DataMuseum.dk

Presents historical artifacts from the history of:

CR80 Wang WCS documentation floppies

This is an automatic "excavation" of a thematic subset of
artifacts from Datamuseum.dk's BitArchive.

See our Wiki for more about CR80 Wang WCS documentation floppies

Excavated with: AutoArchaeologist - Free & Open Source Software.


top - download

⟦41160d206⟧ Wang Wps File

    Length: 60799 (0xed7f)
    Types: Wang Wps File
    Notes: CPS/TCM/005 (Sec. 5 + 6)  
    Names: »1698A «

Derivation

└─⟦3fbecbc6f⟧ Bits:30006206 8" Wang WCS floppy, CR 0307A
    └─ ⟦this⟧ »1698A « 

WangText

'…00……00…'…02…'
…00……00…' '…06…&…09…&…0b…&…0f……1b……01……1b… …1b……06……1a……0c……1a……0e……14……01……14…
…14……06……13……08……13……0a……13……0c……13……0e……13……00……13……02……13… …13……07……12……09……12……0b……12……0d……12……0f……12……01……12… …12……06……11……08……11……0a……11……0c……11……0e……11…
…11……05……11……06……10……08……10……0c……10……0e……10……00……10……02……10… …0f……08……86…1         …02…   …02…   …02…   …02…                                           


 
    1698A/ktd …02…CPS/TCM/005

…02…KJA/830912…02…  …02…      CAMPS SITE LEVEL MAINTENANCE MANUAL  
…02…Issue 1…02… CAMPS








* * * * * * * * * * *                         
*   OUTLET  CR2510  *                         
* * * * * * * * * * *                


















































                      Figure 4.5.4-5
                      OUTLET CR 2510


* * * * * * * * * * *                         
*   OUTLET  CR2510  *                         
* * * * * * * * * * *                


C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

                    No controls and indicators on the module

 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲


                            Table 4.5.4-5



M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

     No module identification necessary.


* * * * * * * * * * * * * * *                   Idle indication/
*   POWER SUPPLY  CR8022S   *                   normal position
* * * * * * * * * * * * * * *        


















































                      Figure 4.5.4-6
                  POWER SUPPLY CR 8022S


* * * * * * * * * * * * * * *           
*   POWER SUPPLY  CR8022S   *           
* * * * * * * * * * * * * * *        


C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

+5V                 Indicates that +5V DC power is available at
(green)             the output of the POWER SUPPLY module.

+12V                Indicates that +12V DC power is available at 
(green)             the output of the POWER SUPPLY module.

-12V                Indicates that -12V DC power is available at 
(green)             the output of the POWER SUPPLY module.

FUSE                This fuse protects the +12V DC and -12V DC 
0.63A               POWER SUPPLY.

FUSE                This fuse protects the +5V DC POWER SUPPLY.
3.15A

 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲


                            Table 4.5.4-6



M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

     No module identification necessary.


* * * * * * * * * * * * *                    
*   TDX CRATE CR1081S   *                    
* * * * * * * * * * * * *            


















































                      Figure 4.5.4-7
                    TDX CRATE CR 1081S


* * * * * * * * * * * * *                   
*   TDX CRATE CR1081S   *                   
* * * * * * * * * * * * *            


C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

                    No controls and indicators

 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲


                            Table 4.5.4-7



C̲r̲a̲t̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

         No crate identification necessary.


* * * * * * * * * * * * *                       Idle indication/
*   TDX CTRL  CR1070S   *                       normal position
* * * * * * * * * * * * *            


















































                      Figure 4.5.4-8
                    TDX CTRL CR 1070S


* * * * * * * * * * * * *                    
*   TDX CTRL  CR1070S   *                    
* * * * * * * * * * * * *            


C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

POWER               Indicates that DC power is applied to the 
(green)             module.

TEST                Indicates that an error is detected by the
(red)               built-in-test routine. The TEST LED will always light
                    for a few seconds upon masterclear, since it is on
                    during the built-in-test routine.

REC ST              Indicates that the module has selected upper
(yellow)            bus 1.

TR.ST               Indicates that an error has been detected in 
(red)               the TRANSMIT code

FUSE                Indicates that the fuse is opened.
(red)

 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲


                            Table 4.5.4-8



M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

                 TDX Ctrl., slot 1
                 (only TU1 and TU4): No identification necessary.



S̲t̲r̲a̲p̲s̲ ̲S̲e̲t̲t̲i̲n̲g̲s̲.

    SR       2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲5̲ ̲ ̲ ̲6̲ ̲ ̲ ̲7̲ ̲ ̲ ̲8̲ ̲ ̲ ̲9̲ ̲ ̲ ̲1̲0̲ ̲ ̲1̲1̲ ̲ ̲1̲2̲
             ̲
             A   B   B   C   B   B   C   B   B   A   A   


             1̲3̲ ̲ ̲1̲4̲ ̲ ̲1̲5̲ ̲ ̲1̲6̲ ̲ ̲1̲7̲ ̲ ̲1̲8̲ ̲ ̲1̲9̲
             B   B   A   A   B   B   B


* * * * * * * * * *                             Idle indication/
*   TSP CR1103S   *                             normal position
* * * * * * * * * *                  


















































                      Figure 4.5.4-9
                       TSP CR 1103S


* * * * * * * * * *                           
*   TSP CR1103S   *                           
* * * * * * * * * *                  


C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲


                    No controls and indicators on the module.

 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲


                            Table 4.5.4-9



M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

     (Rear of crate) No module identification necessary



* * * * * * * * * *                           
*   BACK PANEL    *                           
* * * * * * * * * *                  


















































                   Figure 4.5.5-1a
                   BACK PANEL (BP)


* * * * * * * * * *                           
*   BACK PANEL    *                           
* * * * * * * * * *                  


C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

                    No controls and indicators on the module 
       
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲


                            Table 4.5.5-1



M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

     No module identification necessary.


     S̲t̲r̲a̲p̲s̲e̲t̲t̲i̲n̲g̲s̲:̲



* * * * * * * * * *                           
*   BACK PANEL    *                           
* * * * * * * * * *                  


















































                   Figure 4.5.5-1b
                 BP #1 ADAPTOR CRATE


* * * * * * * * * *                           
*   BACK PANEL    *                           
* * * * * * * * * *                  

















































                   Figure 4.5.5-1c
             BP #2 CODING …01…ADAPTOR CRATE


* * * * * * * * * *                           
*   BACK PANEL    *                           
* * * * * * * * * *                  

















































                   Figure 4.5.5-1d
            LTUX-S - STAT.MUX.1…01…INTERFACE



* * * * * * * * * *                           
*   BACK PANEL    *                           
* * * * * * * * * *                  















































                   Figure 4.5.5-1e
                BP#1 REMOTE TERMINALS
             STAT MUX - OPTO T/R…01…INTERFACE


* * * * * * * * * *                           
*   BACK PANEL    *                           
* * * * * * * * * *                  

















































                   Figure 4.5.5-1f
        CODING BP#2 REMOTE TERMINALS STAT MUX
                - OCR AND LSM INTERFACE




* * * * * * * * * * * * * * * *                 Idle indication/
*   L/L ADAPTER  4 CHANNELS   *                 normal position
* * * * * * * * * * * * * * * *      


















































                   Figure 4.5.5-1g
             BP#1 OPTIONAL ADAPTOR CRATE


* * * * * * * * * * * * * * * *          
*   L/L ADAPTOR  4 CHANNELS   *          Idle indication/
* * * * * * * * * * * * * * * *        normal position
















































                     Figure 4.5.5-2a
                  L/L ADAPTOR 4 CHANNELS


* * * * * * * * * * * * * * * *          
*   L/L ADAPTOR  4 CHANNELS   *          
* * * * * * * * * * * * * * * *      


C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

POWER               Indicates that DC power is applied to the
(green)             module.

 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲


                            Table 4.5.5-2



M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

     No address identification.


