Before terminating the opto cable, a rubber tubing,
size 8 x 12 x 250 mm, must be mounted on the cable,
see AB dwg. 130.
b) The opto fibres are to be pulled through the rear
waveguide (port 3) into the VDU.
(See AB dwg. 130).
c) The two fibres must be terminated with special
opto connectors.
For detailed termination procedures see para 1.3,
doc. 4. OPTO-CABLE TERMINATION PROCEDURE.
d) In case of opto splicing this will be done by mounting
of an adapter between the two male connectors,
using the same kind of male connectors as for the
terminals.
e) Before connecting the two fibres to the optical
modem board in the VDU, the black receiver cable
with the opto connector must be checked for supplying
enough light emission.
The transmitter of the opto T/R in the TDX crate
is used as source for the opto fibre (black cable
connected).
f) Connect the black fibre in the VDU end to the 11XE
fiber optic power meter and verify that the optical
power output is not less than 34,6dBm.
g) If the Optical Power Output is less than - 34,6
dBm, the cable will be terminated with a new pair
of OPTO connectors. If still outside tolerance,
the cable will be marked as bad and a new cable
must be installed.
h) To get access to the optical modem board located
inside the VDU, unlock the two snappers on the
rear and lift the terminal access cover of the
VDU.
i) The white fibre must be connected to the transmitter
jack ("out") and the black fibre to the receiver
jack ("in") (see AB drawing 130).
j) The opto cable must be permanently marked with
cable No during the termination procedure.
4.11.3 M̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲K̲e̲y̲b̲o̲a̲r̲d̲ ̲a̲n̲d̲ ̲K̲e̲y̲s̲
a) The keyboard cable is connected to the female cannon
plug located on the lower right hand front of the
terminal. The connector is secured by the two front
screws.
b) Remove the two keys placed on the inside of the
terminal access cover and insert the keys in the
key-lock on front of the terminal.
4.12 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲T̲R̲A̲C̲O̲R̲ ̲M̲S̲P̲
4.12.1 P̲o̲w̲e̲r̲ ̲P̲l̲u̲g̲ ̲C̲o̲n̲n̲e̲c̲t̲i̲o̲n̲s̲
Repeat step 4.11.1 for the power plug of the MSP.
4.12.2 T̲e̲r̲m̲i̲n̲a̲t̲i̲o̲n̲ ̲o̲f̲ ̲O̲p̲t̲o̲ ̲C̲a̲b̲l̲e̲s̲
Repeat step 4.11.2 item a) thru g).
h) To get access to the optical modem board located
inside the printer, unlock the two snappers in
front of the printer and lift the cover of the
printer.
i) Install the fibres through the rear connector entry
hole, route through the optical cable entry hole
and connect the white fibre to the transmitter
("output") and the black fibre to the receiver
("input"). (See AB dwg. 130).
j) The opto cable must be permanently marked with
cable number during the termination procedure.
4.12.3 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲P̲A̲P̲E̲R̲ ̲A̲N̲D̲ ̲R̲I̲B̲B̲O̲N̲
Install the paper and the ribbon according to the instructions
in the operator's manual.
4.12.4 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲P̲I̲S̲T̲O̲N̲ ̲S̲P̲R̲I̲N̲G̲
Mount the piston spring between the bottom and the
lid of the printer by rotating the piston spring clockwise
into the screw thread in the bottom of the printer.
The piston spring is connected to the lid by the screw
through the hinge mounted in the lid.
4.13 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲P̲T̲P̲/̲P̲T̲R̲
a) The PTP/PTR is installed in the off-line encryption
area (ref AB drawing 105).
b) The 3/4" 45…0e…o…0f… fitting is mounted in the J-box and
fastened from inside the J-box by the nut.
c) The metallic conduit is mounted to the fitting
by means of the hose lock and the lock nut.
d) Repeat step b) and c) for mounting of the conduit
to the PTP/PTR (see AB drawing 131).
e) The metallic interface cable coming from the filter
box is pulled through the conduit into the PTP/PTR.
The cable will be terminated by a cannon plug according
to the pin assignment table 1-2 in the AB.
f) The cable is connected according to AB drawing
131.
4.14 T̲E̲S̲T̲ ̲O̲F̲ ̲S̲U̲P̲/̲U̲S̲E̲R̲ ̲T̲E̲R̲M̲I̲N̲A̲L̲S̲
4.14.1 T̲e̲s̲t̲ ̲o̲f̲ ̲D̲e̲l̲t̲a̲ ̲V̲D̲U̲
a) Connect the power plug to the wall outlet.
b) Turn on the "power on/off" switch located on the
lower right front of the terminal.
c) Operate the keylock switch to the ON position (turn
right) (right hand front panel).
d) Immediately after power up the terminal executes
a series of system diagnostics. If all are working
properly, the power-up menu will be displayed on
the screen within 10 seconds.
e) Adjust the intensity and focus until the characters
are clear and bright. Do not advance the intensity
too far or the display area may be highlighted.
f) Adjust the audible alarm for the desired sound
level (control shift and the G key).
g) When all the terminals have been switched on and
locally tested, the transmitter of the optical
modem board in the VDU, the white opto cable, and
the opto connection to the TDX crate must be checked
for supplying enough light emission.
h) Connect one by one all the white fibres terminated
in the opto T/R located in the TDX crates to the
11XE fibre optic power meter and check that the
optical power output is less than -34,6dBm.
i) If the Optical Power Output is less than -34,6
dBm, the cable will be terminated with a new pair
of opto connectors. If still outside tolerance,
the cable will be marked as bad and a new cable
must be installed.
