DataMuseum.dk

Presents historical artifacts from the history of:

CR80 Wang WCS documentation floppies

This is an automatic "excavation" of a thematic subset of
artifacts from Datamuseum.dk's BitArchive.

See our Wiki for more about CR80 Wang WCS documentation floppies

Excavated with: AutoArchaeologist - Free & Open Source Software.


top - download

⟦7fb844744⟧ Wang Wps File

    Length: 83255 (0x14537)
    Types: Wang Wps File
    Notes: LKSAA Vol. II part 1      
    Names: »4240A «

Derivation

└─⟦84f7719fc⟧ Bits:30006031 8" Wang WCS floppy, CR 0385A
    └─ ⟦this⟧ »4240A « 

WangText

…00……00……00……00……00…I…02……00……00…I H…0b…H G…0c…G…05…F…0d…F…05…F…06…,
+…09…+…0d…+…06…*…05……16……00……16……01……16……07……15……0c……15……01……15……05……15……06……14……0a……14……0b……14……0c……14……02……14……06……13……0b……13……0d……13……0e……13……02……13… …12……0a……86…1         …02…   …02…   …02…   …02…                                           


                                                       Issue 1.5
LKSAA - VOLUME II                                      SYS/84-06-15
Part 1
TECHNICAL PROPOSAL                                     Page  #a






2.3      A̲V̲A̲I̲L̲A̲B̲I̲L̲I̲T̲Y̲ ̲R̲E̲Q̲U̲I̲R̲E̲M̲N̲E̲T̲S̲

         The availability of the proposed equipment is very
         high due to not only a high reliability of individual
         system elements, but mainly due to the chosen CR80
         computer configuration, where functional like elements
          substitute each other automatically in case of failure.
         

         The actual availability will be very close to 100%,
         due to the exceptional design of the CR80 configuration
         for the LKSAA.



2.3.1    G̲e̲n̲e̲r̲a̲l̲ ̲C̲o̲n̲s̲i̲d̲e̲r̲a̲t̲i̲o̲n̲s̲

         The high system availability has been achieved by the
         use of highly reliable modules, redundant processor
         units and automatic reconfiguration facilities. Care
         has been taken to ensure that single point errors do
         not cause total system failure.

         The reliability criteria imposed on the computer systems
         have been evaluated and the proposed hardware/software
         operational system analysed to determine the degree
         of availability and data integrity provided. In this
         chapter reliability is stated in numerical terms and
         the detailed predictions derived from mathematical
         models presented.

         The availability predictions are made in accordance
         with system reliability models and block diagrams corresponding
         to the proposed configuration. This procedure involves
         the use of module level and processor unit level failure
         rates, or MTBF, (mean time between failures) and MTTR
         (meantime to repair); these factors are used in conjunction
         with a realistic modeling of the configuration to arrive
         at system level MTBF and availability.

         Tabulated results of the analysis are presented including
         the reliability factors: system MTBF and repair time
         MTTR.



         The basic elements of the proposed system architecture
         are constituted by standard CR80 units. Reliability
         and maintainability engineering was a significant factor
         in guiding the development of the CR80.

         The CR80 architecture is designed with a capability
         to achieve a highly reliable computer system in a cost-effective
         way. It provides a reliable set of services to the
         users of the system because it may be customized to
         the actual availability requirements. The CR80 fault
         tolerant computers are designed to avoid single point
         errors of all critical system elements by provision
         of redundancy paths, multi-processor capabilities and
         dual power supplies.

         The architecture reflects the fact that the reliability
         of peripheral devices is lower than that of the associated
         CR80 device controllers. This applies equally well
         to communication lines where modems are used as part
         of the transmision media. Thus, the peripheral devices,
         modems, communication line, etc., impact the system
         availability much more than the corresponding device
         controllers.

         To assure this very highly reliable product, several
         criteria were also introduced on the module level:

         -   An extensive use of hi-rel, mil-spec components,
             ICs are tested to the requirements of MIL-STD 883
             level B or similar

         -   All hardware is designed in accordance with the
             general CR80 H/W design principles. These include
             derating specification, which greatly enhance the
             reliability and reduce the sensibility to parameter
             variations

         -   Critical modules feature a Built-In Test (BIT)
             capability as well as a display of the main states
             of the internal process by Light Emitting Diodes
             on the module front plate. This greatly improves
             module maintainability, as it provides debugging
             and trouble shooting methods, which reduce the
             repair time

         -   A high quality production line, which includes
             high quality soldering, inspection, burn-in and
             an extensive automatic functional test



         -   Software reliability is another aspect which will
             be incorporated in achieving high over all availability

         -   Data has been replicated in order to increase system
             availability

         -   Automatic and manual facilities are provided to
             perform quick reconfiguration in case of errors

         -   Extensive M & D, maintenance and diagnostic software
             can be used to minimize down times.



