⟦51ac16819⟧ Wang Wps File

    Length: 22578 (0x5832)
    Types: Wang Wps File
    Notes: CPS/TCN/029               
    Names: »1260A «

Derivation

└─⟦2a70d8cf1⟧ Bits:30006046 8" Wang WCS floppy, CR 0073A
    └─ ⟦this⟧ »1260A « 

WangText

…10……00……00……00……00…>…02……00……00…>
=…0b…=…01…=…07…<…0d…<…00…<…86…1                                             …02…           …02…   …02…        

…02…CPS/TCN/029

…02…DL/810914…02……02…#
TERMINATION PROCEDURE FOR
VERSITRON FIBRE OPTIC CABLE…02……02…CAMPS








                 T̲A̲B̲L̲E̲ ̲O̲F̲ ̲C̲O̲N̲T̲E̲N̲T̲S̲



   CABLE PREPARATIONS ...............................
      4

    1  Remove a piece of the cover jacket ...........
          4
    2  Place a crimp-ferrule over each of the outer
       jackets ......................................
          4
    3  Remove 25 mm of the outer jacket of each fiber
          4
    4  Remove the exposed Kevlar ....................
          4
    5  Remove another 10 mm of the outer jackets ....
          5
    6  Remove 19 mm of the inner jackets ............
          5
    7  Remove som of both dual buffer jackets .......
          6
    8  Place the fibers with the ends upwards .......
          7

   EPOXY PREPARATION ................................
     10

    9  Mix the two-component epoxy ..................
         10
   10  Fill the connector tip with epoxy ............
         10

   CONNECTOR ASSEMBLY ...............................
     11

   11  Insert the fiber in the connector ............
         11
   12  Crimp the connector to the fiber .............
         11
   13  Repeat # 10 through 12 for other connectors ..
         13

   FINAL EPOXY-WORK .................................
     16

   14  Clean the epoxy syringe ......................
         16
   15  Cure the epoxy in the connectors .............
         17

   FINAL CONNECTOR-WORK .............................
     19

   16  Trim off the exposed Kevlar ..................
         19
   17  Remove excess fiber ..........................
         19
   18  Put on the connector nuts ....................
         19
   19  Put on the shrinkable tubes ..................
         21

   POLISHING ........................................
     22

   20  Polish the connectors ........................
         22

   APPENDIX .........................................
     26

   21  Terminology for cable ........................
         27
   22  Terminology for tools ........................
         28
   23  Parts list for termination kit ...............
         29


   1.  a̲c̲t̲i̲o̲n̲     R̲E̲M̲O̲V̲E̲ ̲A̲ ̲P̲I̲E̲C̲E̲ ̲O̲F̲ ̲T̲H̲E̲ ̲C̲O̲V̲E̲R̲ ̲J̲A̲C̲K̲E̲T̲
       reason     Remove as much as needed for easy handling,
                  e.g. 300 mm.

       p̲r̲o̲c̲e̲d̲u̲r̲e̲  a)  Measure up the desired length and
                      set a mark.

                  b)  Cut down the middle of the cover
                      jacket (i.e. between the two outer
                      jackets) with a single egded razorblade.

                  c)  Twist the cover jacket apart, down
                      to the mark and

                  d)  Cut it off with the wire cutter.

   2.  a̲c̲t̲i̲o̲n̲     P̲L̲A̲C̲E̲ ̲A̲ ̲C̲R̲I̲M̲P̲-̲F̲E̲R̲R̲U̲L̲E̲ ̲O̲V̲E̲R̲ ̲E̲A̲C̲H̲ ̲O̲F̲ ̲T̲H̲E̲
                  ̲O̲U̲T̲E̲R̲ ̲J̲A̲C̲K̲E̲T̲S̲ ̲(̲T̲O̲ ̲T̲H̲E̲ ̲B̲O̲T̲T̲O̲M̲)̲
       reason     It is easy now and then you will not
                  forget it.

