top - download
⟦41160d206⟧ Wang Wps File
Length: 60799 (0xed7f)
Types: Wang Wps File
Notes: CPS/TCM/005 (Sec. 5 + 6)
Names: »1698A «
Derivation
└─⟦3fbecbc6f⟧ Bits:30006206 8" Wang WCS floppy, CR 0307A
└─ ⟦this⟧ »1698A «
WangText
'…00……00…'…02…'
…00……00…' '…06…&…09…&…0b…&…0f……1b……01……1b… …1b……06……1a……0c……1a……0e……14……01……14…
…14……06……13……08……13……0a……13……0c……13……0e……13……00……13……02……13… …13……07……12……09……12……0b……12……0d……12……0f……12……01……12… …12……06……11……08……11……0a……11……0c……11……0e……11…
…11……05……11……06……10……08……10……0c……10……0e……10……00……10……02……10… …0f……08……86…1 …02… …02… …02… …02…
1698A/ktd …02…CPS/TCM/005
…02…KJA/830912…02… …02… CAMPS SITE LEVEL MAINTENANCE MANUAL
…02…Issue 1…02… CAMPS
* * * * * * * * * * *
* OUTLET CR2510 *
* * * * * * * * * * *
Figure 4.5.4-5
OUTLET CR 2510
* * * * * * * * * * *
* OUTLET CR2510 *
* * * * * * * * * * *
C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
No controls and indicators on the module
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
Table 4.5.4-5
M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲
No module identification necessary.
* * * * * * * * * * * * * * * Idle indication/
* POWER SUPPLY CR8022S * normal position
* * * * * * * * * * * * * * *
Figure 4.5.4-6
POWER SUPPLY CR 8022S
* * * * * * * * * * * * * * *
* POWER SUPPLY CR8022S *
* * * * * * * * * * * * * * *
C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
+5V Indicates that +5V DC power is available at
(green) the output of the POWER SUPPLY module.
+12V Indicates that +12V DC power is available at
(green) the output of the POWER SUPPLY module.
-12V Indicates that -12V DC power is available at
(green) the output of the POWER SUPPLY module.
FUSE This fuse protects the +12V DC and -12V DC
0.63A POWER SUPPLY.
FUSE This fuse protects the +5V DC POWER SUPPLY.
3.15A
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
Table 4.5.4-6
M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲
No module identification necessary.
* * * * * * * * * * * * *
* TDX CRATE CR1081S *
* * * * * * * * * * * * *
Figure 4.5.4-7
TDX CRATE CR 1081S
* * * * * * * * * * * * *
* TDX CRATE CR1081S *
* * * * * * * * * * * * *
C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
No controls and indicators
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
Table 4.5.4-7
C̲r̲a̲t̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲
No crate identification necessary.
* * * * * * * * * * * * * Idle indication/
* TDX CTRL CR1070S * normal position
* * * * * * * * * * * * *
Figure 4.5.4-8
TDX CTRL CR 1070S
* * * * * * * * * * * * *
* TDX CTRL CR1070S *
* * * * * * * * * * * * *
C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
POWER Indicates that DC power is applied to the
(green) module.
TEST Indicates that an error is detected by the
(red) built-in-test routine. The TEST LED will always light
for a few seconds upon masterclear, since it is on
during the built-in-test routine.
REC ST Indicates that the module has selected upper
(yellow) bus 1.
TR.ST Indicates that an error has been detected in
(red) the TRANSMIT code
FUSE Indicates that the fuse is opened.
(red)
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
Table 4.5.4-8
M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲
TDX Ctrl., slot 1
(only TU1 and TU4): No identification necessary.
S̲t̲r̲a̲p̲s̲ ̲S̲e̲t̲t̲i̲n̲g̲s̲.
SR 2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲5̲ ̲ ̲ ̲6̲ ̲ ̲ ̲7̲ ̲ ̲ ̲8̲ ̲ ̲ ̲9̲ ̲ ̲ ̲1̲0̲ ̲ ̲1̲1̲ ̲ ̲1̲2̲
̲
A B B C B B C B B A A
1̲3̲ ̲ ̲1̲4̲ ̲ ̲1̲5̲ ̲ ̲1̲6̲ ̲ ̲1̲7̲ ̲ ̲1̲8̲ ̲ ̲1̲9̲
B B A A B B B
* * * * * * * * * * Idle indication/
* TSP CR1103S * normal position
* * * * * * * * * *
Figure 4.5.4-9
TSP CR 1103S
* * * * * * * * * *
* TSP CR1103S *
* * * * * * * * * *
C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
No controls and indicators on the module.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
Table 4.5.4-9
M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲
(Rear of crate) No module identification necessary
* * * * * * * * * *
* BACK PANEL *
* * * * * * * * * *
Figure 4.5.5-1a
BACK PANEL (BP)
* * * * * * * * * *
* BACK PANEL *
* * * * * * * * * *
C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
No controls and indicators on the module
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
Table 4.5.5-1
M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲
No module identification necessary.
S̲t̲r̲a̲p̲s̲e̲t̲t̲i̲n̲g̲s̲:̲
* * * * * * * * * *
* BACK PANEL *
* * * * * * * * * *
Figure 4.5.5-1b
BP #1 ADAPTOR CRATE
* * * * * * * * * *
* BACK PANEL *
* * * * * * * * * *
Figure 4.5.5-1c
BP #2 CODING …01…ADAPTOR CRATE
* * * * * * * * * *
* BACK PANEL *
* * * * * * * * * *
Figure 4.5.5-1d
LTUX-S - STAT.MUX.1…01…INTERFACE
* * * * * * * * * *
* BACK PANEL *
* * * * * * * * * *
Figure 4.5.5-1e
BP#1 REMOTE TERMINALS
STAT MUX - OPTO T/R…01…INTERFACE
* * * * * * * * * *
* BACK PANEL *
* * * * * * * * * *
Figure 4.5.5-1f
CODING BP#2 REMOTE TERMINALS STAT MUX
- OCR AND LSM INTERFACE
* * * * * * * * * * * * * * * * Idle indication/
* L/L ADAPTER 4 CHANNELS * normal position
* * * * * * * * * * * * * * * *
Figure 4.5.5-1g
BP#1 OPTIONAL ADAPTOR CRATE
* * * * * * * * * * * * * * * *
* L/L ADAPTOR 4 CHANNELS * Idle indication/
* * * * * * * * * * * * * * * * normal position
Figure 4.5.5-2a
L/L ADAPTOR 4 CHANNELS
* * * * * * * * * * * * * * * *
* L/L ADAPTOR 4 CHANNELS *
* * * * * * * * * * * * * * * *
C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
POWER Indicates that DC power is applied to the
(green) module.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
Table 4.5.5-2
M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲
No address identification.