2.3.2    R̲e̲c̲o̲v̲e̲r̲y̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲s̲

         Flexible variation in the size and structure of the
         CR80 system used for the LKSAA are permitted by the
         unusual degree of hardware and software modularity.
         The hardware essentially consists of fast transfer
         buses joined to each other by adapters which allow
         units on one bus to access those on another. Dualization
         at the internal level and multiple redundancy at the
         system level provide a CR80 hardware architecture which
         is exploited by the DAMOS software operating system
         and programs to survive operational failure of individual
         components.

         Reliability, which is increasingly becoming of concern
         in real-time and distributed network applications,
         is achieved in the CR80 computer systems by applying
         unique architectural concepts. The CR80 hardware/software
         architecture treats all multiprocessors as equal elements
         not absolutely dedicated to a specific role. Fault
         tolerance and backup are achieved through a redundance
         scheme without preassignment of system functions to
         specific processors. This is in marked contrast to
         the more common rigid dualized configurations often
         encountered in dedicated applications with on-line
         master/slave arrangements, or off-line backup with
         switchover facility.

         All redundant equipment is under control of a watchdog
         micro-computer, which constantly receives information
         on all subsystems status. This strategy ensures that
         all units are ready to operate if any reconfiguration
         is needed.



         The LKSAA has been sized to deal with the required
         data volumes by use of primary hardware only.

         Performance degradation may result from the occurence
         of a failure if it happens durings peak load, because
         systems resources are used to recover from errors.
         As an example, consider the mirrored disc. If a head
         crash occurs on one of the discs, then a fresh blank
         disc must be inserted, and all information must be
         moved from the non-failed disc to the fresh disc. This
         requires more disc activity than normal operational
         use, so it might affect performance levels during peak
         load situations. Of course the operator can choose
         to wait with disc restoration till after peak load,
         but this must be considered unrecommendable, because
         the system is not able to recover from the next failure.

         Similarly, when errors occur in one of the two  processing
         units, the system can continue operation with reduced
         facilities in a graceful degradation mode, but it must
         be realized than following errors might be catastrophic.

         Various degradation strategies can be programmed in
         the watchdog, which initiates all automatic reconfigurations.
         The system operator may override this by enabling/disabling
         various devices and he may also perform physical reconfiguration
         by removing/replacing the various hardware modules.
         This can be done without taking the power off the system.

         In principle, users will be automatically recovered
         from hardware errors, when they occur on a fully redundant
         system, but in some instances it may be necessary to
         ask the users to reenter his last input transaction.

         The CR80 Operating System as well as application processes
         contains a large number of error detection routines.
         A detected error or inconsistency will result in a
         report to the high level operating system, which will
         then report the error on the operator console and call
         a basic error module. If the error is fatal a termination
         will occur and the watchdog will detect that keep-alive
         messages from the active system are missing. This results
         in automatic switchover and recovery.



2.3.3    F̲a̲l̲l̲b̲a̲c̲k̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲s̲

         As described earlier, the CR80 configuration for LKSAA
         has been designed to provide maximum availability.
         This means that several fallback procedures have been
         implemented at the hardware and system software level.
         Logical addressing is used throughout the system, which
         make it possible to access the system from an alternative
         terminal or print out on an alternative hardcopy device
         subject to security constraints.

         In excess of the standard fall back procedures implemented
         in hardware and system software, like the mirrored
         disc concept, procedural fall back procedures may be
         implemented and enforced by the system. As an example
         the parameterized distribution tables found in CAMPS
         and implemented in LKSAA, can provide a copy of all
         messages to be printed on a specific terminal.



2.3.4    R̲e̲c̲o̲v̲e̲r̲y̲ ̲T̲i̲m̲e̲s̲

         Recovery times are minimized throughout the system
         by using automatic recovery wherever possible. This
         approach eliminates all operator reaction time, which
         is normally several magnitudes greater than automated
         procedures. The actual recovery times depends very
         much on the circumstances.

         Reintroducing modules as part of restoring a failed
         system under system operator control, will be dominated
         by operator reaction time, but good procedural rules
         and guidelines can minimize the time required.