   3.  a̲c̲t̲i̲o̲n̲     R̲E̲M̲O̲V̲E̲ ̲2̲5̲ ̲m̲m̲ ̲O̲F̲ ̲T̲H̲E̲ ̲O̲U̲T̲E̲R̲ ̲J̲A̲C̲K̲E̲T̲ ̲O̲F̲
                  ̲E̲A̲C̲H̲ ̲F̲I̲B̲E̲R̲
       reason     The length is determined by the length
                  of the connector. The exposed fiber
                  should be able to go all the way through
                  to connector, plus appr. 10 mm (5).

       p̲r̲o̲c̲e̲d̲u̲r̲e̲  a)  Mark up the white jacket and make
                      the black as long.

                  b)  Use the cable hand stripper to bite
                      carefully through the outer jacket
                      (it is soft).

                  c)  Remove the bit off piece by pulling
                      and twisting (easy).

   4.  a̲c̲t̲i̲o̲n̲     R̲E̲M̲O̲V̲E̲ ̲T̲H̲E̲ ̲E̲X̲P̲O̲S̲E̲D̲ ̲K̲E̲V̲L̲A̲R̲
       reason     A well determined, not t̲o̲o̲ long length
                  of Kevlar is wanted to ease and strengthen
                  the termination (5).

       p̲r̲o̲c̲e̲d̲u̲r̲e̲  a)  Split up the Kevlar pattern

                  b)  Split up the bundle in two halves

                  c)  Bend one half back, over the rim
                      of the inner jacket.



                  d)  Cut if off with the razor blade

                  e)  Repeat c) to d) until all the Kevlar
                      is removed.

   5.  a̲c̲t̲i̲o̲n̲     R̲E̲M̲O̲V̲E̲ ̲A̲N̲O̲T̲H̲E̲R̲ ̲1̲0̲ ̲m̲m̲ ̲O̲F̲ ̲T̲H̲E̲ ̲O̲U̲T̲E̲R̲ ̲J̲A̲C̲K̲E̲T̲S̲
       reason     This length is good for getting the
                  Kevlar out in front of the climp ferrule
                  (16). (Must be more than 6.5 mm).

       p̲r̲o̲c̲e̲d̲u̲r̲e̲  a)  Mark up the white jacket and make
                      the black as long.

                  b)  Use the cable hand stripper to bite
                      carefully through the outer jacket
                      (it is soft).

                  c)  Remove the bit off piece by pulling
                      and twisting (easy).

   6.  a̲c̲t̲i̲o̲n̲     R̲E̲M̲O̲V̲E̲ ̲1̲9̲ ̲m̲m̲ ̲O̲F̲ ̲T̲H̲E̲ ̲I̲N̲N̲E̲R̲ ̲J̲A̲C̲K̲E̲T̲S̲
       reason     The length is chosen to protect the
                  fiber as far into the connector as possible.

       note       This length has to be precise.

       p̲r̲o̲c̲e̲d̲u̲r̲e̲  a)  19 mm is measured from the edge
                      of the outer jacket out towards
                      the end of the fiber. Mark them
                      both.

                  b)  Use the wire stripper in th 26.
                      ga position.

                  c)  Take a loose grip on the inner jacket
                      on the mark with the wire stripper.

                  d)  Move the fiber to an angle appr.
                      45 deg. to the wire stripper.

       reason     To prevent the fiber from bending (breaking?)
                  when you bite.

                  e)  Quickly close the wire stripper,
                      BUT!

       warning    Do n̲o̲t̲ attempt to remove the bit off
                  part by pulling with the wire stripper!

                  f)  Remove the wire stripper



                  g)  Grasp firmly around the end of the
                      outer jacket with one hand and around
                      the inner jacket with the other
                      hand.

                  h)  Twist the inner jacket while pulling
                      lightly to separate the inner jacket
                      where it was scored by the wire
                      stripper.

       note       The fiber inside the inner jacket will
                  not be twisted thanks to the silicone
                  fluid than makes it "float" inside the
                  inner jacket.

                  i)  Pull the separated section completely
                      off the fiber.

                  j)  Repeat b) through i) with the other
                      fiber.

                  k)  Be careful to wipe off all the silicone
                      fluid of the exposed fibers.

