top - download
⟦3dc2ace47⟧ Wang Wps File
Length: 4168 (0x1048)
Types: Wang Wps File
Notes: CPS/TCM/027
Names: »3875A «
Derivation
└─⟦011bcd343⟧ Bits:30006160 8" Wang WCS floppy, CR 0242A
└─ ⟦this⟧ »3875A «
WangText
…02…CPS/TCM/027
…02…LU/830719…02……02…#
CAMPS POWER LINE FILTER
…02……02…CAMPS
CAMPS POWER LINE FILTER
CPS/TCM/027
CDRL Documentation No. 03
Line Item No. 9.3
Bjarne Berthold/Leif Uldam
Kurt Nybroe-Nielsen
SHAPE (3), NCS (1), GJ, KNN, BHB, QA,
Conf. Mgmt., PMS, KM, LT, LU, GQAR
…0e……0e… ILS Manager 830719…0f……0f…
…0e…1
830719…0f… Conf. Mgmt. 830719
3875A/jaa …02…CPS/TCM/027
…02…LU/830719…02… ii
CAMPS POWER LINE FILTER
…02……02…CAMPS
her inds`ttes "Kiss of Life"
…0f… 3875A/jaa …02…CPS/TCM/027
…02…LU/830719…02… iii
CAMPS POWER LINE FILTER
…02……02… CAMPS…0e…
830719 All First Issue of Document
…0f… 3875A/jaa …02…CPS/TCM/027
…02…LU/830719…02… iv
CAMPS POWER LINE FILTER
…02……02…CAMPS…0e…
T̲A̲B̲L̲E̲ ̲O̲F̲ ̲C̲O̲N̲T̲E̲N̲T̲S̲
TITLE PAGE ....................................
i
FIRST AID FOR ELECTRICAL SHOCK .................
ii
REVISION RECORD ................................ iii
TABLE OF CONTENTS ..............................
iv
1 SCOPE ........................................
1
2 MAINTENANCE ..................................
1
3 CONNECTION WITH SURROUNDINGS .................
1
4 APPLICABLE DOCUMENTS .........................
1
5 CAPTOR POWER LINE FILTER DOCUMENTATION .......
2
5.1 SPECIFICATIONS ...........................
3
5.2 BLOCKED SCHEMATIC ........................
5
5.3 PARTS LIST ...............................
6
5.4 ASSEMBLY DRAWING .........................
7
1 S̲C̲O̲P̲E̲
The CAPTOR Power Line Filter (PLF) Technical Manual
is an OEM Manual grouped under 'Peripheral Equipment
Manuals' in the CAMPS Documentation Tree.
\…01…2 M̲A̲I̲N̲T̲E̲N̲A̲N̲C̲E̲
The PLF Box has been soldered together and therefore
it cannot be disassembled.
In case of malfunction, the PLF Box shall be replaced.
3 C̲O̲N̲N̲E̲C̲T̲I̲O̲N̲ ̲W̲I̲T̲H̲ ̲S̲U̲R̲R̲O̲U̲N̲D̲I̲N̲G̲S̲
How the PLF is connected with CAMPS is shown in the
CAMPS Hardware Assembly Breakdown CPS/SDS/017.
4 A̲P̲P̲L̲I̲C̲A̲B̲L̲E̲ ̲D̲O̲C̲U̲M̲E̲N̲T̲S̲
Hardware Assembly Breakdown
CPS/SDS/017
5 C̲A̲P̲T̲O̲R̲ ̲P̲O̲W̲E̲R̲ ̲L̲I̲N̲E̲ ̲F̲I̲L̲T̲E̲R̲ ̲D̲O̲C̲U̲M̲E̲N̲T̲A̲T̲I̲O̲N̲
This manual includes, besides the Specifications, also
the Blocked Schematic, Assembly Drawing and Parts List.
(The CAPTOR Documentation to the Power Line Filter
is enclosed in the following)
5.1 C̲A̲P̲T̲O̲R̲ ̲P̲O̲W̲E̲R̲ ̲L̲I̲N̲E̲ ̲F̲I̲L̲T̲E̲R̲ ̲S̲P̲E̲C̲I̲F̲I̲C̲A̲T̲I̲O̲N̲S̲
Operating voltage: 220 VAC or 240 VAC
Voltage tolerances: +10%/-15%
Voltage Rating: 240 VAC line to case
415 VAC line to line
Operating Frequency
(Power): 50 Hz
Frequency tolerances: + 10%/-10%
Current Rating: 10 Amps RMS continuous
for each of the three paired
sections.
Dielectric Withstanding
Voltage: 1200 VDC line to case
1500 VDC line to line (1
min. at 23…0e…o…0f… C)
Voltage Drop: 1% maximum full load (10
Amps RMS) and unity power
factor
Temperature Rise 25…0e…o…0f… C maximum at full load
Insertion Loss See Figure 5.1-1. in accordance
with MIL-STD-220A, full
load extended to 40KHz.
Max oper. altitude 2000 m above sea level
FIGURE 5.1-1 INSERTION LOSS