* * * * * * * * * * * * * * *
* L/L ADAPTER 4 CHANNELS *
* * * * * * * * * * * * * * *
Figure 4.5.5-2b
L/L ADAPTOR LTUX-S/PTP/R INTERFACE
* * * * * * * * * * * * * * *
* L/L ADAPTER 4 CHANNELS *
* * * * * * * * * * * * * * *
Figure 4.5.5-2c
L/L ADAPTOR LTUX-S-TRC/POINT TO POINT INTERFACE
* * * * * * * * * * * * * * *
* L/L ADAPTOR 4 CHANNELS *
* * * * * * * * * * * * * * *
Figure 4.5.5-2d
L/L ADAPTOR REMOTE TERMINAL
STATMUX - OCR INTERFACE
* * * * * * * * * * * * * * *
* L/L ADAPTOR 4 CHANNELS *
* * * * * * * * * * * * * * *
Figure 4.5.5-2e
L/L ADAPTOR REMOTE TERMINALS
STATMUX - VDU/MSP INTERFACE
* * * * * * * * * * * * * * * Idle indication/
* L/L ADAPTOR 1 CHANNEL * normal position
* * * * * * * * * * * * * * *
Figure 4.5.5-3a
L/L ADAPTOR 1 CHANNEL
* * * * * * * * * * * * * * *
* L/L ADAPTOR 1 CHANNEL *
* * * * * * * * * * * * * * *
C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
POWER Indicates that DC power is applied to the
(green) module.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
Table 4.5.5-3
M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲
No address identification.
* * * * * * * * * * * * * *
* L/L ADAPTOR 1 CHANNEL *
* * * * * * * * * * * * * *
Figure 4.5.5-3b
L/L ADAPTOR LTU/SCARS II/ACCIS
INTERFACE
* * * * * * * * * * * * * * *
* L/L ADAPTER 1 CHANNEL *
* * * * * * * * * * * * * * *
Figure 4.5.5-3c
L/L ADAPTOR LTU/COLLOCATED TARE INTERFACE
* * * * * * * * * * * * * * *
* L/L ADAPTER 1 CHANNEL *
* * * * * * * * * * * * * * *
Figure 4.5.5-3d
L/L ADAPTOR LTU/REMOTE TARE INTERFACE
* * * * * * * * * * * * * *
* L/L ADAPTER 1 CHANNEL *
* * * * * * * * * * * * * *
Figure 4.5.5-3e
L/L ADAPTOR LTUX-S/OCR INTERFACE
* * * * * * * *
* TARE MODEM *
* * * * * * * *
Figure 4.5.5-4
TARE MODEM
* * * * * * * *
* TARE MODEM *
* * * * * * * *
C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
The controls and indicators of the modem
is described in the Modem Operator Manual
Doc.No. CPS/TCM/016 in the section designated
Controls and Indicators.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
Table 4.5.5-4
U̲N̲I̲T̲ ̲S̲W̲I̲T̲C̲H̲ ̲S̲E̲T̲T̲I̲N̲G̲S̲:̲
T̲A̲R̲E̲ ̲M̲O̲D̲E̲M̲
BASIC MODULE
W 1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲
A A A A + +
SR a̲ ̲ ̲ ̲ ̲b̲ ̲ ̲ ̲ ̲c̲ ̲ ̲ ̲ ̲d̲ ̲ ̲ ̲ ̲e̲ ̲ ̲ ̲ ̲f̲ ̲ ̲ ̲ ̲g̲ ̲ ̲ ̲ ̲h̲ ̲ ̲ ̲ ̲i̲ ̲ ̲ ̲ ̲j̲
̲ ̲ ̲ ̲k̲ ̲ ̲ ̲ ̲m̲ ̲ ̲ ̲n̲
+ + + - - - + + - - + - +
SWA 1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲
1 1 0 1 0 0 1
SWB 1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲ ̲ ̲ ̲ ̲8̲
1 1 0 0 0 0 0 1
SWC 1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲
1 0 1 0 "1" = OFF
U̲P̲P̲E̲R̲ ̲M̲O̲D̲U̲L̲E̲:
SWA 1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲
1 1 1 1 1 1 1
SWA 1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲
1 1 0 1 0 1 1
* * * * * * * *
* TARE MODEM *
* * * * * * * *
S̲Y̲N̲C̲ ̲A̲D̲A̲P̲T̲O̲R̲:
W 1 2 3
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
A B A
SR a b c d
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
- - - -
NOTE: During FAT SR d must be implemented (+)
remove before shipping.
(This page is intentionally left blank)
* * * * * * * * * * * * * Idle indication/
* OPTO T/R CR80109 * normal position
* * * * * * * * * * * * *
Figure 4.5.5-5a
OPTO T/R CR 80109
* * * * * * * * * * * * *
* OPTO T/R CR80109 *
* * * * * * * * * * * * *
C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
POWER Indicates that DC power is applied to the
(green) module.
RCVL Indicates that a low level voltage signal is
(red) not being received.
RTS Indicates that a Request To Send (RTS) is being
(yellow) signalled.
CTS Indicates that a Clear To Send (CTS) is being
(yellow) signalled.
SYNC Indicates that a Synchronization signal is
(red) not being received.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
Table 4.5.5-5
M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲
No identification necessary.
* * * * * * * * * * * * *
* OPTO T/R CR80109 *
* * * * * * * * * * * * *
Figure 4.5.5-5b
OPTO WDP/VDU AND MSP INTERFACE
ADAPTOR CRATE
* * * * * * * * * * * * *
* OPTO T/R CR80109 *
* * * * * * * * * * * * *
Figure 4.5.5-5c
OPTO REMOTE TERMINALS STAT MUX - VDU/MSP
INTERFACE
* * * * * * * * * * * * *
* OPTO T/R CR80109 *
* * * * * * * * * * * * *
Figure 4.5.5-5d
OPTO LTUX-S - VDU/MSP INTERFACE
* * * * * * * * *
* OPTO MSP *
* * * * * * * * *
Figure 4.5.5-6a
OPTO MSP
* * * * * * * * *
* OPTO MSP *
* * * * * * * * *
C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
POWER Indicates that DC power is applied to the
(green) module.
RCVL Indicates that a low level voltage signal is
(red) not being received.
RTS Indicates that a Request To Send (RTS) is being
(yellow) signalled.
CTS Indicates that a Clear To Send (CTS) is being
(yellow) signalled.
SYNC Indicates that a Synchronization signal is
(red) not being received.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
Table 4.5.5-6
M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲
No identification necessary.
* * * * * * * * *
* OPTO MSP *
* * * * * * * * *
S̲t̲r̲a̲p̲s̲e̲t̲t̲i̲n̲g̲s̲ ̲i̲n̲ ̲O̲P̲T̲O̲ ̲m̲o̲d̲u̲l̲e̲ ̲(̲O̲M̲3̲)̲:̲
Figure 4.5.5-6b
OPTO MSP Strapsettings
(This page is intentionally left blank)
* * * * * * * * *
* OPTO VDU *
* * * * * * * * *
Figure 4.5.5-7a
OPTO VDU
* * * * * * * * *
* OPTO VDU *
* * * * * * * * *
C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
POWER Indicates that DC power is applied to the
(green) module.
RCVL Indicates that a low level voltage signal is
(red) not being received.
RTS Indicates that a Request To Send (RTS) is being
(yellow) signalled.
CTS Indicates that a Clear To Send (CTS) is being
(yellow) signalled.
SYNC Indicates that a Synchronization signal is
(red) not being received.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
Table 4.5.5-7
M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲
No identification necessary.