   7.  a̲c̲t̲i̲o̲n̲     R̲E̲M̲O̲V̲E̲ ̲S̲O̲M̲E̲ ̲O̲F̲ ̲B̲O̲T̲H̲ ̲D̲U̲A̲L̲ ̲B̲U̲F̲F̲E̲R̲ ̲J̲A̲C̲K̲E̲T̲S̲
       note       A precise length is needed to protect
                  the fiber as far as possible into the
                  connector w̲i̲t̲h̲o̲u̲t̲ interfearing with
                  the insertion length.

       p̲r̲o̲c̲e̲d̲u̲r̲e̲  a)  Mark up both fibers 26 mm from the
                      inner jacket out against the end
                      of the fibers.

                  b)  Insert the ends of fiber in the
                      buffer stripper, down to the marks.

                  c)  Hold them steady for 2 1/2 to 3
                      minutes.

                  d)  Wipe of one fiber end gently.

                  e)  Place two fingernails around the
                      fiber on the mark.

                  f)  Pull off the dual buffer jackets.

                  g)  Make sure that all of the inner
                      buffer jacket is removed.

                  h)  Repeat d) through g) with the other
                      fiber.

                  i)  Remove excess buffer stripper.



                  j)  Check that the length of exposed
                      dual buffer jackets fit the length
                      of the connector (see fig. 1 (connector
                      drawing)).

   8.  a̲c̲t̲i̲o̲n̲     P̲L̲A̲C̲E̲ ̲T̲H̲E̲ ̲F̲I̲B̲R̲E̲S̲ ̲W̲I̲T̲H̲ ̲T̲H̲E̲ ̲E̲N̲D̲S̲ ̲U̲P̲W̲A̲R̲D̲S̲
       reason     To prevent the silicone fluid from running
                  out.

       warning    Be careful not to hit the end of the
                  fiber. It might penetrate you and break
                  off. Then it is impossible to find by
                  vision or x-rays!!!!!

       note       The cable now looks as shown on figure
                  2.

















   9.  a̲c̲t̲i̲o̲n̲     M̲I̲X̲ ̲T̲H̲E̲ ̲T̲W̲O̲-̲C̲O̲M̲P̲O̲N̲E̲N̲T̲ ̲E̲P̲O̲X̲Y̲
       reason     The two-component epoxy is chosen for
                  obtaining a good glass grip, possibility
                  of polishing, fast curing and ease of
                  handling.

       note  1    This epoxy is used in equal shares of
                  epoxy and hardener which gives a handling
                  (work) time of appr. 10 minutes after
                  mixing. 

       note  2    The amount of epoxy and hardener to
                  be mixed for a certain number of connectors
                  can be seen in table 1.

       note  3    It is not likely possible to make more
                  than 10 connections during the handling
                  time of the epoxy.

       p̲r̲o̲c̲e̲d̲u̲r̲e̲  a)  Select the number of connections
                      to be completed.

       warning    Before mixing the epoxy be sure that
                  you have got all the connectors to be
                  terminated, within reach!

                  b)  Refer to Table 1 and place the proper
                      amount of epoxy and hardener in
                      a aluminum dish.

                  c)  Mix thoroughly with a wooden stick.

       warning    Insufficient mixing could result in
                  an epoxy that will not harden completely
                  (i.e. loss of a termination)!

       warning    The termination processes must be completed
                  within 10 minutes!