4.14.2 O̲p̲e̲r̲a̲t̲i̲o̲n̲a̲l̲ ̲T̲e̲s̲t̲
a) Assure that the required terminal functions and
characteristics are correctly stored by checking
the contents of the Configuration menu:
DEL/BS -N̲ PRT CR DLY -O̲
ECHO -N̲ PRT LF AFT CR -N̲
CR-XOFF -N̲ PRT PROT DATA -N̲
XMT SO SEQ -N̲ PRT BSY -N̲
MEM RELEASED -Y̲ PRT BUSY-HIGH -N̲
PRT FF -N̲
BAUDOT -N̲ PRT BUF (0,1,2,3) -O̲
WRU?X̲7̲2̲6̲0̲ W̲H̲A̲T̲R̲U̲?̲ CAMPS CLK O̲O̲O̲O̲O̲O̲
I/O HOST PRINT
CHAR -7̲ -7̲
PARITY -E̲ -E̲
STOP BITS -C̲ -C̲
BAUD RATE -G̲ -G̲
b) The terminal is logged on to the system
according to procedures stated in the
Operator's Manual.
c) Messages are sent/rec. between the terminal
and other terminals.
4.14.3 T̲e̲s̲t̲ ̲o̲f̲ ̲T̲r̲a̲c̲o̲r̲ ̲M̲S̲P̲
a) Connect the power plug to the wall outlet.
b) Turn on the power switch located on
the rear right hand side.
Verify that the power lamp on the front
panel lights.
c) Operate the key-lock switch to the ON
position (left hand side in front).
d) Depress the "line feed" button on the
TCM front panel and verify that line
feed of paper occurs.
e) Press the test button for not more than
4 sec. Verify that all lamps on the
printer lights.
f) Press the test button for at least 5
sec. Verify that the following is printed:
NO ERRORS IN ROM
NO ERRORS IN RAM
66 LINES BARBERPOLE PATTERN
g) Repeat step 5.15.1 item h) and j) for
test of transmitter and opto connections.
4.14.4 O̲p̲e̲r̲a̲t̲i̲o̲n̲a̲l̲ ̲T̲e̲s̲t̲
Arrange to have one or ore messages sent to the MSP
and verify message contents with the transmitting station.
Verify during print out that the key-lock switch stops
the printing and that no part of the message is lost
when it is turned on again.
4.14.5 T̲E̲S̲T̲ ̲O̲F̲ ̲P̲T̲P̲/̲P̲T̲R̲
Testing the PTP/PTR is a part of the PROCESSOR/LINE
TERMINATION TEST. Ref. 4.15.
4.15 H̲/̲W̲ ̲T̲E̲S̲T̲ ̲P̲R̲O̲C̲E̲S̲S̲O̲R̲/̲L̲I̲N̲E̲ ̲T̲E̲R̲M̲.̲ ̲U̲N̲I̲T̲S̲
By means of the M&D- and the Test Drive Software, all
hardware- and interface functions shall be verified.
The following outlines the major tasks of the testing
sequence.
For a detailed description of the test procedure including
information of test control, test data, expected test
results, test execution procedures, see CPS/TRP/001
FACTORY ACCEPTANCE TEST SPECIFICATIONS AND PROCEDURES.
4.15.1 P̲U̲/̲C̲U̲/̲T̲D̲X̲ ̲F̲u̲n̲c̲t̲i̲o̲n̲a̲l̲ ̲T̲e̲s̲t̲
a) CPU Test
b) MAP Test
c) RAM Test
d) Disk/FD/LTU/TDS
e) Load Test
4.15.2 W̲a̲t̲c̲h̲d̲o̲g̲ ̲P̲r̲o̲c̲e̲s̲s̲o̲r̲ ̲F̲u̲n̲c̲t̲i̲o̲n̲a̲l̲ ̲T̲e̲s̲t̲
a) WDP Test
b) WDP V24 Interface Test
c) WDP CCBA Interface Test
d) PU #1 CCA Test
e) PU #2 CCA Test
f) CU CCA Test
g) TU1-11 BSM-X Test
4.16 I̲n̲s̲p̲e̲c̲t̲i̲o̲n̲/̲R̲e̲p̲a̲i̲r̲ ̲o̲f̲ ̲G̲a̲s̲k̲e̲t̲s̲ ̲o̲n̲ ̲t̲h̲e̲ ̲D̲o̲o̲r̲s̲
a) If by accident parts of the gaskets
are damaged during transportation, these
parts must be replaced to ensure a correct
shielding. The damaged part of the gaskets
are cut by a knife and removed.
b) For mounting details see 4.2.6.
APPENDIX A
AS-BUILT DRAWINGS
This part of the manual gives the site installation
procedure for the relvant Site No.
COVER SHEET
REVISION RECORD
TABLE OF CONTENTS
LIST OF FIGURES
LIST OF DRAWINGS
ABBREVIATIONS
REFERENCES
1. INTRODUCTION
2. CAMPS EQUIPMENT AREA
3. USER TERMINALS AND CABLING
4. EXTERNAL CONNECTIONS
5. EQUIPMENT DATA
6. DRAWINGS