* * * * * * * * *
* OPTO VDU *
* * * * * * * * *
S̲t̲r̲a̲p̲s̲ ̲s̲e̲t̲t̲i̲n̲g̲s̲ ̲i̲n̲ ̲O̲P̲T̲O̲ ̲m̲o̲d̲u̲l̲e̲ ̲(̲O̲M̲1̲)̲ ̲M̲a̲i̲n̲ ̲S̲i̲t̲e̲
Figure 4.5.5-7b
OPTO VDU MAIN SITE
* * * * * * * * *
* OPTO VDU *
* * * * * * * * *
S̲t̲r̲a̲p̲s̲ ̲s̲e̲t̲t̲i̲n̲g̲s̲ ̲i̲n̲ ̲O̲P̲T̲O̲ ̲m̲o̲d̲u̲l̲e̲ ̲(̲O̲M̲1̲)̲ ̲R̲e̲m̲o̲t̲e̲ ̲S̲i̲t̲e̲
Figure 4.5.5-7c
OPTO VDU REMOTE SITE
* * * * * * * * * * * * * * *
* STATISTICAL MULTIPLEXER *
* * * * * * * * * * * * * * *
FRONT VIEW
Figure 4.5.5-8
STATISTICAL MULTIPLEXER
* * * * * * * * * * * * * *
* STATISTICAL MULTIPLEXER *
* * * * * * * * * * * * * *
C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
The controls and indicators of the statistical
multiplexer is described in the STAT.MUX.
User's Manual Doc.No. CPS/TPN/008 Sec. 4.1
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
Table 4.5.5-8
U̲n̲i̲t̲ ̲S̲w̲i̲t̲c̲h̲ ̲S̲e̲t̲t̲i̲n̲g̲s̲:̲
S̲T̲A̲T̲M̲U̲X̲ ̲(̲M̲A̲I̲N̲ ̲S̲I̲T̲E̲:̲
B̲A̲S̲I̲C̲ ̲B̲O̲A̲R̲D̲:
S1 1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲ ̲ ̲ ̲ ̲8̲ ̲ ̲
1 0 0 1 1 1 0 0
S2 1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲ ̲ ̲ ̲ ̲8̲ ̲ ̲
1 0 1 1 1 1 1 1
S3 1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲ ̲ ̲ ̲ ̲8̲ ̲ ̲
1 1 0 0 1 1 0 0
S4 1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲ ̲ ̲ ̲ ̲8̲ ̲ ̲
1 1 0 0 1 1 0 0
U̲P̲P̲E̲R̲ ̲B̲O̲A̲R̲D̲:
S1 1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲ ̲ ̲ ̲ ̲8̲ ̲ ̲
1 1 0 0 1 1 0 0
S2 1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲ ̲ ̲ ̲ ̲8̲ ̲ ̲
1 1 0 0 1 1 0 0
"1" =
OPEN
* * * * * * * * * * * * * *
* STATISTICAL MULTIPLEXER *
* * * * * * * * * * * * * *
S̲w̲i̲t̲c̲h̲ ̲S̲e̲t̲t̲i̲n̲g̲s̲:̲
S̲T̲A̲T̲M̲U̲X̲ ̲(̲R̲E̲M̲O̲T̲E̲ ̲S̲I̲T̲E̲)̲
B̲A̲S̲I̲C̲ ̲B̲O̲A̲R̲D̲:
S1 1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲5̲ ̲ ̲ ̲6̲ ̲ ̲ ̲7̲ ̲ ̲ ̲8̲ ̲ ̲
1 1 0 1 1 1 1 1
S2 1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲5̲ ̲ ̲ ̲6̲ ̲ ̲ ̲7̲ ̲ ̲ ̲8̲ ̲ ̲
1 0 1 1 1 1 1 1
S3 1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲5̲ ̲ ̲ ̲6̲ ̲ ̲ ̲7̲ ̲ ̲ ̲8̲ ̲
1 1 1 1 1 1 1 1
S4 1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲5̲ ̲ ̲ ̲6̲ ̲ ̲ ̲7̲ ̲ ̲ ̲8̲ ̲
1 1 1 1 1 1 1 1
U̲P̲P̲E̲R̲ ̲B̲O̲A̲R̲D̲:
S1 1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲5̲ ̲ ̲ ̲6̲ ̲ ̲ ̲7̲ ̲ ̲ ̲8̲ ̲
1 1 1 1 1 1 1 1
S2 1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲5̲ ̲ ̲ ̲6̲ ̲ ̲ ̲7̲ ̲ ̲ ̲8̲ ̲
1 1 1 1 1 1 1 1
"1" = OPEN
(This page is intentionally left blank)
* * * * * * * * *
* MAINS SWITCH *
* * * * * * * * *
Figure 4.5.6-1
MAINS SWITCH
* * * * * * * * *
* MAINS SWITCH *
* * * * * * * * *
C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
MAINS SWITCH This indicator illuminates to indicate that
ON/OFF there is an output of the mainswitch
(LED)
MAINS SWITCH This switch controls the AC power output
ON/OFF of the Mains Switch unit
(SWITCH)
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
Table 4.5.6-1
* * * * * * * * * * *
* DELTA DATA, VDU *
* * * * * * * * * * *
Figure 4.5.7-1a
DELTA DATA, VDU
* * * * * * * * * * *
* DELTA DATA, VDU *
* * * * * * * * * * *
To access the OPTION Menu
a. Hit the MON key.
b. Move the cursor to the entry, OPTION.
c. Hit the ENTER key.
The screen now displays the OPTION menu as shown:
Figure 4.5.7-1b
VDU OPTION MENU
* * * * * * * * * * *
* DELTA DATA, VDU *
* * * * * * * * * * *
To access the SPLIT menu
a. Hit the MON key.
b. Move the cursor to the entry, SPLIT.
c. Hit the ENTER key.
The screen now displays the SPLIT menu as shown:
Figure 4.5.7-1c
VDU, SPLIT MENU
* * * * * * * * * * *
* DELTA DATA, VDU *
* * * * * * * * * * *
To access the CONFIGURATION menu
a. Hit the MON key.
b. Move the cursor to the entry, CONFIGURATION.
c. Hit the ENTER key.
The screen now displays the CONFIGURATION menu as shown:
Figure 4.5.7-1d
MAINTENANCE POSITION VDU
CONFIGURATION MENU
* * * * * * * * * * *
* DELTA DATA, VDU *
* * * * * * * * * * *
To access the CONFIGURATION menu
a. Hit the MON key.
b. Move the cursor to the entry, CONFIGURATION.
c. Hit the ENTER key.
The screen now displays the CONFIGURATION menu as shown:
Figure 4.5.7-1e
OPERATOR VDU
CONFIGURATION MENU
* * * * * * * * * * *
* DELTA DATA, VDU *
* * * * * * * * * * *
C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
BRIGHT Adjusts the intensity of the characters
displayed on the screen.
FOCUS Adjusts the focus of the characters displayed
on the screen.
BELL Changes the autio level of the bell.
POWER This switch controls the power of the VDU.
(switch)
FUSE (Rear of VDU) This fuse opens if the current to the
VDU exceeds 2 amp.
KEY-LOCK Prevents using of the VDU by unauthorized
(switch) persons.