   10. a̲c̲t̲i̲o̲n̲     F̲I̲L̲L̲ ̲T̲H̲E̲ ̲C̲O̲N̲N̲E̲C̲T̲O̲R̲ ̲T̲I̲P̲ ̲W̲I̲T̲H̲ ̲E̲P̲O̲X̲Y̲

       p̲r̲o̲c̲e̲d̲u̲r̲e̲  a)  Bend the epoxy dish to a V-profile

                  b)  Take the epoxy syringe barrel (without
                      tip and plunger)

                  c)  Pour the mixed epoxy into the syringe
                      barrel.



                  d)  Hold the syringe barrel almost horizontal
                      so the syringe barrel tip opens
                      for air flow.

                  e)  Press the plunger slowly into the
                      barrel, and see to it that all the
                      air gets out (move the syringe to
                      vertical as required).

                  f)  Put the syringe tip on the barrel.

                  g)  Place the syringe tip into the hole
                      in the rear of the connector (to
                      the bottom).

                  h)  Insert epoxy until a drop appears
                      at the hole on the connector tip.

       warning    It is n̲o̲t̲ a good idea to fill more than
                  one connector at the time. If anything
                  fails, it is better that the epoxy cures
                  inside the syringe tip than in the connector
                  tip (which is more likely since the
                  hole is much smaller)!



   11. a̲c̲t̲i̲o̲n̲     I̲N̲S̲E̲R̲T̲ ̲T̲H̲E̲ ̲F̲I̲B̲E̲R̲ ̲I̲N̲ ̲T̲H̲E̲ ̲C̲O̲N̲N̲E̲C̲T̲O̲R̲

       p̲r̲o̲c̲e̲d̲u̲r̲e̲  a)  Tear up the Kevlar to make it bristle
                      as much as possible.

       reason     To avoid it from gettig inside the connector
                  where it is for no use.

                  b)  Holding the inner jacket, slowly
                      insert the fiber from the rear of
                      the connector.

       note       It might be avantageous to move the
                  crimp ferrule up in your palm while
                  inserting the fiber. (12).

                  c)  Rotate the connector slowly while
                      inserting the fiber.

       reason     To give the fiber more chance to hit
                  the hole in the tip of the connector.

                  d)  Push the connector down to the outer
                      jacket of the fiber and see to that
                      as much Kevlar as possible gets
                      outside the connector.

   12. a̲c̲t̲i̲o̲n̲     C̲R̲I̲M̲P̲ ̲T̲H̲E̲ ̲C̲O̲N̲N̲E̲C̲T̲O̲R̲ ̲T̲O̲ ̲T̲H̲E̲ ̲F̲I̲B̲E̲R̲

       procedure  a)  Make sure that the crimp tool is
                      open and ready to use.

                  b)  Slide the crimp ferrule over the
                      Kevlar and the rear end of the connector.

                  c)  Place the crimp ferrule in the cavity
                      C of the crimp tool and lock the
                      tool without sqeezing the ferrule.

                  d)  Press: the connector against the
                             crimp tool

                             the crimp ferrule against
                             the connector

                             the cable against the connector

                      (see figure 3 (connector/cable assembly))

       note       Observe that the fiber end moves a little
                  more out of the connector.


                  e)  Crimp the ferrule

                  f)  Move the crimp tool a little backwards
                      and finish the crimp ferrule.

                  g)  Gently pull the fiber end to make
                      sure that it is seated on the dual
                      buffer jacket inside the connector
                      tip.

       note       The connection now looks as on figure
                  4.

                  h)  With a toothpicker place an epoxy
                      "dot" on the tip of the connector,
                      so it is totally covered. (Not too
                      much).

                  i)  Place the connector with tips against
                      the floor (if possible).

       reason     To avoid that the epoxy moves away from
                  the tip of the connector.

   13. a̲c̲t̲i̲o̲n̲     R̲E̲P̲E̲A̲T̲ ̲#̲ ̲1̲0̲ ̲T̲H̲R̲O̲U̲G̲H̲ ̲1̲2̲ ̲F̲O̲R̲ ̲O̲T̲H̲E̲R̲ ̲C̲O̲N̲N̲E̲C̲T̲O̲R̲S̲

       warning    Observe the quality of the epoxy to
                  be used (time!).