* * * * * * * * * * * * * * *                 
* L/L ADAPTER  4 CHANNELS   *                          
  
* * * * * * * * * * * * * * *        


















































                   Figure 4.5.5-2b
          L/L ADAPTOR LTUX-S/PTP/R INTERFACE



* * * * * * * * * * * * * * *                 
* L/L ADAPTER  4 CHANNELS   *                          
 
* * * * * * * * * * * * * * *        


















































                   Figure 4.5.5-2c
   L/L ADAPTOR LTUX-S-TRC/POINT TO POINT INTERFACE



* * * * * * * * * * * * * * *                 
* L/L ADAPTOR   4 CHANNELS  *                          
 
* * * * * * * * * * * * * * *        


















































                   Figure 4.5.5-2d
             L/L ADAPTOR REMOTE TERMINAL
               STATMUX - OCR INTERFACE


* * * * * * * * * * * * * * *                 
* L/L ADAPTOR 4 CHANNELS    *                          
  
* * * * * * * * * * * * * * *        

















































                   Figure 4.5.5-2e
             L/L ADAPTOR REMOTE TERMINALS
             STATMUX - VDU/MSP INTERFACE


* * * * * * * * * * * * * * *                   Idle indication/
*   L/L ADAPTOR 1 CHANNEL   *                   normal position
* * * * * * * * * * * * * * *        


















































                   Figure 4.5.5-3a
                L/L ADAPTOR 1 CHANNEL


* * * * * * * * * * * * * * *             
*   L/L ADAPTOR 1 CHANNEL   *             
* * * * * * * * * * * * * * *        


C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

POWER               Indicates that DC power is applied to the
(green)             module.

 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲


                            Table 4.5.5-3



M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

     No address identification.


* * * * * * * * * * * * * *                   
* L/L ADAPTOR  1 CHANNEL  *                            
 
* * * * * * * * * * * * * *          

















































                   Figure 4.5.5-3b
            L/L ADAPTOR LTU/SCARS II/ACCIS
                      INTERFACE


* * * * * * * * * * * * * * *                 
* L/L ADAPTER   1 CHANNEL   *                          
 
* * * * * * * * * * * * * * *        


















































                   Figure 4.5.5-3c
      L/L ADAPTOR LTU/COLLOCATED TARE INTERFACE



* * * * * * * * * * * * * * *                 
* L/L ADAPTER  1 CHANNEL    *                          
 
* * * * * * * * * * * * * * *        


















































                   Figure 4.5.5-3d
        L/L ADAPTOR LTU/REMOTE TARE INTERFACE



* * * * * * * * * * * * * *                   
* L/L ADAPTER  1 CHANNEL  *                            
 
* * * * * * * * * * * * * *          


















































                   Figure 4.5.5-3e
           L/L ADAPTOR LTUX-S/OCR INTERFACE



* * * * * * * *                       
* TARE MODEM  *                                  
* * * * * * * *               










































                    Figure 4.5.5-4
                      TARE MODEM


* * * * * * * *                       
* TARE MODEM  *                                  
* * * * * * * *               



C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

                    The controls and indicators of the modem 
                    is described in the Modem Operator Manual 
                    Doc.No. CPS/TCM/016 in the section designated
                    Controls and Indicators.
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲


                            Table 4.5.5-4

U̲N̲I̲T̲ ̲S̲W̲I̲T̲C̲H̲ ̲S̲E̲T̲T̲I̲N̲G̲S̲:̲

T̲A̲R̲E̲ ̲M̲O̲D̲E̲M̲

        BASIC MODULE

   W    1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲
        A    A    A    A    +    +

   SR   a̲ ̲ ̲ ̲ ̲b̲ ̲ ̲ ̲ ̲c̲ ̲ ̲ ̲ ̲d̲ ̲ ̲ ̲ ̲e̲ ̲ ̲ ̲ ̲f̲ ̲ ̲ ̲ ̲g̲ ̲ ̲ ̲ ̲h̲ ̲ ̲ ̲ ̲i̲ ̲ ̲ ̲ ̲j̲
        ̲ ̲ ̲ ̲k̲ ̲ ̲ ̲ ̲m̲ ̲ ̲ ̲n̲
        +    +    +    -    -    -    +    +    -    -    +    -   +

   SWA  1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲
        1    1    0    1    0    0    1

   SWB  1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲ ̲ ̲ ̲ ̲8̲
        1    1    0    0    0    0    0    1


   SWC  1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲
        1    0    1    0                       "1" = OFF

        U̲P̲P̲E̲R̲ ̲M̲O̲D̲U̲L̲E̲:

   SWA  1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲
        1    1    1    1    1    1    1

   SWA  1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲
        1    1    0    1    0    1    1


* * * * * * * *                       
* TARE MODEM  *                                  
* * * * * * * *               

   S̲Y̲N̲C̲ ̲A̲D̲A̲P̲T̲O̲R̲:

   W    1    2    3
         ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

        A    B    A


   SR   a    b    c    d
         ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

        -    -    -    -


        NOTE: During FAT SR d must be implemented (+)
        remove before shipping.









     (This page is intentionally left blank)




* * * * * * * * * * * * *                       Idle indication/
*   OPTO  T/R  CR80109  *                       normal position
* * * * * * * * * * * * *            


















































                   Figure 4.5.5-5a
                  OPTO T/R CR 80109


* * * * * * * * * * * * *                     
*   OPTO  T/R  CR80109  *                     
* * * * * * * * * * * * *            


C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

POWER               Indicates that DC power is applied to the
(green)             module.

RCVL                Indicates that a low level voltage signal is 
(red)               not being received.

RTS                 Indicates that a Request To Send (RTS) is being 
(yellow)            signalled.

CTS                 Indicates that a Clear To Send (CTS) is being 
(yellow)            signalled.

SYNC                Indicates that a Synchronization signal is
(red)               not being received.

 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲


                            Table 4.5.5-5



M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

     No identification necessary.


* * * * * * * * * * * * *                              
         
*   OPTO  T/R  CR80109  *                              
        
* * * * * * * * * * * * *            

















































                   Figure 4.5.5-5b
            OPTO WDP/VDU AND MSP INTERFACE
                    ADAPTOR CRATE


* * * * * * * * * * * * *                              
         
*   OPTO  T/R  CR80109  *                              
        
* * * * * * * * * * * * *            

















































                   Figure 4.5.5-5c
       OPTO REMOTE TERMINALS STAT MUX - VDU/MSP
                      INTERFACE


* * * * * * * * * * * * *                              
         
*   OPTO  T/R  CR80109  *                              
        
* * * * * * * * * * * * *            





















       




























                   Figure 4.5.5-5d
           OPTO LTUX-S - VDU/MSP INTERFACE



* * * * * * * * *                                      
         
*   OPTO  MSP   *
* * * * * * * * *                    


















































                     Figure 4.5.5-6a
                         OPTO MSP


* * * * * * * * *                                      
         
*   OPTO  MSP   *
* * * * * * * * *                    


C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

POWER               Indicates that DC power is applied to the
(green)             module.

RCVL                Indicates that a low level voltage signal is 
(red)               not being received.

RTS                 Indicates that a Request To Send (RTS) is being 
(yellow)            signalled.

CTS                 Indicates that a Clear To Send (CTS) is being 
(yellow)            signalled.

SYNC                Indicates that a Synchronization signal is
(red)               not being received.

 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲


                            Table 4.5.5-6



M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

     No identification necessary.


* * * * * * * * *                                      
         
*   OPTO  MSP   *
* * * * * * * * *                    


S̲t̲r̲a̲p̲s̲e̲t̲t̲i̲n̲g̲s̲ ̲i̲n̲ ̲O̲P̲T̲O̲ ̲m̲o̲d̲u̲l̲e̲ ̲(̲O̲M̲3̲)̲:̲















































                     Figure 4.5.5-6b
                  OPTO MSP Strapsettings













         (This page is intentionally left blank)


* * * * * * * * *                                          
     
*   OPTO  VDU   *
* * * * * * * * *                    


















































                     Figure 4.5.5-7a
                         OPTO VDU


* * * * * * * * *                                      
         
*   OPTO VDU    *
* * * * * * * * *                    


C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

POWER               Indicates that DC power is applied to the
(green)             module.