Key-lock must be in the ON position for the VDU to
operate.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
Table 4.5.7-1
* * * * * * * * * * *
* TRACOR, MSP *
* * * * * * * * * * *
Figure 4.5.8-1
MEDIUM SPEED PRINTER, MSP
* * * * * * * * * * *
* TRACOR, MSP *
* * * * * * * * * * *
C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
PAPER OUT Indicates that the page printer paper supply is depleted.
EOF Indicates five characters prior to the end of a line.
PWR Indicates that power is applied to the equipment.
ALARM Sounds upon receipt of a precedence message
(audible indic) header or five characters before the end of a line.
AUDIO LEVEL Varies the sound level output of the audio
(control) alarm.
PARITY ERROR Indicates a received parity error is detected. (push
button) may clear the error indication.
LINE FEED Push button. Causes the page printer to feed paper.
FORM FEED Push button. Causes the page printer to advance paper
to the top of the next form.
TEST Push button. Momentary depression causes lamp test.
Push button. Continued depression 5 seconds or longer
initiates system self-test.
SUSP PRINT (push button) Changed printer line status.
(indicator) Printing is suspended.
KEY-LOCK Prevents printing by unauthorized persons.
(switch) Key-lock must be in the ON positon for the printer
to operate.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
Table 4.5.8-1
* * * * * * * * * * *
* TRACOR, MSP *
* * * * * * * * * * *
M̲S̲P̲ ̲I̲N̲T̲E̲R̲N̲A̲L̲ ̲S̲T̲R̲A̲P̲S̲E̲T̲T̲I̲N̲G̲
A̲ ̲1̲0̲:̲ Signal Interface Card.
S1 1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲5̲ ̲ ̲ ̲6̲ ̲ ̲ ̲7̲ ̲
1 0 0 0 0 0 0
S2 1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲5̲ ̲ ̲ ̲6̲ ̲ ̲ ̲7̲ ̲
1 1 1 1 1 0 1 "1" = OPEN
A̲ ̲2̲: CPU Card
BAUD RATE:
S1 1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ S1 1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲B̲R̲
0 1 0 1 1 0 1 0 110
0 1 1 0 150
"1" = ON 1 1 1 0 300
0 0 0 1 600
1 0 0 1 1200
0̲ ̲ ̲ ̲1̲ ̲ ̲ ̲0̲ ̲ ̲ ̲1̲ ̲ ̲ ̲2̲4̲0̲0̲
A̲ ̲7̲:̲ Printer Interface Card
S1 1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲
0 1 1 0 "l" = ON
* * * * * *
* PTP/R *
* * * * * *
Figure 4.5.9-1a
PAPER TAPE PUNCHER/PAPER TAPE READER,PTP/PTR
* * * * * *
* PTP/R *
* * * * * *
C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
PAPER ON/OFF SWITCH Applies 115 VAC Power to both the reader and punch
circuits.
POWER ON LED Indicates reader/punch circuits energized.
Switch Momentary Switch to control tape direction.
RUN/LOAD Switch RUN for normal reading operation.
LOAD to inhibit reader stopping for tape loading, data
outputs remain active.
LDR Switch Pushbutton switch to produce a tape leader with sprocket
holes. The punch operational the 60 characters per
second rate in the forward direction.
TAPE STATUS LED Indicates a tape handling problem in the punch only.
The punch tape supply is exhausted or the tape is broken,
loose or too taut.
REWIND Switch Controls rewind post to rewind short strips of tape.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
Table 4.5.9-1
* * * * * *
* PTP/R *
* * * * * *
P̲T̲P̲/̲R̲ ̲I̲N̲T̲E̲R̲N̲A̲L̲ ̲S̲T̲R̲A̲P̲S̲ ̲S̲E̲T̲T̲I̲N̲G̲:̲
Reader PCB:
S1 ̲ ̲1̲^̲ ̲2̲^̲ ̲3̲^̲ ̲4̲
OFF^ON^ON^ON
Puncher PCB:
Thumbwheel switch: 5
A̲R̲C̲ ̲V̲1̲1̲/̲V̲2̲8̲ ̲A̲D̲A̲P̲T̲O̲R̲ ̲C̲A̲R̲D̲ ̲ (rear of PTP/R)
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲
^ ^3/ ^4/ ^5/ ^6/ ^8/ ^4/ ^5/ ^6/ ^4/ ^6/ ^4/ ^6/ ^4/ ^6/
^
^ ̲S̲R̲ ̲ ̲^̲ ̲ ̲1̲^̲ ̲ ̲1̲^̲ ̲ ̲1̲^̲ ̲ ̲1̲^̲ ̲ ̲1̲^̲ ̲ ̲2̲^̲ ̲ ̲2̲^̲ ̲ ̲2̲^̲ ̲ ̲3̲^̲ ̲ ̲3̲^̲ ̲ ̲4̲^̲ ̲ ̲4̲^̲ ̲ ̲5̲^̲
̲ ̲5̲^
^ ^ ^ ^ ^ ^ ^ ^ ^ ^ ^ ^ ^ ^ ^
^
^ Pos.^ B ^ A ^ B ^ B ^ B ^ B ^ C ^ B ^ C ^ A ^ B ^ C ^ B ^
B ^
^ ̲ ̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲
̲ ̲ ̲^
(shown in figure 4.5.9-1b)
* * * * * *
* PTP/R *
* * * * * *
Figure 4.5.9-1b
PTP/R ARC Straps Settings
5 S̲/̲W̲ ̲M̲A̲I̲N̲T̲E̲N̲A̲N̲C̲E̲ ̲P̲R̲O̲C̲E̲D̲U̲R̲E̲S̲
5.1 I̲N̲T̲R̲O̲D̲U̲C̲T̲I̲O̲N̲
The maintenance procedures can be defined in 3 main
levels:
1) Detecting an error
2) Reporting and registration of the error
3) Performing S/W modifications
Modifications will be distributed from the CSSI to
any CAMPS site where the RST will perform the installation
(see 5.3). The following types of S/W modifications
are identified:
a) System S/W
b) Application S/W and
c) Patch files
The S/W modifications are transported to CAMPS sites
on applicable media (normally floppy disk).
A step-by-step procedure describing S/W maintenance
is shown in section 5.3.2.
5.2 R̲E̲P̲O̲R̲T̲I̲N̲G̲ ̲A̲N̲D̲ ̲R̲E̲G̲I̲S̲T̲R̲A̲T̲I̲O̲N̲
A failure reporting- and registration system will be
established in order to maintain the operation and
overall performance of the system. By an analysis of
the errors reported, it is possible to screen systematic
failures and proper action may be taken to avoid unnecessary
down-time. Prerequisites for failure reports from the
sites are a properly maintained logbook and the error
printouts appearing on the maintenance position line
printer.
a) F̲a̲i̲l̲u̲r̲e̲ ̲R̲e̲p̲o̲r̲t̲s̲
When a failure report is filled in at a site (see
Figure 5.2-1), one copy is filed for information
and two copies are sent to CSSI. When the problem
is solved, the report is completed and one copy
is filed at CSSI enclosed to the F̲ield C̲hange N̲otice
(see Figure 6.3.2-1) and one copy is filed at CR.
The failure report-file may be used in screening
for systematic errors.
b) L̲o̲g̲b̲o̲o̲k̲
The logbook (see Figure 6.1.1-1) must reflect the
time span of any irregularity, the cause of it,
what has been done within the time span to correct
it, a signature, and a reconfiguration, if any.