         The system operator can advise users of any planned
         system facilities reduction.



2.3.5    O̲v̲e̲r̲a̲l̲l̲ ̲S̲y̲s̲t̲e̲m̲ ̲A̲v̲a̲i̲l̲a̲b̲i̲l̲i̲t̲y̲

         The LKSAA system has been designed with the objective
         of providing an extremely high available system.

         The computer system is partitioned into system elements
         and the model used for reliability and availability
         prediction shows how the proposed quipment provides
         the high degree of reliability required.



         The reliability characteristics for the system are
         stated in numerical terms by a mathematical model.
         The supporting detailed prediction is presented in
         this chapter. The system model is partitioned into
         modular units and system elements that reflect the
         redundancy of the configuration; it accounts for all
         interconnections and switching points. The MTBF and
         MTTR for the individual elements used in the calculations
         were obtained from experience with similar equipment
         on other programs.

         The equipment has been partitioned and functions apportioned,
         so that system elements can have only two states -
         operable or failed. System elements are essentially
         stand-alone and free of chain failures.

         Careful attention has been paid in the design to eliminate
         series risk elements. Redundant units are repairable
         without interruption of service. Maintenance and reconfiguration
         are possible without compromising system performance.

         The primary source selected for authenticated reliability
         data and predictions is the MIL-HDBK-217. The failure
         rate data are primarily obtained from experience from
         previous programs and continously revised as part of
         the maintenance program on concurrent programs.

         The reliability model which applies to the proposed
         configurations is identified in the figure shown in
         the following.

         The model that has been calculated covers the basic
         operational system.  In order to improve availability
         for the minimal system and the Communication Handling
         system to an even higher degree, you can ensure higher
         spare part availability on important modules, which
         can be easily introduced as part of a fall back procedure.

         The crypto subsystem has not been reliability modelled,
         because the dedicated encryption/decryption device
         is not known to CHRISTIAN ROVSING A/S at this time.
          However, CHRISTIAN ROVSING is proposing a dual Local
         Area Network with a dual set of Network Managemnet
         Hosts.


















































                      Figure 2.3.5-1
               Reliability Model for LKSAA
                  User Terminal Position


2.3.6    M̲e̲a̲n̲-̲T̲i̲m̲e̲-̲B̲e̲t̲w̲e̲e̲n̲-̲F̲a̲i̲l̲u̲r̲e̲ ̲(̲M̲T̲B̲F̲)̲

         The high reliability of the proposed equipment is achieved
         through use of proven failure rate equipment similar
         to that supplied for other programs.

         Early in the design phase, a major objective for each
         module is to achieve reliable performance. CR80 modules
         make extensive use of carefully chosen components;
         most of the IC…08…s are tested to the requirement of MIL-STD
         883 level B.

         The inverse of MTBF representing failure rate which
         applies to system elements and modules is listed.

         The MTBF data has been derived from reliability data
         maintained on similar programs. Inherent MTBF values
         are in general derived from the reliability predictions
         accomplished in accordance with the U.S. MIL-HDBK-217
         "Reliable Predictions of Electroic Equipment".

         Failure rate data for terminal and peripheral equipment
         is generally provided by the vendor in accordance with
         the subcontract specifications:





 …06…1         …02…   …02…   …02…   …02…           …02…  …02…     …02…       …02… …02…       …02…    
Module   Item Description           MTBF          FPMH    MTTR
N̲o̲.̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲(̲h̲r̲s̲)̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲(̲m̲i̲n̲u̲t̲e̲s̲)̲

8002     CPU, SCM                                                 36500  27.4 30
8003     CPU, CACHE                                               26100  38.3 30
8009     EPM                                                     
                                                                 
                                                                 172400 
                                                                         5.8 30
8013     EPROM                                                    91700  10.9 30
8016     RAM 128K/64K         17000/29600                        
                                                                 
                                                                 
                                                                 58.8/33.8 30
8020     MAP                                                      19400  51.6 30
8021     STI                                                      32800  30.5 30
8037     UNIVAC I/F                                               33200  30.1 30
8039     IBM CH, I/F                                              32400  30.9 30
8044     DISC CTRL
         DUAL                       30200                        
                                                                 
                                                                 
                                                                  33.1 30
8045     TAPE CTRL 16K                                            35700  28.0 30
8046     DUAL PAR.CTRL                                            35700  28.0 30
8047     ST.FD.CTRL
         DUAL                                                     59500 
                                                                        