RCVL                Indicates that a low level voltage signal is 
(red)               not being received.

RTS                 Indicates that a Request To Send (RTS) is being 
(yellow)            signalled.

CTS                 Indicates that a Clear To Send (CTS) is being 
(yellow)            signalled.

SYNC                Indicates that a Synchronization signal is
(red)               not being received.

 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲


                            Table 4.5.5-7



M̲o̲d̲u̲l̲e̲ ̲A̲d̲d̲r̲e̲s̲s̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

     No identification necessary.


* * * * * * * * *                                      
         
*   OPTO VDU    *
* * * * * * * * *                    


S̲t̲r̲a̲p̲s̲ ̲s̲e̲t̲t̲i̲n̲g̲s̲ ̲i̲n̲ ̲O̲P̲T̲O̲ ̲m̲o̲d̲u̲l̲e̲ ̲(̲O̲M̲1̲)̲ ̲M̲a̲i̲n̲ ̲S̲i̲t̲e̲















































                     Figure 4.5.5-7b
                    OPTO VDU MAIN SITE


* * * * * * * * *                                          
     
*   OPTO VDU    *
* * * * * * * * *                    


S̲t̲r̲a̲p̲s̲ ̲s̲e̲t̲t̲i̲n̲g̲s̲ ̲i̲n̲ ̲O̲P̲T̲O̲ ̲m̲o̲d̲u̲l̲e̲ ̲(̲O̲M̲1̲)̲ ̲R̲e̲m̲o̲t̲e̲ ̲S̲i̲t̲e̲















































                     Figure 4.5.5-7c
                   OPTO VDU REMOTE SITE


* * * * * * * * * * * * * * *                              
     
*  STATISTICAL MULTIPLEXER  *                              
         
* * * * * * * * * * * * * * *

         FRONT VIEW
















































                      Figure 4.5.5-8
                 STATISTICAL MULTIPLEXER


* * * * * * * * * * * * * *           
* STATISTICAL MULTIPLEXER *                   
* * * * * * * * * * * * * *   



C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

                    The controls and indicators of the statistical 
                    multiplexer is described in the STAT.MUX. 
                    User's Manual Doc.No. CPS/TPN/008 Sec. 4.1   
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

                            Table 4.5.5-8

U̲n̲i̲t̲ ̲S̲w̲i̲t̲c̲h̲ ̲S̲e̲t̲t̲i̲n̲g̲s̲:̲        

S̲T̲A̲T̲M̲U̲X̲ ̲(̲M̲A̲I̲N̲ ̲S̲I̲T̲E̲:̲

        B̲A̲S̲I̲C̲ ̲B̲O̲A̲R̲D̲:

   S1   1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲ ̲ ̲ ̲ ̲8̲ ̲ ̲
        1    0    0    1    1    1    0    0


   S2   1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲ ̲ ̲ ̲ ̲8̲ ̲ ̲
        1    0    1    1    1    1    1    1


   S3   1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲ ̲ ̲ ̲ ̲8̲ ̲ ̲
        1    1    0    0    1    1    0    0


   S4   1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲ ̲ ̲ ̲ ̲8̲ ̲ ̲
        1    1    0    0    1    1    0    0

        U̲P̲P̲E̲R̲ ̲B̲O̲A̲R̲D̲:

   S1   1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲ ̲ ̲ ̲ ̲8̲ ̲ ̲
        1    1    0    0    1    1    0    0


   S2   1̲ ̲ ̲ ̲ ̲2̲ ̲ ̲ ̲ ̲3̲ ̲ ̲ ̲ ̲4̲ ̲ ̲ ̲ ̲5̲ ̲ ̲ ̲ ̲6̲ ̲ ̲ ̲ ̲7̲ ̲ ̲ ̲ ̲8̲ ̲ ̲
        1    1    0    0    1    1    0    0
                                                "1" =
                                                OPEN


* * * * * * * * * * * * * *           
* STATISTICAL MULTIPLEXER *                   
* * * * * * * * * * * * * *   


S̲w̲i̲t̲c̲h̲ ̲S̲e̲t̲t̲i̲n̲g̲s̲:̲        

S̲T̲A̲T̲M̲U̲X̲ ̲(̲R̲E̲M̲O̲T̲E̲ ̲S̲I̲T̲E̲)̲

             B̲A̲S̲I̲C̲ ̲B̲O̲A̲R̲D̲:

         S1  1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲5̲ ̲ ̲ ̲6̲ ̲ ̲ ̲7̲ ̲ ̲ ̲8̲ ̲ ̲
             1   1   0   1   1   1   1   1


         S2  1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲5̲ ̲ ̲ ̲6̲ ̲ ̲ ̲7̲ ̲ ̲ ̲8̲ ̲ ̲
             1   0   1   1   1   1   1   1


         S3  1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲5̲ ̲ ̲ ̲6̲ ̲ ̲ ̲7̲ ̲ ̲ ̲8̲ ̲
             1   1   1   1   1   1   1   1


         S4  1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲5̲ ̲ ̲ ̲6̲ ̲ ̲ ̲7̲ ̲ ̲ ̲8̲ ̲
             1   1   1   1   1   1   1   1

             U̲P̲P̲E̲R̲ ̲B̲O̲A̲R̲D̲:

         S1  1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲5̲ ̲ ̲ ̲6̲ ̲ ̲ ̲7̲ ̲ ̲ ̲8̲ ̲
             1   1   1   1   1   1   1   1


         S2  1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲5̲ ̲ ̲ ̲6̲ ̲ ̲ ̲7̲ ̲ ̲ ̲8̲ ̲
             1   1   1   1   1   1   1   1
                                             "1" = OPEN













         (This page is intentionally left blank)



* * * * * * * * *                     
* MAINS SWITCH  *
* * * * * * * * *    


















































                      Figure 4.5.6-1
                       MAINS SWITCH


* * * * * * * * *                     
* MAINS SWITCH  *
* * * * * * * * *    



C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

MAINS SWITCH        This indicator illuminates to indicate that    
ON/OFF              there is an output of the mainswitch      
(LED)                                                            

MAINS SWITCH        This switch controls the AC power output
ON/OFF              of the Mains Switch unit
(SWITCH)
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

                            Table 4.5.6-1


* * * * * * * * * * *                 
* DELTA DATA, VDU   *
* * * * * * * * * * *  


















































                     Figure 4.5.7-1a
                     DELTA DATA, VDU


* * * * * * * * * * *                 
* DELTA DATA, VDU   *
* * * * * * * * * * *  


         To access the OPTION Menu

             a.  Hit the MON key.
             b.  Move the cursor to the entry, OPTION.
             c.  Hit the ENTER key.

         The screen now displays the OPTION menu as shown:









































                     Figure 4.5.7-1b
                     VDU OPTION MENU



* * * * * * * * * * *                 
* DELTA DATA, VDU   *
* * * * * * * * * * *                  


         To access the SPLIT menu

             a.  Hit the MON key.
             b.  Move the cursor to the entry, SPLIT.
             c.  Hit the ENTER key.

         The screen now displays the SPLIT menu as shown:









































                     Figure 4.5.7-1c
                     VDU, SPLIT MENU


* * * * * * * * * * *                 
* DELTA DATA, VDU   *
* * * * * * * * * * *                  


         To access the CONFIGURATION menu

             a.  Hit the MON key.
             b.  Move the cursor to the entry, CONFIGURATION.
             c.  Hit the ENTER key.

         The screen now displays the CONFIGURATION menu as shown:








































                     Figure 4.5.7-1d
                 MAINTENANCE POSITION VDU
                    CONFIGURATION MENU


* * * * * * * * * * *                 
* DELTA DATA, VDU   *
* * * * * * * * * * *                  


         To access the CONFIGURATION menu

             a.  Hit the MON key.
             b.  Move the cursor to the entry, CONFIGURATION.
             c.  Hit the ENTER key.