The logbook may be a reference document for a failure
report to which a copy may be enclosed. Furthermore,
the logbook must be accessible to CR to the extent
necessary for systematic troubleshooting.
c) E̲r̲r̲o̲r̲ ̲P̲r̲i̲n̲t̲o̲u̲t̲s̲
All events detected by the on-line diagnostics
are logged on the maintenance position line printer
(see Appendix A) with a time indication and an
error information. If an automatic switchover is
performed, this will also be indicated.
As the error printouts are time information of
the equipment status, it is mandatory that they
are filed. The error printouts must be enclosed
to the failure report. Those printouts must be
accessible to CR to the extent necessary for a
systematic troubleshooting.
Figure 5.2-1
5.3 P̲E̲R̲F̲O̲R̲M̲I̲N̲G̲ ̲S̲/̲W̲ ̲M̲O̲D̲I̲F̲I̲C̲A̲T̲I̲O̲N̲S̲
Patchfiles, modified S/W as well as new S/W, is developed
and tested at the CSSI site. On applicable media, the
modifications together with the FCN are transported
to CAMPS sites, where the S/W is installed by the RST,
using the guidelines described in 5.3.1 and 5.3.2.
5.3.1 L̲o̲a̲d̲ ̲o̲f̲ ̲M̲o̲d̲i̲f̲i̲e̲d̲ ̲S̲/̲W̲
The above mentioned types of S/W are loaded in the
operational disks, using the commands and procedures
described in CPS/OPM/005, section 5.6.4. The new S/W
is loaded at the start-up time using the procedures
shown in CPS/OPM/005, section 5.3.2.
The FCN must contain sufficient information concerning:
a) Type of software Modified system S/W
Modified application S/W
Patchfiles and the number of
files
b) Type of media
Information to be used in 5.3.2.
5.3.2 S̲t̲e̲p̲-̲b̲y̲-̲S̲t̲e̲p̲ ̲M̲a̲i̲n̲t̲e̲n̲a̲n̲c̲e̲
S̲T̲E̲P̲ A̲C̲T̲I̲O̲N̲ R̲E̲M̲A̲R̲K̲S̲
1 ERROR OCCUR Error-report is written on the
maintenance position printer.
If error-report-id indicates
that a S/W error has occurred
(see Figure 4.3.2-1), go to
step 2, if not,
GO TO chapter 4.3.
2 WRITE AND DIS- The following must be enclosed:
PATCH FAILURE
REPORT TO CCSI a) Printouts from maintenance
SITE position printer, such as
WAIT FOR REPLY! Log of commands
Error-reports
System status information
b) Copy of logbook
The failure report must be filled
in as adequate as possible.
GO TO step 3.
3 FCN ENCLOSED CSSI site will use applicable
THE S/W media to transport the
MODIFICATION modification:
IS RECEIVED
GO TO step 4
S̲T̲E̲P̲ A̲C̲T̲I̲O̲N̲ R̲E̲M̲A̲R̲K̲S̲
4 RST WILL LOAD As mentioned in 5.3.1, the FCN
MODIFIED S/W will contain necessary information
concerning load and boot of
the modified S/W.
LOAD OF MODIFIED SOFTWARE -
LMOS
where the following parameters
are taken from the FCN and used
LMOS-parameters:
a) COPY MODE From off-line
disk
From floppy
disk
b) Type of S/W Modified system
S/W
Modified application
S/W
Patchfiles
c) File number If patchfiles,
number of files
GO TO step 5
5 BOOT OF The commands mentioned in
MODIFIED S/W CPS/OPM/005 concerning start-up
procedures must be used with
the same parameters as in step
4a) to step 4b).
…86…1 …02… …02… …02… …02…
5.3 N̲E̲W̲ ̲S̲/̲W̲ ̲L̲O̲A̲D̲I̲N̲G̲ ̲A̲N̲D̲ ̲V̲E̲R̲I̲F̲I̲C̲A̲T̲I̲O̲N̲
TBD
5.4 M̲E̲M̲O̲R̲Y̲ ̲P̲U̲M̲P̲S̲
TBD
5.5 F̲A̲I̲L̲U̲R̲E̲ ̲R̲E̲P̲O̲R̲T̲I̲N̲G̲
TBD
6 F̲A̲I̲L̲U̲R̲E̲ ̲R̲E̲P̲O̲R̲T̲I̲N̲G̲ ̲S̲Y̲S̲T̲E̲M̲
6.1 L̲O̲G̲B̲O̲O̲K̲
A logbook will be issued to be used from the date of
acceptance (PSA) of the equipment. In the logbook all
deviations from the normal operation of the CAMPS site
will be logged. Thus, the loghook must at all times
reflect the status of the equipment and the place where
the history record of the equipment is found. A copy
of the logbook is to be enclosed with the failure report
in case of an error.
6.1.1 L̲o̲g̲b̲o̲o̲k̲ ̲F̲o̲r̲m̲
A logbook sheet is shown in fig. 6.1.1-1 and the use
of the logbook is explained in the subparagraphs below.
6.1.1.1 H̲e̲a̲d̲i̲n̲g̲
The date is written in this field. In case a day's
events cannot be described on one page, subsequent
pages may be added.
6.1.1.2 T̲i̲m̲e̲-̲O̲f̲-̲D̲a̲y̲
The time to be filled in is the time when the event
occurred, that is, the same time which appears on this
printout at the maintenance position line printer.
6.1.1.3 S̲t̲a̲r̲t̲/̲S̲t̲o̲p̲ ̲T̲i̲m̲e̲
The time when an action is commenced is writen in the
start column; similarly, the time when the equipment
is returned to normal operation or when action is terminated
is written in the stop column.
6.1.1.4 S̲y̲m̲p̲t̲o̲m̲
A brief description of the event is written here.
6.1.1.5 A̲c̲t̲i̲o̲n̲ ̲G̲r̲o̲u̲p̲
The Action Group column divides the events into different
chategories. The following groups are defined
A : Errors
B : Preventive Maintenance
C : Verification of repairs from depot
D : Load of new S/W
E : On-Job-Training
F : Equipment Expansion
G : Other Access to the equipment
6.1.1.6 A̲c̲t̲i̲o̲n̲
A brief description of the actions performed is written
here.
6.1.1.7 I̲n̲i̲t̲i̲a̲l̲s̲
The originator must legibly write his name here.
6.2 F̲A̲I̲L̲U̲R̲E̲ ̲R̲E̲P̲O̲R̲T̲S̲
Whenever a failing item is identified and returned
to depot, a Failure Report must be issued as identification.
The failure report will serve as a cover sheet for
other enclosed documentation and ensure that all errors
can be centrally registrated.
It should be noticed that it is important to fill in
the failure report accurately and detailed (if necessary,
with enclosures) as this may ease the troubleshooting
at the next level.
During the warranty phase of the equipment, a record
of all failure reports will be maintained by the manufacturer
(CRAS), but each site should keep a copy for information.
6.2.1 F̲a̲i̲l̲u̲r̲e̲ ̲R̲e̲p̲o̲r̲t̲ ̲F̲o̲r̲m̲
The Failure Report is shown in Figure 6.2.1-1 and the
instructions for filling in the report are outlined
below .