                                                                        
                                                                         16.8 30
8050     POWER SUPPLY                                             26800  37.3 30
8055     MBT                                                     
                                                                 
                                                                 285700  
                                                                         3.5 30
8059     MBE                                                     10000000  
                                                                           0.1 30
8066     LTU DUAL                                                 27600 
                                                                        
                                                                        
                                                                         36.9 30
8070     CSA                                                     
                                                                 
                                                                 769000  
                                                                         1.3 30
8071     MIA                                                      85500  11.7 30
8072     SBA                                                      90100  11.1 30
8073     TIA                                                     
                                                                 
                                                                 117600  
                                                                         8
                                                                         5 30
8074     EPA                                                     
                                                                 
                                                                 256000  
                                                                         3.9 30
8078     IBA                                                      21600  46.2 30
8079     UIA                                                      15600  64.0 30
8081     CIA A & B                                                71400  14.0 30
8082     LIA-N                                                   10000000  
                                                                           0.1 30
8083     LIA-S (Switch +
         Common)           534759/3571428    1.87/0.28           30
8084     DCA                                                      46900  21.3 30
8085     TCA                                                     
                                                                 
                                                                 128200  
                                                                         7.8 30


Module   Item Description           MTBF          FPMH    MTTR
N̲o̲.̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲(̲h̲r̲s̲)̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲(̲m̲i̲n̲u̲t̲e̲s̲)̲

8086     PCA                        185200         5.4      30
8087     SFA                      10000000         0.1      30
8088     EIA A & B                  113600         8.8      30
8106     MAINS FILTER
         DISTRIBUTION               625000         1.6      30
8115     Minicrate                   26300          38      60
8125/PC  PU-CRATE                   200000         5.0      60
8124/AB  CU-CRATE                   703630         1.4      60






Peripheral Item Description         MTBF          FPMH    MTTR
N̲o̲.̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲(̲h̲r̲s̲)̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲(̲m̲i̲n̲u̲t̲e̲s̲)̲

8300/--- DISC DRIVE,
         SMD, 40-300MB                4000       250.0      90
8301/--- DISC DRIVE,
         CMD (16-48)+16MB             4000       250.0      90
8302/--- DISC DRIVE, MMD,
         12-80MB                      8000       125.0      60
8307/--- FLOPPY DRIVE,
         dual/single                  8000       125.0      30
         sided
8320/001 TAPE STATION,
         Pertec FT 8000               8000       125.0      60
8320/002 TAPE STATION,
         Pertec FT 9000               2500       400.0      60



2.3.7    M̲e̲a̲n̲-̲T̲i̲m̲e̲-̲T̲o̲ ̲R̲e̲p̲a̲i̲r̲ ̲(̲M̲T̲T̲R̲)̲

         The proposed system is designed for ease of maintenance.
         The system is built of modules each comprising a complete
         well-defined function. Replacement of modular units
         result in minimum repair time. Software and firmware
         diagnostic routines rapidly isolate faulty modules;
         repair can then be performed by semi-skilled maintenance
         personnel and usually without special tools.

         The proposed system, composed of redundant elements,
         meets the objective of ease of maintenance. All units
         and system elements are of a modular construction so
         that any defective module can be isolated and replaced
         in a minimum amount of time.

         In the design of the System Elements, careful attention
         was given to ease of maintenance without requiring
         special tools, so that the maintenance could be performed
         by semi-skilled maintenance personnel.

         Fault detection and isolation to the system element,
         in som cases module level, is inherent in the software
         residing in the various processors. In peripheral devices,
         the fault detection and isolation is accomplished by
         a combination of on-line, software, built-in test,
         and operator observations.

         In case the correct function of the system is extremely
         critical, the Processors will have built-in, on-line,
         diagnostic programs. Even though the Processors are
         highly reliable, failures can occur; usage of the off-line
         diagnostics minimizes the downtime for a system.

         An off-line diagnostics software package can be employed
         to ease the diagnostics in case of error. Normally,
         this software package is stored on disc. After initiation,
         the program will test all modules forming the system
         and print the name and address of the erronous module
         on the operator…08…s console. Having replaced the erronious
         module, the Processor is ready for operation again.
         The operator might, if necessary, run the off-line
         diagnostics program once more to verify that the system
         is now working without errors.



         The command interpreter module of the diagnostic package
         enables the operator to initiate any or all of the
         test programs for the specific subsystem off-line,
         to assist in trouble shooting and to verify the repair.

         Examples of modules tested are LTU…08…s, CPU and RAM modules,
         etc.