         The screen now displays the CONFIGURATION menu as shown:








































                     Figure 4.5.7-1e
                       OPERATOR VDU
                    CONFIGURATION MENU


* * * * * * * * * * *                 
* DELTA DATA, VDU   *
* * * * * * * * * * *                  



C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

BRIGHT              Adjusts the intensity of the characters        
                    displayed on the screen.                 

FOCUS               Adjusts the focus of the characters displayed
                    on the screen.

BELL                Changes the autio level of the bell.

POWER               This switch controls the power of the VDU.
(switch)

FUSE                (Rear of VDU) This fuse opens if the current to the
                    VDU exceeds 2 amp.

KEY-LOCK            Prevents using of the VDU by unauthorized
(switch)            persons.
                    Key-lock must be in the ON position for the VDU to
                    operate.

 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

                            Table 4.5.7-1


* * * * * * * * * * *                 
*   TRACOR, MSP     *
* * * * * * * * * * *  


















































                      Figure 4.5.8-1
                MEDIUM SPEED PRINTER, MSP


* * * * * * * * * * *                 
*   TRACOR, MSP     *
* * * * * * * * * * *  


C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

PAPER OUT           Indicates that the page printer paper supply is depleted.

EOF                 Indicates five characters prior to the end of a line.

PWR                 Indicates that power is applied to the equipment.

ALARM               Sounds upon receipt of a precedence message
(audible indic)     header or five characters before the end of a line.

AUDIO LEVEL         Varies the sound level output of the audio
(control)           alarm.

PARITY ERROR        Indicates a received parity error is detected. (push
                    button) may clear the error indication.

LINE FEED           Push button. Causes the page printer to feed paper.

FORM FEED           Push button. Causes the page printer to advance paper
                    to the top of the next form.

TEST                Push button. Momentary depression causes lamp test.
                    Push button. Continued depression 5 seconds or longer
                    initiates system self-test.

SUSP PRINT          (push button) Changed printer line status.
                    (indicator) Printing is suspended.

KEY-LOCK            Prevents printing by unauthorized persons.
(switch)            Key-lock must be in the ON positon for the printer
                    to operate.

 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲


                            Table 4.5.8-1



* * * * * * * * * * *                 
*   TRACOR, MSP     *
* * * * * * * * * * *  

M̲S̲P̲ ̲I̲N̲T̲E̲R̲N̲A̲L̲ ̲S̲T̲R̲A̲P̲S̲E̲T̲T̲I̲N̲G̲

    A̲ ̲1̲0̲:̲ Signal Interface Card.


         S1  1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲5̲ ̲ ̲ ̲6̲ ̲ ̲ ̲7̲ ̲
             1   0   0   0   0   0   0


         S2  1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲5̲ ̲ ̲ ̲6̲ ̲ ̲ ̲7̲ ̲
             1   1   1   1   1   0   1           "1" = OPEN


         A̲ ̲2̲: CPU Card
                                     BAUD RATE:

         S1  1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲       S1  1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲ ̲ ̲ ̲B̲R̲
             0   1   0   1           1   0   1   0   110
                                     0   1   1   0   150
                  "1" = ON           1   1   1   0   300
                                     0   0   0   1   600
                                     1   0   0   1   1200
                                     0̲ ̲ ̲ ̲1̲ ̲ ̲ ̲0̲ ̲ ̲ ̲1̲ ̲ ̲ ̲2̲4̲0̲0̲

         A̲ ̲7̲:̲    Printer Interface Card

         S1  1̲ ̲ ̲ ̲2̲ ̲ ̲ ̲3̲ ̲ ̲ ̲4̲   
             0   1   1   0                       "l" = ON


   * * * * * *              
   *  PTP/R  *              
   * * * * * *                


















































                     Figure 4.5.9-1a
       PAPER TAPE PUNCHER/PAPER TAPE READER,PTP/PTR


   * * * * * *              
   *  PTP/R  *              
   * * * * * *                

C̲O̲N̲T̲R̲O̲L̲/̲I̲N̲D̲I̲C̲A̲T̲O̲R̲ ̲ ̲ ̲ ̲ ̲F̲U̲N̲C̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲


PAPER ON/OFF SWITCH Applies 115 VAC Power to both the reader and punch
                    circuits.

POWER ON LED        Indicates reader/punch circuits energized.

     Switch         Momentary Switch to control tape direction.

RUN/LOAD Switch     RUN for normal reading operation. 
                    LOAD to inhibit reader stopping for tape loading, data
                    outputs remain active.

LDR Switch          Pushbutton switch to produce a tape leader with sprocket
                    holes. The punch operational the 60 characters per
                    second rate in the forward direction.

TAPE STATUS LED     Indicates a tape handling problem in the punch only.
                    The punch tape supply is exhausted or the tape is broken,
                    loose or too taut.

REWIND Switch       Controls rewind post to rewind short strips of tape.

 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲


                            Table 4.5.9-1


   * * * * * *              
   *  PTP/R  *              
   * * * * * *                


         P̲T̲P̲/̲R̲ ̲I̲N̲T̲E̲R̲N̲A̲L̲ ̲S̲T̲R̲A̲P̲S̲ ̲S̲E̲T̲T̲I̲N̲G̲:̲


         Reader  PCB:

         S1   ̲ ̲1̲^̲ ̲2̲^̲ ̲3̲^̲ ̲4̲
             OFF^ON^ON^ON


         Puncher PCB:

             Thumbwheel switch:  5

         A̲R̲C̲ ̲V̲1̲1̲/̲V̲2̲8̲ ̲A̲D̲A̲P̲T̲O̲R̲ ̲C̲A̲R̲D̲ ̲ (rear of PTP/R)


   ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ 
 ^     ^3/ ^4/ ^5/ ^6/ ^8/ ^4/ ^5/ ^6/ ^4/ ^6/ ^4/ ^6/ ^4/ ^6/
 ^
 ^ ̲S̲R̲ ̲ ̲^̲ ̲ ̲1̲^̲ ̲ ̲1̲^̲ ̲ ̲1̲^̲ ̲ ̲1̲^̲ ̲ ̲1̲^̲ ̲ ̲2̲^̲ ̲ ̲2̲^̲ ̲ ̲2̲^̲ ̲ ̲3̲^̲ ̲ ̲3̲^̲ ̲ ̲4̲^̲ ̲ ̲4̲^̲ ̲ ̲5̲^̲
 ̲ ̲5̲^
 ^     ^   ^   ^   ^   ^   ^   ^   ^   ^   ^   ^   ^   ^   ^
   ^
 ^ Pos.^ B ^ A ^ B ^ B ^ B ^ B ^ C ^ B ^ C ^ A ^ B ^ C ^ B ^
 B ^
 ^ ̲ ̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲ ̲ ̲ ̲^̲
 ̲ ̲ ̲^
                                      (shown in figure 4.5.9-1b)



* * * * * *              
*  PTP/R  *              
* * * * * *                


















































                     Figure 4.5.9-1b
                PTP/R ARC Straps Settings


              5  S̲/̲W̲ ̲M̲A̲I̲N̲T̲E̲N̲A̲N̲C̲E̲ ̲P̲R̲O̲C̲E̲D̲U̲R̲E̲S̲



5.1      I̲N̲T̲R̲O̲D̲U̲C̲T̲I̲O̲N̲

         The maintenance procedures can be defined in 3 main
         levels:

         1)  Detecting an error

         2)  Reporting and registration of the error

         3)  Performing S/W modifications

         Modifications will be distributed from the CSSI to
         any CAMPS site where the RST will perform the installation
         (see 5.3). The following types of S/W modifications
         are identified:

         a)  System S/W

         b)  Application S/W and

         c)  Patch files

         The S/W modifications are transported to CAMPS sites
         on applicable media (normally floppy disk).

         A step-by-step procedure describing S/W maintenance
         is shown in section 5.3.2.