   14. a̲c̲t̲i̲o̲n̲     C̲L̲E̲A̲N̲ ̲T̲H̲E̲ ̲E̲P̲O̲X̲Y̲ ̲S̲Y̲R̲I̲N̲G̲E̲
       reason     The syringe must be cleaned immediately
                  after use, to make it reusable.

       procedure  a)  Place some acetone in an aluminum
                      dish.

                  b)  Put the tip of the epoxy syringe
                      into the acetone (in the dish).

                  c)  Empty the epoxy syringe into the
                      epoxy dish.

                  d)  Fill the acetone syringe halfway
                      with acetone.

                  e)  Squirt a small amount of acetone
                      into each of the 4 sections in the
                      back of the epoxy syringe (plunger)
                      (appr. 5 mm up).

       reason     This will lubricate the barrel of the
                  syringe as the plunger is pulled out.

                  f)  Put the epoxy syringe barrel tip
                      into the acetone.

                  g)  Pull out the plunger s̲l̲o̲w̲l̲y̲

       reason     To fill up the barrel with acetone

       warning    The barrel is v̲e̲r̲y̲ sticky inside due
                  to the epoxy, so be careful not to use
                  too much force. It will make the black
                  plunger tip go off!

                  h)  When the plunger is 5 mm from the
                      back of the barrel, push it back
                      (with force) to get out all the
                      acetone (and epoxy).

                  i)  Repeat f) through h) 3 times.

       reason     To be sure that all epoxy has been removed
                  from the barrel of the syringe.

                  j)  Fill the syringe with acetone and
                      put on the syringe tip.



                  k)  Holding firmly around the tip force
                      the epoxy out of the needle (and
                      the acetone through it).

                  l)  Fill the syringe through the needle.

                  m)  Repeat k) and l) 3 times

                  n)  Split up the syringe and see to
                      that all parts are completely dry
                      (from acetone)

       note       Beat it against something and blow on
                  it.

       warning    Watch the plunger tip!

       reason     This is important if the syringe is
                  to be used again right away.

                  o)  Look through the needle to be sure
                      that all epoxy is gone.

   15. a̲c̲t̲i̲o̲n̲     C̲U̲R̲I̲N̲G̲ ̲O̲F̲ ̲E̲P̲O̲X̲Y̲

       procedure  a)  Make a set-up where the connectors
                      hang down (vertical) without touching
                      each other.

       note       Max. 6 connectors, 4 at the best.

                  b)  Place the heat gun on the same level
                      as the connectors, in 400 mm distance.

                  c)  Set the heat gun air temperature
                      to 300…0e…o…0f… F (150…0e…o…0f… C).

       note       The rated temperature is at the tip
                  of the heat gun.

                  d)  Turn on the heat gun for c̲o̲l̲d̲ air
                      and align it so the air flow hits
                      all connectors equally.

       note       Feel it with the tip of your fingers.

                  e)  Turn on the warm air and check that
                      the temperature of the connectors
                      does not burn your fingers.



       reason     The max. curing temperature is 70…0e…o…0f…C
                  - and that hurts your fingers.

       warning    If the connectors are cured at temperatures
                  over 90…0e…o…0f…, the dual buffer jackets of
                  the cable are destroyed!

                  f)  Curing time will be appr. 20 minutes.

                  g)  After 20 minutes check the condition
                      of the epoxy with a tooth picker.

       warning    Do not touch the connector, it is hot!

                  h)  Touch the epoxy with the tip of
                      the toothpicker: 

                      1) if it sticks and makes threads
                         then the epoxy is n̲o̲t̲ yet done.
                         - 10 more minutes.

                      2) if it sticks and lets go again,
                         the epoxy is nearly done - 5
                         more minutes.