         The diagnostic package will also assist in fault isolation
         of the peripherals. However, common and special test
         equipment might have to be used to isolate the faulty
         module.

         The Mean-Time-To-Repair for the equipment is derived
         from two sources. The first is actual experience data
         on the equipment proposed for the system. The other
         source is from predictions generated in accordance
         with MIL-HDBK-472 or similar documents. As an example,
         the MTTR for the Disk Storage Unit was derived from
         repair times measured by the supplier. The repair times
         of other units were derived by a time-line analysis
         of the tasks associated with fault detection, isolation,
         repair, and verification. These repair times were weighted
         by the MTBF of each module to derive the unit MTTR.
         The calculation of the Mean-Time-To-Repair (MTTR) is
         done by weighting the individual module repair times
         by the MTBF of the individual module. The MTTRs of
         the major CR80 equipments are presented.

         The predicted MTTR values are from experience with
         modules of other programs. The predicted MTTR assumes
         that all tools, repair parts, manpower, etc., required
         for maintenance are continuously available.






The equivalent calculated overall availability will be above
 

                          99.999
                          ======

         For safety reasons MTTR figures used for a calculations
         are very conservative, typically 30 minutes, but a
         much better result can be obtained when operators and
         maintenance people are carefully instructed and trained.
         The following figure shows a typical fault isolation
         and replacement sequence, when skilled people are used.



















































                      Figure 2.3.7-1
     Typical Fault Isolation and…01…Replacement Sequence



         Functions                   Failure   Critical
                                     Factor    Value
          ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
         ̲ ̲ ̲ ̲ ̲ ̲

         1   Local Area Network      1.0       N/A
         2   Host                    1.0       A   99% …0e…1)…0f…
         3   Disk storage            1.0       A   99% …0e…1)…0f…

             Input/Output
         4   Connections and 
             interfaces
         5   Paper Tape Reader
         6   Display Workstation
         7   High Speed Printer
         8   Paper Tape Punch
         9   Log Printer
         10  Document Printer
         11  Krypto LAN              1.0       A   99% …0e…1)…0f…
         12  OCR                     1.0       N/A
         13  Maintenance position    1.0       A   95% …0e…2)…0f…
         14  Software                1.0       A   95%


         R̲e̲l̲i̲a̲b̲i̲l̲i̲t̲y̲ ̲F̲a̲c̲t̲o̲r̲s̲

         1)  The configuration for the LKSAA has been designed
             with particular emphasis on high availability as
             shown in the earlier availability calculation.
             The Central Processing Units has been dualized
             and all disks are mirrored. The Local Area Network
             for Krypto control has been dualized.

         2)  The maintenance position can use standard equipment
             which can easily be replaced. Regarding the S/W
             reliability the standard message switching software
             has then been extensively tested in order to minimize
             failures, and all software has been structured
             so that individual programs that fail can be isolated
             so that total system break down can be minimized.




2.4      I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲

         All equipment delivered by contractor is to be installed
         in the FMZ (TELKO-NEUBAU) except for the TX and RX
         sites.



2.4.1    F̲M̲Z̲ ̲I̲n̲s̲t̲a̲l̲l̲a̲t̲i̲o̲n̲s̲

         The equipment to be installed in the FMZ comprises
         the below listed major assemblies and workstations.
         A reference to the location specified by customer is
         made by the numbers used in Anhang 13 of the I.F.B.:

         10) 1.  ZVA dual computer mounted in 5 standard 19"
                 racks, four disk drives, a high speed printer
                 and one system console position with a VDU
                 and a hardcopying printer.

             2.  Crypto computer and two crypto supervisor positions
                 with 2 VDU's, 1 paper tape reader and 1 printer.

             3.  Line switching facility mounted in a standard
                 19" rack. (Shalt platz and Handvermittlung).

         16) Eight Message service operator positions with eight
             VDU's.

          6) Tape in/out position with four paper tape readers.

         15) Four paper tape punch. Four printers

         12) 1.  Document printing system with two copiers.

             2.  Message service operator position with one
                 VDU.

             3.  Message distribution operator position with
                 one VDU and one printer.

             4.  Security log position with one printer.


          9) Radio Control Center equipment as described below
             in 2.4.2.1.

         13) System Supervisor position with one color graphic
             display and one printer.


         Other positions:

         1.  One TELETEX station, location to be decided on
             a Site Survey.

         2.  Four situation monitors to be located on distributed
             positions. Location to be decided on a Site Survey.