5.2      R̲E̲P̲O̲R̲T̲I̲N̲G̲ ̲A̲N̲D̲ ̲R̲E̲G̲I̲S̲T̲R̲A̲T̲I̲O̲N̲

         A failure reporting- and registration system will be
         established in order to maintain the operation and
         overall performance of the system. By an analysis of
         the errors reported, it is possible to screen systematic
         failures and proper action may be taken to avoid unnecessary
         down-time. Prerequisites for failure reports from the
         sites are a properly maintained logbook and the error
         printouts appearing on the maintenance position line
         printer.



         a)  F̲a̲i̲l̲u̲r̲e̲ ̲R̲e̲p̲o̲r̲t̲s̲

             When a failure report is filled in at a site (see
             Figure 5.2-1), one copy is filed for information
             and two copies are sent to CSSI. When the problem
             is solved, the report is completed and one copy
             is filed at CSSI enclosed to the F̲ield C̲hange N̲otice
             (see Figure 6.3.2-1) and one copy is filed at CR.
             The failure report-file may be used in screening
             for systematic errors.

         b)  L̲o̲g̲b̲o̲o̲k̲

             The logbook (see Figure 6.1.1-1) must reflect the
             time span of any irregularity, the cause of it,
             what has been done within the time span to correct
             it, a signature, and a reconfiguration, if any.

             The logbook may be a reference document for a failure
             report to which a copy may be enclosed. Furthermore,
             the logbook must be accessible to CR to the extent
             necessary for systematic troubleshooting.

         c)  E̲r̲r̲o̲r̲ ̲P̲r̲i̲n̲t̲o̲u̲t̲s̲

             All events detected by the on-line diagnostics
             are logged on the maintenance position line printer
             (see Appendix A) with a time indication and an
             error information. If an automatic switchover is
             performed, this will also be indicated.

             As the error printouts are time information of
             the equipment status, it is mandatory that they
             are filed. The error printouts must be enclosed
             to the failure report. Those printouts must be
             accessible to CR to the extent necessary for a
             systematic troubleshooting.


























































                       Figure 5.2-1



5.3      P̲E̲R̲F̲O̲R̲M̲I̲N̲G̲ ̲S̲/̲W̲ ̲M̲O̲D̲I̲F̲I̲C̲A̲T̲I̲O̲N̲S̲

         Patchfiles, modified S/W as well as new S/W, is developed
         and tested at the CSSI site. On applicable media, the
         modifications together with the FCN are transported
         to CAMPS sites, where the S/W is installed by the RST,
         using the guidelines described in 5.3.1 and 5.3.2.



5.3.1    L̲o̲a̲d̲ ̲o̲f̲ ̲M̲o̲d̲i̲f̲i̲e̲d̲ ̲S̲/̲W̲

         The above mentioned types of S/W are loaded in the
         operational disks, using the commands and procedures
         described in CPS/OPM/005, section 5.6.4. The new S/W
         is loaded at the start-up time using the procedures
         shown in CPS/OPM/005, section 5.3.2.

         The FCN must contain sufficient information concerning:

         a)  Type of software   Modified system S/W 
                                Modified application S/W
                                Patchfiles and the number of
                                files

         b)  Type of media

         Information to be used in 5.3.2.




5.3.2    S̲t̲e̲p̲-̲b̲y̲-̲S̲t̲e̲p̲ ̲M̲a̲i̲n̲t̲e̲n̲a̲n̲c̲e̲

         S̲T̲E̲P̲  A̲C̲T̲I̲O̲N̲           R̲E̲M̲A̲R̲K̲S̲

          1    ERROR OCCUR      Error-report is written on the
                                maintenance position printer.
                                If error-report-id indicates
                                that a S/W error has occurred
                                (see Figure 4.3.2-1), go to
                                step 2, if not,

                                GO TO chapter 4.3.



          2    WRITE AND DIS-   The following must be enclosed:
               PATCH FAILURE
               REPORT TO CCSI   a) Printouts from maintenance
               SITE                position printer, such as
               WAIT FOR REPLY!     Log of commands
                                   Error-reports
                                   System status information

                                b) Copy of logbook

                                The failure report must be filled
                                in as adequate as possible.

                                GO TO step 3.



          3    FCN ENCLOSED     CSSI site will use applicable
               THE S/W          media to transport the 
               MODIFICATION     modification:
               IS RECEIVED
                                GO TO step 4



         S̲T̲E̲P̲  A̲C̲T̲I̲O̲N̲           R̲E̲M̲A̲R̲K̲S̲

          4    RST WILL LOAD    As mentioned in 5.3.1, the FCN
               MODIFIED S/W     will contain necessary information
                                concerning load and boot of
                                the modified S/W. 

                                LOAD OF MODIFIED SOFTWARE -
                                LMOS
                                where the following parameters
                                are taken from the FCN and used
                                LMOS-parameters: 

                                a) COPY MODE    From off-line
                                                disk
                                                From floppy
                                                disk

                                b) Type of S/W  Modified system
                                                S/W
                                                Modified application
                                                S/W
                                                Patchfiles

                                c) File number  If patchfiles,
                                                number of files

                                GO TO step 5



          5    BOOT OF          The commands mentioned in
               MODIFIED S/W     CPS/OPM/005 concerning start-up
                                procedures must be used with
                                the same parameters as in step
                                4a) to step 4b).

         …86…1         …02…   …02…   …02…   …02…                               
                    
5.3      N̲E̲W̲ ̲S̲/̲W̲ ̲L̲O̲A̲D̲I̲N̲G̲ ̲A̲N̲D̲ ̲V̲E̲R̲I̲F̲I̲C̲A̲T̲I̲O̲N̲

         TBD



5.4      M̲E̲M̲O̲R̲Y̲ ̲P̲U̲M̲P̲S̲

         TBD




5.5      F̲A̲I̲L̲U̲R̲E̲ ̲R̲E̲P̲O̲R̲T̲I̲N̲G̲

         TBD





               6  F̲A̲I̲L̲U̲R̲E̲ ̲R̲E̲P̲O̲R̲T̲I̲N̲G̲ ̲S̲Y̲S̲T̲E̲M̲



6.1      L̲O̲G̲B̲O̲O̲K̲

         A logbook will be issued to be used from the date of
         acceptance (PSA) of the equipment. In the logbook all
         deviations from the normal operation of the CAMPS site
         will be logged. Thus, the loghook must at all times
         reflect the status of the equipment and the place where
         the history record of the equipment is found. A copy
         of the logbook is to be enclosed with the failure report
         in case of an error.



6.1.1    L̲o̲g̲b̲o̲o̲k̲ ̲F̲o̲r̲m̲

         A logbook sheet is shown in fig. 6.1.1-1 and the use
         of the logbook is explained in the subparagraphs below.



6.1.1.1  H̲e̲a̲d̲i̲n̲g̲

         The date is written in this field. In case a day's
         events cannot be described on one page, subsequent
         pages may be added.



6.1.1.2  T̲i̲m̲e̲-̲O̲f̲-̲D̲a̲y̲

         The time to be filled in is the time when the event
         occurred, that is, the same time which appears on this
         printout at the maintenance position line printer.



6.1.1.3  S̲t̲a̲r̲t̲/̲S̲t̲o̲p̲ ̲T̲i̲m̲e̲

         The time when an action is commenced is writen in the
         start column; similarly, the time when the equipment
         is returned to normal operation or when action is terminated
         is written in the stop column.























































6.1.1.4  S̲y̲m̲p̲t̲o̲m̲

         A brief description of the event is written here.



6.1.1.5  A̲c̲t̲i̲o̲n̲ ̲G̲r̲o̲u̲p̲

         The Action Group column divides the events into different
         chategories. The following groups are defined

             A : Errors
             B : Preventive Maintenance
             C : Verification of repairs from depot
             D : Load of new S/W
             E : On-Job-Training
             F : Equipment Expansion
             G : Other Access to the equipment



6.1.1.6  A̲c̲t̲i̲o̲n̲

         A brief description of the actions performed is written
         here.



6.1.1.7  I̲n̲i̲t̲i̲a̲l̲s̲

         The originator must legibly write his name here.