6.2.1.1 F̲a̲i̲l̲u̲r̲e̲ ̲R̲e̲p̲o̲r̲t̲ ̲N̲o̲.̲
Each site (and depot) has been provided an identification
No. which must be applied followed by a serial No.
Her inds`ttes failure report
6.2.1.2 I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲
Sufficient informaton necessary for identification
of the failing item must be provided. In case a H/W
or a firmware error is reported, the following identification
must be completed:
- Name of failing item
- Type No.
- Serial No. (if any)
- Revision No. (if any)
In case a S/W error is reported, the following identification
should be completed as applicable:
- Name of failing item (program, subroutine)
- Type No. (if any)
- Revision No. (if any)
6.2.1.3 P̲h̲y̲s̲i̲c̲a̲l̲ ̲L̲o̲c̲a̲t̲i̲o̲n̲
Sufficient information for identification of the failing
item and its position must be provided. Notice, that
a failure in the main CAMPS equipment may be unequivocally
identified by its identification code. Hence;
1A1A1A4
identifies the MAP module in slot 4 of the processor
crate in rack A (ref. to CAMPS H/W Assembly Break-Down
- CPS/SDS 0617-18).
This part is not completed in case of a S/W error.
6.2.1.4 T̲y̲p̲e̲ ̲o̲f̲ ̲E̲r̲r̲o̲r̲
The appropriate fields must be marked.
6.2.1.5 S̲i̲t̲e̲ ̲L̲e̲v̲e̲l̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲
The following information must be provided:
a) Sitename (abbreviation)
b) Originator's name
c) Date of completion of the failure report
6.1.2.6 R̲e̲p̲a̲i̲r̲ ̲T̲i̲m̲e̲
The following information should be provided:
a) Date-Of-Failure (DOF) and Time-Of-Day (TOD)
The Time-Of-Day must be the same which appears
in the Logbook. The date of failure is written
in case the date is not the same as the date of
the completion of the Failure Report above.
b) Repair Start
Fill-in the TOD when the repair was initiated.
c) Repair Stop
Fill-in the TOD when the repair was stopped.
d) Equipment Operation Restored
Indicate TOD and day/month/year appropriate.
e) Elapsed Time
If the equipment operation has been restored, this
field will indicate the time for which the equipment
was out of service. Notice that this is not necessarily
indicated to the time spent on the repair of the
fault.
6.2.1.7 E̲r̲r̲o̲r̲ ̲D̲e̲s̲c̲r̲i̲p̲t̲i̲o̲n̲
Provide a brief, but thorough description of the failure
indications. Support the descriptions with enclosure
where necessary. Also describe the means which remedied
the failure, if possible.
6.2.1.8 E̲n̲v̲i̲r̲o̲n̲m̲e̲n̲t̲a̲l̲ ̲C̲o̲n̲d̲i̲t̲i̲o̲n̲s̲
If the environmental conditions were abnormal at the
time of failure, it should be indicated in this field.
6.2.1.9 T̲y̲p̲e̲
Indicate the process which was in progress at the timew
of failure. Tasks like
- Retrieval of date (ROD)
- Preventive maintenance (PM)
- Test of repaired modules (TEST)
- On the job training (OJT)
may be indicated in the "Other" field.
6.2.1.10 E̲n̲c̲l̲o̲s̲u̲r̲e̲
Mark as appropriate. Enclose as much information as
possible in order to ease fault finding at the next
level.
6.3 C̲O̲N̲F̲I̲G̲U̲R̲A̲T̲I̲O̲N̲ ̲C̲O̲N̲T̲R̲O̲L̲
6.3.1 I̲n̲t̲r̲o̲d̲u̲c̲t̲i̲o̲n̲
The CAMPS will be managed under a strict configuration
control procedure. During the warrant period CR will
be responsible for advising SHAPE of all changes that
are to be made to the CAMPS hardware and software.
After JFAI the responsibility will be retained by SHAPE.
All instructions for modification or changes to the
CAMPS will be issued by the SHAPE CAMPS System Direction
and Support Office. These will be issued in the form
of Field Change Notices (FCNs).
Site Maintenance Personnel are not permitted to make
any hardware or software changes unless instructed
in a FCN.
The site Configuration Management Inventory shows all
the modules together with their serial number and revision
level. Master records are held by CR and these will
be transferred to SHAPE. As all items of hardware are
exchanged through the depots the precise status of
each site will be maintained with the depot (and Namsa)
computer systems. SHAPE will have access to the system
data base.…86…1 …02… …02… …02… …02…
6.3.2 F̲i̲e̲l̲d̲ ̲C̲h̲a̲n̲g̲e̲ ̲N̲o̲t̲i̲c̲e̲s̲ ̲(̲F̲C̲N̲)̲
6.3.2.1 G̲e̲n̲e̲r̲a̲l̲
Whenever a modification is necessary, a Field Change
Notice (FCN) will be issued and 2 copies will be provided
to SHAPE and 1 copy to each site affected.
The FCN will contain detailed information describing
the:
- Type of information
- Tools, Parts, and time required
- Equipment to be modified
- Instructions for implementing the modifications
Where the FCN indicates use of materials they will
be enclosed. If a modification necessitates amendment
of documentation, new pages will be provided sufficient
to amend all affected documentation.
Generation of FCNs by CR will commence after the Site
Provisional Acceptance and take place during the H/W
or S/W warranty periods whichever is applicable.
6.3.2.2 R̲e̲g̲i̲s̲t̲r̲a̲t̲i̲o̲n̲ ̲o̲f̲ ̲F̲C̲N̲s̲
A reference or Master List of all modifications will
be issued and concurrently updated. Herein the FCNs
are listed consecutively indicating the equipment modified
and the reason for modification.
6.3.2.3 D̲e̲s̲c̲r̲i̲p̲t̲i̲o̲n̲ ̲o̲f̲ ̲F̲C̲N̲s̲
The field Change Notice Sheets shown overleaf are explained
by the following subparagraphs (1-10).
Refer to fig. 6.3.2-1 and -2.
6.3.2.4 H̲e̲a̲d̲i̲n̲g̲
The FCNs are issued consecutively commencing with number
1. The number of pages included in the FCN in question
is indicated.
6.3.2.5 I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲
The part addressed by the FCN is identified by Type,
Parts No., NATO Stock no. if available, and description
as well as the next higher level is indicated.
6.3.2.6 P̲a̲r̲t̲s̲ ̲D̲i̲s̲p̲o̲s̲i̲t̲i̲o̲n̲
A checkmark indicates the disposition of parts, "N.A."
means "Not Applicable".
6.3.2.7 C̲l̲a̲s̲s̲i̲f̲i̲c̲a̲t̲i̲o̲n̲
The checkmark indicates the urgency by which the modification
must be executed. "Desirable" means earliest convenient
opportunity while "Mandatory" means immediately. "Mandatory"
classification is typically employed when the equipment
may malfunction without the modification or if the
operation of the system is endangered.