             Tables and chairs for above positions are not included
             in this proposal.



2.4.2    R̲a̲d̲i̲o̲ ̲C̲o̲n̲t̲r̲o̲l̲ ̲S̲y̲s̲t̲e̲m̲



2.4.2.1  R̲a̲d̲i̲o̲ ̲C̲o̲n̲t̲r̲o̲l̲ ̲C̲e̲n̲t̲e̲r̲

         The installation at the radio control center comprises
         installation of the following equipment:

         -   2 19" racks containing a dualized x-net incl. branching
             boxes, XCP's, XTA's, modems and customer furnished
             equipment (TT modem, ATS or ARQ).

         -   6 workstations, each of one VDU, an interface box
             and a loudspeaker.

         -   1 log printer and a customer provided teletype.



2.4.2.2  T̲X̲ ̲S̲t̲a̲t̲i̲o̲n̲

         At each of the two TX stations, the following equipment
         shall be installed:

         -   2 19" racks containing a dualized x-net incl. a
             branching box, XCP's, XCT's, wall outlets, modem
             and customer provided transmitters.





2.4.2.3  R̲X̲ ̲S̲t̲a̲t̲i̲o̲n̲

         At each of the two RX stations the following equipment
         shall be installed:

         -   2 19" racks containing a dualized x-net, branching
             boxes, XCP's, XCT's, XTA's, wall outlets, antenna
             matrix and four customer provided recievers.



2.4.3    A̲E̲ ̲-̲ ̲I̲n̲s̲t̲a̲l̲l̲a̲t̲i̲o̲n̲s̲ ̲(̲o̲p̲t̲i̲o̲n̲)̲

         The AE-installations comprise up to 10 AE workstations
         and the Interface (signal cables) with the computers.
         The type of the workstations is TBD.



2.4.4    T̲y̲p̲i̲c̲a̲l̲ ̲L̲a̲y̲o̲u̲t̲

         a)  A typical layout of the ZVA computer area are shown
             in figure 2.4-1. The equipment shown comprises:

             -   Pos P1-P5 dual main processor mounted in 5
                 standard 19" racks.

             -   One position (Table) with one system console.
                 The console comprises a visual display unit
                 with keyboard and hardcopy printer.

             -   Four 300 MB SMD disc drives, selfcontained.





















































                    ZVA Computer Area
                      TYPICAL LAYOUT
                       Figure 2.4-1



         b)  The layout reflects the floor space required by
             cabinets and operator position. The access dimensions
             for racks and terminal equipment are shown in figure
             2.4-2 and 2.4-3. The racks and disc cabinets are
             positioned such that sufficient clearance is maintained
             for access to the front and rear of the equipment.
             Otherwise, only few constraints as to the placement
             of the equipment exist. The final layout will take
             into account human factors, segregation of functional
             activities, access for maintenance and other considerations
             or preferences of the operating personnel.

             One of the tasks to be performed at the site survey
             is to work out the optimal layout in conjunction
             with customer.


















































          RACK ASSEMBLIES, DIMENSION AND ACCESS
                       FIGURE 2.4-2

















































                    TERMINAL EQUIPMENT
         TYPICAL LAYOUTS AND ACCESS REQUIREMENTS
                       FIGURE 2.4-3



         c)  It is anticipated that the equipment room will
             be provided with a computer floor. The heaviest
             rack is well within the standard floor load limit
             of 1000 Kp/m…0e…2…0f… for the computer floor as can be
             seen from the following calculation:

             Floor load of the heaviest rack:

             W̲e̲i̲g̲h̲t̲ ̲ ̲ ̲ ̲ ̲ ̲= ̲ ̲ ̲ ̲ ̲ ̲2̲6̲0̲ ̲k̲g̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ = 413 Kg/sq.mtrs
             Floor Space  0.6 x 1.05 sq.metres

             Since the rack is provided with access space at
             front and rear, the distributed floor load is considerable
             smaller. Equipment weight and dimensions are given
             in table 2.4-4.