                      3) if it does not (or hardly) sticks,
                         the epoxy is done.

                  i)  Repeat h) actions until 3) applies.

                  j)  Turn off the warm air (leave the
                      cool air on) and let the connectors
                      cool off completely.

       note       Until they feel cold (appr. 5 minutes)

                  k)  The epoxy drop should feel hard
                      and glassy smooth to the touch of
                      a sharp tool. (When it is cold).



   16. a̲c̲t̲i̲o̲n̲     T̲R̲I̲M̲ ̲O̲F̲ ̲T̲H̲E̲ ̲K̲E̲V̲L̲A̲R̲ ̲T̲H̲A̲T̲ ̲I̲S̲ ̲E̲X̲P̲O̲S̲E̲D̲ ̲A̲R̲O̲U̲N̲D̲
                  ̲T̲H̲E̲ ̲C̲R̲I̲M̲P̲ ̲F̲E̲R̲R̲U̲L̲E̲,̲ ̲U̲S̲I̲N̲G̲ ̲A̲ ̲W̲I̲R̲E̲ ̲C̲U̲T̲T̲E̲R̲.̲
       reason     The Kevlar should not be cut off before
                  the curing of epoxy, to avoid Kevlar
                  threads from sticking in the wet epoxy.

   17. a̲c̲t̲i̲o̲n̲     R̲E̲M̲O̲V̲E̲ ̲E̲X̲C̲E̲S̲S̲ ̲F̲I̲B̲E̲R̲

       procedure  a)  Cleave the fiber by making a scratch
                      on the fiber with the glass cleaver.

       note       As close to the epoxy dot as possible
                  dot, to make the polishing safe.

                  b)  Break off the excess fiber by bending
                      the end away from the scratch.

       warning    Be careful with the fiber bits. Make
                  sure that you throw them away and n̲o̲t̲
                  in a cloth which is to be used later!

   18. a̲c̲t̲i̲o̲n̲     P̲U̲T̲ ̲O̲N̲ ̲T̲H̲E̲ ̲C̲O̲N̲N̲E̲C̲T̲O̲R̲ ̲N̲U̲T̲

       procedure  a)  Put a snapring on the connector
                      (use the right front to ease the
                      nut insertion). Figure 5.1.

                  b)  Crimp it a bit with the tool (58
                      cage). Figure 5.2.

       note       The tool will wear out (appr. 70 terminations)
                  but can be made reusable with a file.

                  c)  Hold the ring crimped, covering
                      only the rear half of it. Figure
                      5.3.

                  d)  Put on the nut so it holds the ring
                      crimped.

                  e)  Remove the tool and push on the
                      nut until it "clics". It is locked.








   19. a̲c̲t̲i̲o̲n̲     P̲U̲T̲ ̲O̲N̲ ̲T̲H̲E̲ ̲S̲H̲R̲I̲N̲K̲A̲B̲L̲E̲ ̲T̲U̲B̲E̲

       p̲r̲o̲c̲e̲d̲u̲r̲e̲  a)  Slide the heat shrinkable tubing
                      over the connector until it just
                      passes the connector nut.

       reason     It shall cover the Kevlar without touching
                  the nut.

                  b)  Carefully heat the tubing until
                      it is shrunk tightly around the
                      crimp ferrule.

       note       Turn the connector around while heating,
                  to prevent the connector from getting
                  too hot (the fiber will be destroyed).

       warning    Avoid to make the heat hit the tip of
                  the connector, otherwise the epoxy will
                  soften up!

                  c)  When you have finished heating,
                      hold the hot part (tube and cable)
                      as straight as possible.

       reason     To prevent it from growing stiff in
                  a bend position.

       note       The shrunk tube shall n̲o̲t̲ hold tight
                  to the outer jacket. This gives flexibility
                  and protection of the cable in extreme
                  bendings at the connector.

                  d)  Repeat with the other connectors.