6.3.2.8 T̲y̲p̲e̲ ̲o̲f̲ ̲I̲n̲f̲o̲r̲m̲a̲t̲i̲o̲n̲
This section is checked as appropriate. The three
main groups existing are:
- Rework (H/W change)
- Spares Change
- Software Change
Figure 6.3.2-1
Field Change Notice, Front Page
Figure 6.3.2- 2
Field Change Notice, Subsequent Pages
6.3.2.9 R̲e̲l̲a̲t̲e̲d̲ ̲I̲n̲f̲o̲r̲m̲a̲t̲i̲o̲n̲
This section cross references related documents to
the FCN. Engineering Change Order (ECO) is the reference
no. for a CR in-house document, while the Failure Report
No. indicates that the FCN is originated by an error
occurred at a site or depot.
6.3.2.10 Fi̲e̲l̲d̲ ̲C̲h̲a̲n̲g̲e̲ ̲D̲e̲s̲c̲r̲i̲p̲t̲i̲o̲n̲
The description includes a reason for action that is,
a brief explanation of why that particular FCN is necessary.
It also describes the change in details or, if the
space is insufficient, provides a summary of the modification.
It is always described as "Is" and "Was".
6.3.2.11 A̲f̲f̲e̲c̲t̲e̲d̲ ̲D̲o̲c̲u̲m̲e̲n̲t̲s̲
If a modification implies that the documentation is
revised, the applicable documents are listed with the
new revision level. Also reference documents are mentioned,
if any.
6.3.2.12 A̲p̲p̲r̲o̲v̲a̲l̲ ̲A̲u̲t̲h̲o̲r̲i̲t̲y̲
The author of the FCN must sign together with the approval
authorities and the RST which implemented the modification.
Upon completion, a signed copy of the front page of
the FCN must be returned to CR to indicate the status
of the equipment. The equipment is considered modified
upon receipt of this copy.
6.3.2.13 S̲u̲c̲c̲e̲e̲d̲i̲n̲g̲ ̲P̲a̲g̲e̲s̲
The succeeding pages provide the detailed information
about the modification. First the tools, parts, and
time required for the modification is indicated, next
step by step instructions illustrated as "Is" and "Was",
if applicable.
6.3.3 I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲ ̲o̲f̲ ̲M̲o̲d̲u̲l̲e̲ ̲R̲e̲v̲i̲s̲i̲o̲n̲ ̲L̲e̲v̲e̲l̲
The following pages describes how the various assemblies
are marked so that site personnal can identify the
revision level of all assemblies.
6.3.3.1 C̲R̲A̲S̲ ̲M̲o̲d̲u̲l̲e̲s̲
a) Modules are identified as a product of type Nos.,
Version Nos., Print Revisions, and Revision Levels.
E.g., a specific LTUX module may be identifies
as
CRAS PART NO 4̲.̲0̲4̲1̲4̲1̲ 0̲8̲ ̲ SER. NO. 3̲2̲8̲ Rev 2̲ -
D̲
Family Name …0e… ̲ ̲ ̲ ̲ ̲…0f…
Version No. …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
Module's Serial No. …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
Print Version …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
Latest Revision …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲…0f…
where
- The PART NO, Version, and Serial No. are a
coherent identification which may be either
in the form of a metal label or directly etched
into the PCB. In the latter case, the version
and serial No. are handwritten directly on
the PCB.
The family name and version No. identifies
a module with respect to Form, Fit, and Function
(FFF). The FFF is established through a baseline
documentation.
- The serial No. refers to the production sequence.
- The print version No. is derived from the PCB
layout number. E.g. the LTUX module
4̲7̲4̲ A̲ - 2̲
PCB Type No. …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
Side A of PCB …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
PCB Revision …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
The PCB revision will always remain the same
on both the A side and B side of the PCB.
- The Revision Level is a matrix which indicates
the ECO status of the board. E.g.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
A B D E
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
means that Revision A, B, and D have been implemented
while Revision C is N/A for this module. This
implies that in the first issue of the print
version the matrix is left blank.
Updates per revision level will not affect
Form, Fit, and Function.
The Revision Matrix may be found either as
a metal label or etched into the PCB.
b) Firmware is identified by CRAS Part No. and Version
Code marked by a label on the top of the PROM.
Any changes to the PROM will be indicated by an
updated version code, but configuration control
is to be maintained at module level. "Minor" changes
will be reflected as new revision levels while
major changes will cause a new module version.
c) Diagrams and Parts lists are issued as baseline
documentation. New revisions will be relected as
"pen and ink" changes until the revisions are incorporated
in a new PCB version. At that time, a new diagram
and parts list will be issued.
d) Field Changes are issued as Field Changes Notices.
Refer to section 6.3 for details.
6.3.3.2 P̲e̲r̲i̲p̲h̲e̲r̲a̲l̲s̲
Peripherals and modules in the CAMPS program which
are not being manufactured by CRAS, are generally controlled
by commercial standards. This means that configuration
control will be ensured by revision levels rather than
by serial Nos. A brief description of each individual
product is provided below.
6.3.3.2.1 M̲M̲D̲ ̲-̲ ̲C̲D̲C̲ ̲M̲o̲d̲e̲l̲ ̲9̲7̲3̲0̲
a) Units are identified by an Equipment Identification
No. found on a label at the rear of the unit (see
Figure 6.4.3.3-1.a). The Series Code indicates
the revision baseline at system level, and the
Equipment Identificaton No. and Series Code should
always be provided with any technical requests.
b) Modules are identified by a 3-letter family code
preceeded by a revision letter (or 2 rev. letters)
(see Figure 6.4.3.3-1.b). The 4 letters correspond
to an 8-digit Parts No. which is stamped upon the
components side of the PCB. Any changes to a PCB
will result in a new revision letter and subsequent
new P/N.
c) Firmware is identified by an 8-digit part No. stamped
upon the IC. A change will result in a new P/N,
but also the revision letter and parts No. of the
module will change.
d) An Equipment Configuration Log Sheet is provided
in front of the Service Manual. All ECOs and reconfigurations
to the equipment should be logged here to reflect
the field history of the equipment.
e) Field Changes are issued as Field Change Orders
(FCO). Upon completion of the modification, the
revision letter and the parts No. must be scratched
out and replaced by the numbers indicated in the
FCO.
When a modification is implemented, it must be
recorded in a Field Change Order Log positioned
beneath the PCB compartment.
Also it must be logged in the Equipment Configuration
Log Sheet placed as the first page of the Service
Manual. In this way, the field history is preserved
both in the equipment and in the documentation.
Fig. a. Equipment Identification
̲ ̲E̲Q̲U̲I̲P̲.̲I̲D̲E̲N̲T̲.̲N̲O̲.̲ ̲S̲E̲R̲I̲E̲S̲ ̲C̲O̲D̲E̲ ̲ ̲ ̲P̲A̲R̲T̲ ̲N̲O̲.̲ ̲ ̲S̲E̲R̲.̲N̲O̲.̲
̲ ̲ ̲ ̲ ̲B̲Z̲ ̲5̲A̲ ̲5̲B̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲1̲3̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲7̲3̲0̲3̲6̲7̲0̲7̲ ̲ ̲ ̲1̲7̲1̲1̲
̲ ̲
MMD Disk …0e… …0f…
80 MByte …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
220/240V, 50Hz
Single Channel …0e… ̲ ̲ ̲ ̲…0f…
w/96 Fixed head
Production Baseline …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
Unit P/N …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
Unit S/N …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲…0f…
Fig. b
H̲ F̲G̲X̲ 7̲6̲9̲3̲ ̲5̲5̲0̲8̲
Revision Level …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
Family Code …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
CDC P/N …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
Figure 6.4.3.1-1
f) Major subassemblies such as the Power Supply Unit
and the Sealed Head Unit are serialized.