         EQUIPMENT         UNIT       ̲ ̲ ̲ ̲U̲N̲I̲T̲ ̲S̲I̲Z̲E̲ ̲C̲M̲ ̲ ̲ ̲ ̲ ̲ ̲A̲C̲C̲E̲S̲S̲
                                     ̲C̲M̲ ̲
                           WEIGHT
         POS               KG        WIDTH  DEPTH  HEIGHT  FRONT  REAR
         NO  ITEM
          ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
         ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

         P1  Proc.Rack     260       60     105    180     120    100

         P2  Proc.Rack     210       60     105    180     120    100

         P3  Proc.Rack     260       60     105    180     120    100

         P4  Proc.Rack     210       60     105    180     120    100

         P5  Proc.Rack     260       60     105    180     120    100

         SC  Table          30       140     80     70     100    
                                                                  
                                                                  5

         SC  VDU            35       48      76     43     100    
                                                                  15

         SC  Printer        27       60      55     25     100    
                                                                  15

         DISC 300 MB       252       59      92     92     100    100

         DISC 300 MB       252       59      92     92     100    100

         DISC 300 MB       252       59      92     92     100    100

         DISC 300 MB       252       59      92     92     100    100


                    ZVA COMPUTER AREA
             EQUIPMENT WEIGHT AND DIMENSIONS
                       TABLE 2.4-4


         c)  The equipment is cooled by fans with intake in
             the front and exhaust at the top as shown in figure
             2.4-5. The heat dissipation figures are given in
             table 2.4-6.

         d)  Power to the equipment is fed from individual fuse
             protected 220 VAC outlets. It is anticipated that
             the power is supplied from a no break (UPS) system.

             The equipment will operate within the following
             AC power limits:

             Voltage:    220 VAC single phase +/- 10 per cent.

             Frequency:  50 HZ +/- 4 per cent

             Except for the proposed CDC disc drives which will
             require the following limits in order to operate
             without degraded performance:

             Voltage:    220 VAC single phase + 6 per cent -
                         10 per cent.

             Frequency:  50 HZ + 1 per cent - 2 per cent.




         e)  E̲n̲v̲i̲r̲o̲n̲m̲e̲n̲t̲a̲l̲ ̲S̲p̲e̲c̲i̲f̲i̲c̲a̲t̲i̲o̲n̲s̲

             The CR80 Computer equipment is designed to operate/comply
             with the following:

             D̲e̲f̲i̲n̲i̲t̲i̲o̲n̲s̲

             o   Operating:      These limits apply to equipment
                                 installed as specified and
                                 operating in a normal office
                                 or computer room environment.

             o   Storage:        The limits apply to equipment
                                 properly packed and protected
                                 against dust, moisture, condensed
                                 water etc.

             o   Transportation: These limits apply to equipment
                                 properly packed for export.

             T̲e̲m̲p̲e̲r̲a̲t̲u̲r̲e̲

             o   Operating:      15…0e…o…0f… C to 32…0e…o…0f…
                                 Maximum rate of change
                                 6…0e…o…0f… per hour


             o   Storage/Trans-  - 40…0e…o…0f… to 70…0e…o…0f…C
                 portation:

             H̲u̲m̲i̲d̲i̲t̲y̲

             o   Operating:      20 per cent to 80 per cent
                                 RH non condensing. Maximum
                                 rate of change 10 per cent
                                 RH per hour.

                                 Absolute water content in the
                                 room air shall be limited to
                                 22g water per cubic meter of
                                 air.

             o   Storage/Trans-  10 per cent to 90 per cent
                                 non
                 portation:      condensing.

             A̲l̲t̲i̲t̲u̲d̲e̲

             o   Operating:      0 to 2000 m.

             o   Storage/Trans-  0 to 10.000 m.
                 portation:


             V̲i̲b̲r̲a̲t̲i̲o̲n̲

             o   Operating and   5 Hz to 50 Hz constant dis-
                 Storage:        placement of 0.02 mm.

                                 50 Hz smooth crossover
                                 50 Hz - 350 Hz constant acceleration
                                 0.2 g.

             o   Transportation: 5 Hz to 350 Hz constant acceleration
                                 1.5 g.

             S̲h̲o̲c̲k̲

             o   Operating and   1g, half sine wave, 10 ms duration.
                                 Not to be repeated more often
                                 than one per 10 seconds.

             o   Transportation: 25g, half sine wave, 10 ms
                                 duration.
















































                RACK ASSEMBLIES - AIRFLOW
                       FIGURE 2.4-5






                  E̲L̲E̲C̲T̲R̲I̲C̲A̲L̲ ̲R̲E̲Q̲U̲I̲R̲E̲M̲E̲N̲T̲S̲                 A̲I̲R̲
                 ̲C̲O̲O̲L̲I̲N̲G̲…06…1    …02…   …02…   …02…     …02…    …02…      …02…      …02…   
                   …02…      …02…      …02…    …02…     