   20. a̲c̲t̲i̲o̲n̲     P̲O̲L̲I̲S̲H̲ ̲T̲H̲E̲ ̲C̲O̲N̲N̲E̲C̲T̲O̲R̲S̲

       p̲r̲o̲c̲e̲d̲u̲r̲e̲  a)  Remove any excess epoxy from the
                      side of the connector tip, with
                      a razorblade. (figure 6).

       warning    Do not cut too high at the top, so the
                  whole epoxy drop will go off and destroy
                  the termination!

                  b)  Insert the connector in the polishing
                      fixture.

       note       If it does not insert easily there are
                  still some epoxy on the side of the
                  connector tip.

                  c)  Put the 60-micron polishing film
                      on the smooth aluminium plate.

       reason     The plate shall be without scratches
                  to avoid bulks in the polishing film
                  where the connector will grip.

       note       Use water as a lubricant and coolant
                  during polishing.

                  d)  Polish off the epoxy dot using the
                      60 micron polishing film until appr.
                      0.3 mm from the connector tip.

       reason     A thin film of epoxy shall be left on
                  the tip, so the connector does not get
                  hurt from the rough polishing film.

       warning    Be aware of any white spots on the polishing
                  film, they may indicate particles underneath
                  the film!

       warning    Do not press, about 10 rotations are
                  enough!

                  e)  Flush the polishing fixture and
                      polishing film with water from the
                      bottle.

       reason     To remove any particles of metal or
                  epoxy before going to the next grade
                  of polishing film.

                  f)  Wrap the polishing plate and the
                      polishing fixture dry with a KIM-WIPE
                      as required.


       reason     To ensure that no particles are left.

                  g)  Exchange the polishing film with
                      the next one in use. Place the used
                      one in a vertical position.

       reason     To make it able to dry up. (To make
                  it reusable).

                  h)  Use the 40-micron polishing film
                      and polish until scratch marks are
                      just visible on the connector tip.

       note  1    To remove the epoxy completely you may
                  have to press a little. You can feel
                  (and hear) the difference when the metal
                  grips.

       note  2    A ring-groove may appear on the tip
                  of the connector. This is due to production
                  tolerances. This groove should be removed
                  too, if possible.

                  j)  Repeat e), f), and g).

                  k)  Remove the connector from the polishing
                      fixture and remove any excess epoxy
                      from the conical side of the connector.

       reason     To avoid epoxy-smears over the connector
                  tip in the furhter polishing procedure
                  with finer films.

       note       You cannot hurt the fiber now where
                  the epoxy top is gone.

                  l)  Insert the connector into the polishing
                      fixture.

                  m)  Polish with the 12-micron film until
                      all prior scratch marks are removed.
                      Use water as lubricant and coolant
                      during polishing.

       note       Practically no metal will be taken off
                  from this point, so the surface should
                  begin to reflect from the areas without
                  scratches.



       warning    At this point you must be sure to make
                  an equal pressure all the way around
                  the polishing fixture. It may be advantageous
                  to polish in "8s" or b̲i̲g̲ circles and
                  to use all the polishing film!

                  n)  Repeat e), f), and g).

                  p)  Check the connector surface with
                      the magnifier:

       note  1    It should appear to be a uniform quality.
                  Look for major scratches and their location.
                  Remember, THE FIBER IS IMPORTANT.

       note  2    When examining the connector with the
                  magnifier, turn the connector around
                  so you will see all the details.

                  q)  Repeat m), n), and p) using the
                      3-micron film.

       note       At this point all major scratches shall
                  be gone.

                  r)  Repeat m), n), and p) using the
                      1-micron film.

       note       If epoxy smears (blue/grey film) or
                  scratches will not disappear, go back
                  to 3-micron film (or even 12 micron
                  when required).

       warning    At this point the film is so fine that
                  you can feel any particle. They m̲u̲s̲t̲
                  ̲n̲o̲t̲ be there!

                  s)  Dry and examine the connector carefully,
                      especially the fiber itself.

       reason     The optical surface must be flat and
                  free of scratches, chips or epoxy smears.

                  t)  Put on the red connector protecting
                      head.

                  u)  Go on with the next polishing

















   A  P  P  E  N  D  I  X…01…**********************











   T̲E̲R̲M̲I̲N̲O̲L̲O̲G̲Y̲ ̲F̲O̲R̲ ̲T̲O̲O̲L̲S̲

   TBD.