6.2      F̲A̲I̲L̲U̲R̲E̲ ̲R̲E̲P̲O̲R̲T̲S̲

         Whenever a failing item is identified and returned
         to depot, a Failure Report must be issued as identification.
         The failure report will serve as a cover sheet for
         other enclosed documentation and ensure that all errors
         can be centrally registrated.

         It should be noticed that it is important to fill in
         the failure report accurately and detailed (if necessary,
         with enclosures) as this may ease the troubleshooting
         at the next level.

         During the warranty phase of the equipment, a record
         of all failure reports will be maintained by the manufacturer
         (CRAS), but each site should keep a copy for information.



6.2.1    F̲a̲i̲l̲u̲r̲e̲ ̲R̲e̲p̲o̲r̲t̲ ̲F̲o̲r̲m̲

         The Failure Report is shown in Figure 6.2.1-1 and the
         instructions for filling in the report are outlined
           below .



6.2.1.1  F̲a̲i̲l̲u̲r̲e̲ ̲R̲e̲p̲o̲r̲t̲ ̲N̲o̲.̲

         Each site (and depot) has been provided an identification
         No. which must be applied followed by a serial No.









               Her inds`ttes failure report




6.2.1.2  I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

         Sufficient informaton necessary for identification
         of the failing item must be provided. In case a H/W
         or a firmware error is reported, the following identification
         must be completed:

         -   Name of failing item
         -   Type No.
         -   Serial No. (if any)
         -   Revision No. (if any)

         In case a S/W error is reported, the following identification
         should be completed as applicable:

         -   Name of failing item (program, subroutine)
         -   Type No. (if any)
         -   Revision No. (if any)



6.2.1.3  P̲h̲y̲s̲i̲c̲a̲l̲ ̲L̲o̲c̲a̲t̲i̲o̲n̲

         Sufficient information for identification of the failing
         item and its position must be provided. Notice, that
         a failure in the main CAMPS equipment may be unequivocally
         identified by its identification code. Hence;

             1A1A1A4

         identifies the MAP module in slot 4 of the processor
         crate in rack A (ref. to CAMPS H/W Assembly Break-Down
         - CPS/SDS 0617-18).

         This part is not completed in case of a S/W error.



6.2.1.4  T̲y̲p̲e̲ ̲o̲f̲ ̲E̲r̲r̲o̲r̲

         The appropriate fields must be marked.





6.2.1.5  S̲i̲t̲e̲ ̲L̲e̲v̲e̲l̲ ̲I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

         The following information must be provided:

         a)  Sitename (abbreviation)
         b)  Originator's name 
         c)  Date of completion of the failure report



6.1.2.6  R̲e̲p̲a̲i̲r̲ ̲T̲i̲m̲e̲

         The following information should be provided:

         a)  Date-Of-Failure (DOF) and Time-Of-Day (TOD)

             The Time-Of-Day must be the same which appears
             in the Logbook. The date of failure is written
             in case the date is not the same as the date of
             the completion of the Failure Report above.

         b)  Repair Start

             Fill-in the TOD when the repair was initiated.

         c)  Repair Stop

             Fill-in the TOD when the repair was stopped.

         d)  Equipment Operation Restored

             Indicate TOD and day/month/year appropriate.

         e)  Elapsed Time

             If the equipment operation has been restored, this
             field will indicate the time for which the equipment
             was out of service. Notice that this is not necessarily
             indicated to the time spent on the repair of the
             fault.





6.2.1.7  E̲r̲r̲o̲r̲ ̲D̲e̲s̲c̲r̲i̲p̲t̲i̲o̲n̲

         Provide a brief, but thorough description of the failure
         indications. Support the descriptions with enclosure
         where necessary. Also describe the means which remedied
         the failure, if possible.



6.2.1.8  E̲n̲v̲i̲r̲o̲n̲m̲e̲n̲t̲a̲l̲ ̲C̲o̲n̲d̲i̲t̲i̲o̲n̲s̲

         If the environmental conditions were abnormal at the
         time of failure, it should be indicated in this field.



6.2.1.9  T̲y̲p̲e̲

         Indicate the process which was in progress at the timew
         of failure. Tasks like 

         -   Retrieval of date        (ROD)
         -   Preventive maintenance   (PM)
         -   Test of repaired modules (TEST)
         -   On the job training          (OJT)

         may be indicated in the "Other" field.



6.2.1.10 E̲n̲c̲l̲o̲s̲u̲r̲e̲

         Mark as appropriate. Enclose as much information as
         possible in order to ease fault finding at the next
         level.



6.3      C̲O̲N̲F̲I̲G̲U̲R̲A̲T̲I̲O̲N̲ ̲C̲O̲N̲T̲R̲O̲L̲



6.3.1    I̲n̲t̲r̲o̲d̲u̲c̲t̲i̲o̲n̲

         The CAMPS will be managed under a strict configuration
         control procedure. During the warrant period CR will
         be responsible for advising SHAPE of all changes that
         are to be made to the CAMPS hardware and software.
         After JFAI the responsibility will be retained by SHAPE.

         All instructions for modification or changes to the
         CAMPS will be issued by the SHAPE CAMPS System Direction
         and Support Office. These will be issued in the form
         of Field Change Notices (FCNs).

         Site Maintenance Personnel are not permitted to make
         any hardware or software changes unless instructed
         in a FCN.

         The site Configuration Management Inventory shows all
         the modules together with their serial number and revision
         level. Master records are held by CR and these will
         be transferred to SHAPE. As all items of hardware are
         exchanged through the depots the precise status of
         each site will be maintained with the depot (and Namsa)
         computer systems. SHAPE will have access to the system
         data base.…86…1         …02…   …02…   …02…   …02…                     
                              
6.3.2    F̲i̲e̲l̲d̲ ̲C̲h̲a̲n̲g̲e̲ ̲N̲o̲t̲i̲c̲e̲s̲ ̲(̲F̲C̲N̲)̲



6.3.2.1  G̲e̲n̲e̲r̲a̲l̲

         Whenever a modification is necessary, a Field Change
         Notice (FCN) will be issued and 2 copies will be provided
         to SHAPE and 1 copy to each site affected.

         The FCN will contain detailed information describing
         the:

         -   Type of information
         -   Tools, Parts, and time required
         -   Equipment to be modified
         -   Instructions for implementing the modifications

         Where the FCN indicates use of materials they will
         be enclosed.  If a modification necessitates amendment
         of documentation, new pages will be provided sufficient
         to amend all affected documentation.

         Generation of FCNs by CR will commence after the Site
         Provisional Acceptance and take place during the H/W
         or S/W warranty periods whichever is applicable.



6.3.2.2  R̲e̲g̲i̲s̲t̲r̲a̲t̲i̲o̲n̲ ̲o̲f̲ ̲F̲C̲N̲s̲

         A reference or Master List of all modifications will
         be issued and concurrently updated.  Herein the FCNs
         are listed consecutively indicating the equipment modified
         and the reason for modification.



6.3.2.3  D̲e̲s̲c̲r̲i̲p̲t̲i̲o̲n̲ ̲o̲f̲ ̲F̲C̲N̲s̲

         The field Change Notice Sheets shown overleaf are explained
         by the following subparagraphs (1-10).
         Refer to fig. 6.3.2-1 and -2.





6.3.2.4  H̲e̲a̲d̲i̲n̲g̲

         The FCNs are issued consecutively commencing with number
         1.  The number of pages included in the FCN in question
         is indicated.



6.3.2.5  I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

         The part addressed by the FCN is identified by Type,
         Parts No., NATO Stock no. if available, and description
         as well as the next higher level is indicated.



6.3.2.6  P̲a̲r̲t̲s̲ ̲D̲i̲s̲p̲o̲s̲i̲t̲i̲o̲n̲

         A checkmark indicates the disposition of parts, "N.A."
         means "Not Applicable".



6.3.2.7  C̲l̲a̲s̲s̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

         The checkmark indicates the urgency by which the modification
         must be executed.  "Desirable" means earliest convenient
         opportunity while "Mandatory" means immediately.  "Mandatory"
         classification is typically employed when the equipment
         may malfunction without the modification or if the
         operation of the system is endangered.