Bad spots in the Sealed Head Unit may be detected
and avoided in the future. Such bad spots should
be logged in a Flow Map positioned in an envelope
on top of the Sealed Head Unit this providing the
field history of the item.
6.3.3.2.2 S̲M̲D̲ ̲-̲ ̲C̲D̲C̲
Configuration control for the SMD follow the same procedures
as those described for the MMD (section 6.4.3.1).
The Equipment Identification Label is found on the
left side of the Deck Assembly, and the Field Change
Order Log is found on the side of the Logic Chassis
Assembly.
6.3.3.2.3 F̲l̲o̲p̲p̲y̲ ̲D̲i̲s̲k̲,̲ ̲S̲h̲u̲g̲a̲r̲t̲ ̲M̲o̲d̲e̲l̲ ̲S̲A̲ ̲8̲0̲1̲
a) Units are identified by Model No. and Serial No.
found on the buttom base right hand side.
b) Revision Level for the PCB is given on the Model
Log Control plate indicated by a digit being punched
out.
c) Field Changes are issued as Engineering Change
(EC).
6.3.3.3.4 V̲D̲U̲,̲ ̲D̲e̲l̲t̲a̲ ̲D̲a̲t̲a̲,̲ ̲M̲o̲d̲e̲l̲ ̲7̲2̲6̲0̲T̲C̲
a) Units are identified by Type and Serial Nos. found
at the rear of the unit.
b) Modules and subassemblies are identified by Type
Nos., Version Codes, and Revision Codes. E.g. the
PMM module, Version 2, Revison 1 is provided with
the following identification code:
7̲8̲5̲ A̲3̲0̲2̲ 4̲0̲2̲ R̲e̲v̲.̲ ̲1̲ ̲
Group Code (module) …0e… ̲ ̲ ̲…0f…
Product Code …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
Version Code …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
Revision Code …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
c) Firmware is identified separately by labels on
the ICs. E.g.
D̲E̲L̲T̲A̲ ̲D̲A̲T̲A̲ ̲E̲-̲P̲R̲O̲M̲ ̲L̲A̲B̲E̲L̲I̲N̲G̲
H̲ 4̲1̲4̲ U̲0̲1̲ 8̲A̲
Revision Sublevel
Revision Level #
Prom Location
Program #
Type of Prom
C̲R̲ ̲E̲-̲P̲R̲O̲M̲ ̲L̲A̲B̲E̲L̲I̲N̲G̲
After updating each E-PROM is identified by a metalic
label containing the following information:
4̲1̲4̲ 0̲1̲ 8̲-̲1̲0̲
Revision Sublevel, Note 1
Revision Level #
Prom Location
Program #
Note 1. Conversion between D.D. and CR methods of sublevel
identification.
D.D. CR
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
A - 10
B - 11
C - 12
D - 13
Information of Promtype is omitted and must be retrieved
from the actual E-PROM itself.
Letter U in PROM location is substitued by a space:
d) Field Changes are issued as Revision Notices. Upon
completion of the modification, the alphanumeric
revision code must be scratched out and replaced
by the next number in succession. Detailed information
will appear from the Revision Notice.
6.3.3.2.5 F̲r̲e̲q̲u̲e̲n̲c̲y̲ ̲S̲t̲a̲b̲i̲l̲i̲z̲e̲r̲,̲ ̲A̲b̲a̲c̲u̲s̲,̲ ̲M̲o̲d̲e̲l̲ ̲1̲1̲5̲2̲-̲3̲
a) Units are identified by Part No. and Serial No.
found at the rear of the unit.
b) Modules are identified by a 5-digit part number
either printed on the PCB or marked on a label.
E.g.
ABACUS CONTROLS 20990 DRIVER MODULE
is found on the PCB.
c) Field Changes are issued as Engineering Change
Notices (ECN).
6.3.3.2.6 S̲t̲a̲t̲i̲s̲t̲i̲c̲a̲l̲ ̲M̲u̲l̲t̲i̲p̲l̲e̲x̲e̲r̲,̲ ̲M̲i̲c̲o̲m̲,̲ ̲M̲i̲c̲r̲o̲ ̲8̲2̲8̲/̲2̲.̲
a) Units are identified by Model No. and Serial No.
found inside to the left behind the fuse panel.
b) Modules are identified by Part No. and Serial No.
Revision Levels are identified by a Letter.
c) Firmware is identified by a 8-digit number marked
on a label e.g.
901-850-04
the last two digits being revision level.
d) Field Changes are issued as Engineering Changes
(EC).
6.3.3.2.7 M̲o̲d̲e̲m̲,̲ ̲R̲a̲c̲a̲l̲-̲M̲i̲l̲g̲o̲,̲ ̲M̲P̲S̲1̲2̲2̲3̲
a) Units are identified by type, revision and Serial
No. found at the rear left side of the unit.
eg. 255A - FOIU 2074
Type
Revision
Serial No.
b) Modification status is given on the MOD-label to
the right of the identification label.
MOD O̲U̲D̲
Modification status
c) Firmware is identified by a 8-digit number marked
on a label e.g.
16000 - 054
the last three digits being revision level.
d) Field Changes are issued as Engineering Changes
(EC).
6.3.3.2.8 M̲S̲P̲ ̲-̲ ̲T̲R̲A̲C̲O̲R̲,̲ ̲M̲o̲d̲e̲l̲ ̲8̲0̲1̲
a) Units are identified by Type No. and Serial No.
found at the rear of the unit.
b) Modules and subassemblies are identified by Type
Nos., Version Codes, and Revision Levels. E.g.
the CPU module, Version 1, Revision C is provided
with the following identificaton code.
1̲9̲3̲9̲7̲/A̲S̲S̲Y̲ ̲1̲4̲6̲5̲7̲-0̲0̲0̲1̲ R̲e̲v̲.̲ ̲C̲
Product Code …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
Same for all modules
and subassys
Type No. (CPU Module) …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
Version Code …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
Revision Code …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
c) Firmware is separately identified by labels on
the ICs. E.g.
1̲4̲1̲5̲5̲6̲-0̲0̲1̲3̲ R̲e̲v̲.̲ ̲B̲
Type No. (PROM) …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
Version Code …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
Revision Code …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
d) Field Change Notices are issued as ECOs. Upon completion
of the modification, the revision letter must be
scratched out and replaced by the next letter in
succession. Detailed information will appear from
the ECO.
6.3.3.2.9 P̲T̲P̲/̲R̲,̲ ̲E̲E̲C̲O̲ ̲R̲P̲-̲9̲3̲6̲2̲
a) Units are identified by Model, partnumber, revision
level and Serial No, found inside on the right
side.
b) Modules are identified by part no. and revision
level.
c) Firmware is N/A.
d) Field Changes are issued as Engineering Changes
(EC).
6.3.3.2.10 R̲a̲c̲k̲s̲
a) Racks are only identified by serial no. found inside
in the bottom right side.