            F̲I̲B̲E̲R̲ ̲O̲P̲T̲I̲C̲ ̲T̲E̲R̲M̲I̲N̲A̲T̲I̲O̲N̲ ̲K̲I̲T̲

           (̲S̲u̲p̲p̲l̲i̲e̲s̲ ̲f̲o̲r̲ ̲8̲0̲ ̲T̲e̲r̲m̲i̲n̲a̲t̲i̲o̲n̲s̲)̲



   I̲T̲E̲M̲    Q̲U̲A̲N̲T̲I̲T̲Y̲   D̲E̲S̲C̲R̲I̲P̲T̲I̲O̲N̲

    1      1          I̲n̲s̲t̲r̲u̲c̲t̲i̲o̲n̲s̲

    2      4 oz ea    E̲p̲o̲x̲y̲ ̲-̲ ̲t̲w̲o̲ ̲c̲o̲m̲p̲o̲n̲e̲n̲t̲

    3                 C̲u̲t̲t̲i̲n̲g̲ ̲i̲m̲p̲l̲e̲m̲e̲n̲t̲s̲

           20         Single edge blades
           1          Wire stripper
           2          Optical cable hand stripper
           2          Wire cutters, 1 small, 1 large

    4      1          C̲r̲i̲m̲p̲ ̲T̲o̲o̲l̲ ̲a̲n̲d̲ ̲D̲i̲e̲

                      P̲o̲l̲i̲s̲h̲i̲n̲g̲ ̲K̲i̲t̲

           1          Polishing fixture
           1          Polishing plate
           1 set      Polishing film

    6      1          H̲e̲a̲t̲ ̲S̲o̲u̲r̲c̲e̲

    7      80         H̲e̲a̲t̲ ̲s̲h̲r̲i̲n̲k̲a̲b̲l̲e̲ ̲t̲u̲b̲e̲,̲ 38 mm

    8      2          B̲u̲f̲f̲e̲r̲ ̲s̲t̲r̲i̲p̲p̲e̲r̲,̲ 120 ml. (glass
                      jar)

    9      2          A̲c̲e̲t̲o̲n̲e̲,̲ 120 ml, (can)

   10      2          K̲i̲m̲w̲i̲p̲e̲s̲ (or similar), 100 pcs.
                      (box)

   11      3          S̲q̲u̲e̲e̲z̲e̲ ̲b̲o̲t̲t̲l̲e̲s̲,̲ 120 ml

   12                 C̲a̲b̲l̲e̲ ̲h̲o̲l̲d̲e̲r̲

           1          Plate
           12         Shoulder screws
           12         Cable clamps

   13      1          R̲e̲t̲a̲i̲n̲i̲n̲g̲ ̲r̲i̲n̲g̲ ̲i̲n̲s̲e̲r̲t̲i̲o̲n̲ ̲t̲o̲o̲l̲



   I̲T̲E̲M̲    Q̲U̲A̲N̲T̲I̲T̲Y̲   D̲E̲S̲C̲R̲I̲P̲T̲I̲O̲N̲

   14      1          L̲i̲g̲h̲t̲ ̲s̲o̲u̲r̲c̲e̲

   15      1          M̲a̲g̲n̲i̲f̲i̲e̲r̲,̲ ̲1̲0̲x̲

   17                 M̲i̲s̲c̲e̲l̲l̲a̲n̲e̲o̲u̲s̲ ̲i̲m̲p̲l̲e̲m̲e̲n̲t̲s̲

           2          Syringe with small needle
           1          Syringe with larg open needle
           1          Toothpicks, 200 (box)
           1          Wood stirring sticks, 100 (box)
           40         Aluminium dishes