6.3.2.8  T̲y̲p̲e̲ ̲o̲f̲ ̲I̲n̲f̲o̲r̲m̲a̲t̲i̲o̲n̲

         This section is checked as appropriate.  The three
         main groups existing are:

         -   Rework (H/W change)
         -   Spares Change
         -   Software Change


















































                      Figure 6.3.2-1
             Field Change Notice, Front Page

















































                     Figure 6.3.2- 2
          Field Change Notice, Subsequent Pages


6.3.2.9  R̲e̲l̲a̲t̲e̲d̲ ̲I̲n̲f̲o̲r̲m̲a̲t̲i̲o̲n̲

         This section cross references related documents to
         the FCN.  Engineering Change Order (ECO) is the reference
         no. for a CR in-house document, while the Failure Report
         No. indicates that the FCN is originated by an error
         occurred at a site or depot.



6.3.2.10 Fi̲e̲l̲d̲ ̲C̲h̲a̲n̲g̲e̲ ̲D̲e̲s̲c̲r̲i̲p̲t̲i̲o̲n̲

         The description includes a reason for action that is,
         a brief explanation of why that particular FCN is necessary.
          It also describes the change in details or, if the
         space is insufficient, provides a summary of the modification.
          It is always described as "Is" and "Was".



6.3.2.11 A̲f̲f̲e̲c̲t̲e̲d̲ ̲D̲o̲c̲u̲m̲e̲n̲t̲s̲

         If a modification implies that the documentation is
         revised, the applicable documents are listed with the
         new revision level.  Also reference documents are mentioned,
         if any.



6.3.2.12 A̲p̲p̲r̲o̲v̲a̲l̲ ̲A̲u̲t̲h̲o̲r̲i̲t̲y̲

         The author of the FCN must sign together with the approval
         authorities and the RST which implemented the modification.
          Upon completion, a signed copy of the front page of
         the FCN must be returned to CR to indicate the status
         of the equipment.  The equipment is considered modified
         upon receipt of this copy.



6.3.2.13 S̲u̲c̲c̲e̲e̲d̲i̲n̲g̲ ̲P̲a̲g̲e̲s̲

         The succeeding pages provide the detailed information
         about the modification.  First the tools, parts, and
         time required for the modification is indicated, next
         step by step instructions illustrated as "Is" and "Was",
         if applicable.



6.3.3    I̲d̲e̲n̲t̲i̲f̲i̲c̲a̲t̲i̲o̲n̲ ̲o̲f̲ ̲M̲o̲d̲u̲l̲e̲ ̲R̲e̲v̲i̲s̲i̲o̲n̲ ̲L̲e̲v̲e̲l̲

         The following pages describes how the various assemblies
         are marked so that site personnal can identify the
         revision level of all assemblies.


6.3.3.1  C̲R̲A̲S̲ ̲M̲o̲d̲u̲l̲e̲s̲

         a)  Modules are identified as a product of type Nos.,
             Version Nos., Print Revisions, and Revision Levels.
             E.g., a specific LTUX module may be identifies
             as

             CRAS PART NO 4̲.̲0̲4̲1̲4̲1̲  0̲8̲ ̲ SER. NO. 3̲2̲8̲  Rev 2̲ -
             D̲

             Family Name …0e… ̲ ̲ ̲ ̲ ̲…0f…
             Version No. …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
             Module's Serial No. …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
             Print Version  …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
             Latest Revision  …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
             ̲ ̲ ̲…0f…

             where

             -   The PART NO, Version, and Serial No. are a
                 coherent identification which may be either
                 in the form of a metal label or directly etched
                 into the PCB. In the latter case, the version
                 and serial No. are handwritten directly on
                 the PCB.

                 The family name and version No. identifies
                 a module with respect to Form, Fit, and Function
                 (FFF). The FFF is established through a baseline
                 documentation.

             -   The serial No. refers to the production sequence.

             -   The print version No. is derived from the PCB
                 layout number. E.g. the LTUX module

                                    4̲7̲4̲ A̲ - 2̲

                 PCB Type No. …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
                 Side A of PCB …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
                 PCB Revision  …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…

                 The PCB revision will always remain the same
                 on both the A side and B side of the PCB.



             -   The Revision Level is a matrix which indicates
                 the ECO status of the board. E.g.

                  ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ 

                  A   B   D   E
                  ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

                 means that Revision A, B, and D have been implemented
                 while Revision C is N/A for this module. This
                 implies that in the first issue of the print
                 version the matrix is left blank.

                 Updates per revision level will not affect
                 Form, Fit, and Function.

                 The Revision Matrix may be found either as
                 a metal label or etched into the PCB.

         b)  Firmware is identified by CRAS Part No. and Version
             Code marked by a label on the top of the PROM.
             Any changes to the PROM will be indicated by an
             updated version code, but configuration control
             is to be maintained at module level. "Minor" changes
             will be reflected as new revision levels while
             major changes will cause a new module version.

         c)  Diagrams and Parts lists are issued as baseline
             documentation. New revisions will be relected as
             "pen and ink" changes until the revisions are incorporated
             in a new PCB version. At that time, a  new diagram
             and parts list will be issued.

         d)  Field Changes are issued as Field Changes Notices.
             Refer to section 6.3 for details.



6.3.3.2  P̲e̲r̲i̲p̲h̲e̲r̲a̲l̲s̲

         Peripherals and modules in the CAMPS program which
         are not being manufactured by CRAS, are generally controlled
         by commercial standards. This means that configuration
         control will be ensured by revision levels rather than
         by serial Nos. A brief description of each individual
         product is provided below.





6.3.3.2.1    M̲M̲D̲ ̲-̲ ̲C̲D̲C̲ ̲M̲o̲d̲e̲l̲ ̲9̲7̲3̲0̲

         a)  Units are identified by an Equipment Identification
             No. found on a label at the rear of the unit (see
             Figure 6.4.3.3-1.a). The Series Code indicates
             the revision baseline at system level, and the
             Equipment Identificaton No. and Series Code should
             always be provided with any technical requests.

         b)  Modules are identified by a 3-letter family code
             preceeded by a revision letter (or 2 rev. letters)
             (see Figure 6.4.3.3-1.b). The 4 letters correspond
             to an 8-digit Parts No. which is stamped upon the
             components side of the PCB. Any changes to a PCB
             will result in a new revision letter and subsequent
             new P/N.

         c)  Firmware is identified by an 8-digit part No. stamped
             upon the IC. A change will result in a new P/N,
             but also the revision letter and parts No. of the
             module will change.

         d)  An Equipment Configuration Log Sheet is provided
             in front of the Service Manual. All ECOs and reconfigurations
             to the equipment should be logged here to reflect
             the field history of the equipment.

         e)  Field Changes are issued as Field Change Orders
             (FCO). Upon completion of the modification, the
             revision letter and the parts No. must be scratched
             out and replaced by the numbers indicated in the
             FCO.

             When a modification is implemented, it must be
             recorded in a Field Change Order Log positioned
             beneath the PCB compartment.

             Also it must be logged in the Equipment Configuration
             Log Sheet placed as the first page of the Service
             Manual. In this way, the field history is preserved
             both in the equipment and in the documentation.







         Fig. a. Equipment Identification

                 ̲ ̲E̲Q̲U̲I̲P̲.̲I̲D̲E̲N̲T̲.̲N̲O̲.̲ ̲S̲E̲R̲I̲E̲S̲ ̲C̲O̲D̲E̲ ̲ ̲ ̲P̲A̲R̲T̲ ̲N̲O̲.̲ ̲ ̲S̲E̲R̲.̲N̲O̲.̲
                 ̲ ̲ ̲ ̲ ̲B̲Z̲ ̲5̲A̲ ̲5̲B̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲1̲3̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲7̲3̲0̲3̲6̲7̲0̲7̲ ̲ ̲ ̲1̲7̲1̲1̲
             ̲ ̲
         
         MMD Disk …0e…    …0f…
         80 MByte …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
         220/240V, 50Hz
         Single Channel …0e… ̲ ̲ ̲ ̲…0f…
         w/96 Fixed head
         Production Baseline …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
         Unit P/N …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
         Unit S/N …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
         ̲ ̲ ̲…0f…



         Fig. b

                                  H̲ F̲G̲X̲     7̲6̲9̲3̲ ̲5̲5̲0̲8̲

         Revision Level …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
         Family Code …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
         CDC P/N …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…




















                     Figure 6.4.3.1-1



         f)  Major subassemblies such as the Power Supply Unit
             and the Sealed Head Unit are serialized. 

             Bad spots in the Sealed Head Unit may be detected
             and avoided in the future. Such bad spots should
             be logged in a Flow Map positioned in an envelope
             on top of the Sealed Head Unit this providing the
             field history of the item.



6.3.3.2.2    S̲M̲D̲ ̲-̲ ̲C̲D̲C̲

         Configuration control for the SMD follow the same procedures
         as those described for the MMD (section 6.4.3.1).

         The Equipment Identification Label is found on the
         left side of the Deck Assembly, and the Field Change
         Order Log is found on the side of the Logic Chassis
         Assembly.



6.3.3.2.3    F̲l̲o̲p̲p̲y̲ ̲D̲i̲s̲k̲,̲ ̲S̲h̲u̲g̲a̲r̲t̲ ̲M̲o̲d̲e̲l̲ ̲S̲A̲ ̲8̲0̲1̲

         a)  Units are identified by Model No. and Serial No.
             found on the buttom base right hand side.

         b)  Revision Level for the PCB is given on the Model
             Log Control plate indicated by a digit being punched
             out.

         c)  Field Changes are issued as Engineering Change
             (EC).



6.3.3.3.4    V̲D̲U̲,̲ ̲D̲e̲l̲t̲a̲ ̲D̲a̲t̲a̲,̲ ̲M̲o̲d̲e̲l̲ ̲7̲2̲6̲0̲T̲C̲

         a)  Units are identified by Type and Serial Nos. found
             at the rear of the unit.

         b)  Modules and subassemblies are identified by Type
             Nos., Version Codes, and Revision Codes. E.g. the
             PMM module, Version 2, Revison 1 is provided with
             the following identification code:



                                  7̲8̲5̲ A̲3̲0̲2̲ 4̲0̲2̲ R̲e̲v̲.̲ ̲1̲ ̲

             Group Code (module) …0e… ̲ ̲ ̲…0f…
             Product Code …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
             Version Code …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
             Revision Code …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…

         c)  Firmware is identified separately by labels on
             the ICs. E.g.

                D̲E̲L̲T̲A̲ ̲D̲A̲T̲A̲ ̲E̲-̲P̲R̲O̲M̲ ̲L̲A̲B̲E̲L̲I̲N̲G̲



         H̲   4̲1̲4̲    U̲0̲1̲  8̲A̲


                                 Revision Sublevel
                                 Revision Level #
                                 Prom Location
                                 Program #
                                 Type of Prom


                    C̲R̲ ̲E̲-̲P̲R̲O̲M̲ ̲L̲A̲B̲E̲L̲I̲N̲G̲

         After updating each E-PROM is identified by a metalic
         label containing the following information:


         4̲1̲4̲        0̲1̲   8̲-̲1̲0̲


                                 Revision Sublevel, Note 1
                                 Revision Level #
                                 Prom Location
                                 Program #




         Note 1. Conversion between D.D. and CR methods of sublevel
         identification.


             D.D.        CR
          ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

             A           - 10
             B           - 11
             C           - 12
             D           - 13

         Information of Promtype is omitted and must be retrieved
         from the actual E-PROM itself. 

         Letter U in PROM location is substitued by a space:

         d)  Field Changes are issued as Revision Notices. Upon
             completion of the modification, the alphanumeric
             revision code must be scratched out and replaced
             by the next number in succession. Detailed information
             will appear from the Revision Notice.



6.3.3.2.5    F̲r̲e̲q̲u̲e̲n̲c̲y̲ ̲S̲t̲a̲b̲i̲l̲i̲z̲e̲r̲,̲ ̲A̲b̲a̲c̲u̲s̲,̲ ̲M̲o̲d̲e̲l̲ ̲1̲1̲5̲2̲-̲3̲

         a)  Units are identified by Part No. and Serial No.
             found at the rear of the unit.

         b)  Modules are identified by a 5-digit part number
             either printed on the PCB or marked on a label.
             E.g.

                    ABACUS CONTROLS 20990 DRIVER MODULE

             is found on the PCB.


         c)  Field Changes are issued as Engineering Change
             Notices (ECN).





6.3.3.2.6    S̲t̲a̲t̲i̲s̲t̲i̲c̲a̲l̲ ̲M̲u̲l̲t̲i̲p̲l̲e̲x̲e̲r̲,̲ ̲M̲i̲c̲o̲m̲,̲ ̲M̲i̲c̲r̲o̲ ̲8̲2̲8̲/̲2̲.̲

         a)  Units are identified by Model No. and Serial No.
             found inside to the left behind the fuse panel.

         b)  Modules are identified by Part No. and Serial No.
             Revision Levels are identified by a Letter.

         c)  Firmware is identified by a 8-digit number marked
             on a label e.g.

                     901-850-04

             the last two digits being revision level.

         d)  Field Changes are issued as Engineering Changes
             (EC).



6.3.3.2.7    M̲o̲d̲e̲m̲,̲ ̲R̲a̲c̲a̲l̲-̲M̲i̲l̲g̲o̲,̲ ̲M̲P̲S̲1̲2̲2̲3̲

         a)  Units are identified by type, revision and Serial
             No. found at the rear left side of the unit.

             eg.      255A   -    FOIU         2074

             Type
             Revision
             Serial No.

         b)  Modification status is given on the MOD-label to
             the right of the identification label.

                      MOD         O̲U̲D̲

             Modification status

         c)  Firmware is identified by a 8-digit number marked
             on a label e.g.

                      16000 - 054

             the last three digits being revision level.

         d)  Field Changes are issued as Engineering Changes
             (EC).





6.3.3.2.8    M̲S̲P̲ ̲-̲ ̲T̲R̲A̲C̲O̲R̲,̲ ̲M̲o̲d̲e̲l̲ ̲8̲0̲1̲

         a)  Units are identified by Type No. and Serial No.
             found at the rear of the unit.

         b)  Modules and subassemblies are identified by Type
             Nos., Version Codes, and Revision Levels. E.g.
             the CPU module, Version 1, Revision C is provided
             with the following identificaton code.

                                1̲9̲3̲9̲7̲/A̲S̲S̲Y̲ ̲1̲4̲6̲5̲7̲-0̲0̲0̲1̲ R̲e̲v̲.̲ ̲C̲

             Product Code …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
             Same for all modules
             and subassys
             Type No. (CPU Module) …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
             Version Code …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
             Revision Code …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…

         c)  Firmware is separately identified by labels on
             the ICs. E.g.

                                   1̲4̲1̲5̲5̲6̲-0̲0̲1̲3̲ R̲e̲v̲.̲ ̲B̲

             Type No. (PROM) …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
             Version Code …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…
             Revision Code …0e… ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…0f…

         d)  Field Change Notices are issued as ECOs. Upon completion
             of the modification, the revision letter must be
             scratched out and replaced by the next letter in
             succession. Detailed information will appear from
             the ECO.






6.3.3.2.9    P̲T̲P̲/̲R̲,̲ ̲E̲E̲C̲O̲ ̲R̲P̲-̲9̲3̲6̲2̲

         a)  Units are identified by Model, partnumber, revision
             level and Serial No, found inside on the right
             side.

         b)  Modules are identified by part no. and revision
             level.

         c)  Firmware is N/A.

         d)  Field Changes are issued as Engineering Changes
             (EC).



6.3.3.2.10   R̲a̲c̲k̲s̲

         a)  Racks are only identified by serial no. found inside
             in the bottom right side.