Pos.     Description Qty.  Volts     Wires  Phase  Per     Total  Per   Total
No.                                                U̲n̲i̲t̲    ̲
                                                   ̲ ̲ ̲ ̲     Unit
                                                           Kcal/
                                                   W       Kw     Kcal/
                                                                  hour
                                                                  hour
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…06…1    …02…   …02…   …02…     …02…    …02…      …02…      …02…      …02…      …02…
      …02…    …02…     

P1       PROC RCAK   1     220       2x3    2      2900    2.9    2500  2500

P2       PROC RACK   1     220       2x3    2      2400    2.4    2060  2060

P3       PROC RACK   1     220       2x3    2      2900    2.9    2500  2500

P4       PROC RACK   1     220       2x3    2      2400    2.4    2060  2060

P5       PROC RACK   1     220       2x3    2      2900    2.9    2500  2500

DISC     300 MB      4     220       3      1      1600    6.40   1375  5500
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

Total                                                      19.90  
                                                                  
                                                                  
                                                                  
                                                                  17120















         CENTRAL COMPUTER, FACILITY REQUIREMENTS
                       TABLE 2.4-6



         f)  The physical characteristics including power and
             environment conditions for the terminal equipment
             to be installed in the FMZ area are specified in
             the Terminal equipment data package appendixed
             to this proposal.

             The Total Power Consumption and Heat Dissipation
             of the proposed equipment are specified in table
             2.4.7 through 2.4.16.




                     POWER CONSUMPTION(KW)  HEAT DISSIPATION(Kcal/Hour)
EQUIPMENT        QTY PER UNIT     TOTAL     PER UNIT        TOTAL
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲

C̲E̲N̲T̲R̲A̲L̲ ̲C̲O̲M̲P̲U̲T̲E̲R̲

CR80 + DISCS    1    19,900     19,900     17,120          17,120

S̲Y̲S̲T̲E̲M̲ ̲C̲O̲N̲S̲O̲L̲E̲

CR16 VDU        1     0,250      0,250        215             215
PT88 PRINTER    1     0,030      0,030         25              25
B-1000          1     0,600      0,600        515             515

C̲R̲Y̲P̲T̲O̲ ̲S̲Y̲S̲T̲E̲M̲

GNT28 PTR       1    0,030      0,030          25              25
PT88 PRINTER    1    0,030      0,030          25              25
CR 16 VDU       2    0,250      0,500         215             430
XTA             100  0,050      5,000          43           4,300
XAB             1    0,050      0,050          43              43
WALL OUTLET     210  0,010      2,100           8,6         1,806
GNT 28 PTR      1    0,030      0̲,̲0̲3̲0̲          26            ̲ ̲ ̲2̲6̲

                     TOTAL     2̲8̲,̲5̲2̲0̲                      2̲4̲,̲5̲3̲0̲


                           TABLE 2.4-7

                  LKSAA CENTRAL COMPUTER SYSTEM
                            (AREA 10)


                     POWER CONSUMPTION(KW)  HEAT DISSIPATION(Kcal/Hour)
EQUIPMENT        QTY PER UNIT     TOTAL     PER UNIT        TOTAL
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲

CR16            8    0,250      2,000      215             1720
                                 ̲ ̲ ̲ ̲ ̲ ̲ ̲                     ̲ ̲ ̲ ̲ ̲ ̲

                     TOTAL      2̲,̲0̲0̲0̲                      1̲7̲2̲0̲



                           TABLE 2.4-8


                 LKSAA MESSAGE SERVICE OPERATORS
                            (AREA 16)




                     POWER CONSUMPTION(KW)  HEAT DISSIPATION(Kcal/Hour)
EQUIPMENT        QTY PER UNIT     TOTAL     PER UNIT        TOTAL
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲

GNT28, PTR      4    0,030      0,120       25             100
GNT3601,PTP     4    0,060      0,240       50             200
PT88 PRINTER    4    0,030      0̲,̲1̲2̲0̲       25             1̲0̲0̲

                     TOTAL      0̲,̲4̲8̲0̲                      4̲0̲0̲


                           TABLE 2.4-9

                   LKSAA TAPE IN/OUT POSITION
                           (AREA 6/15)


                     POWER CONSUMPTION(KW)  HEAT DISSIPATION(Kcal/Hour)
EQUIPMENT        QTY PER UNIT     TOTAL     PER UNIT        TOTAL
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲

M̲S̲G̲E̲ ̲S̲E̲R̲V̲I̲C̲E̲ ̲O̲P̲.

CR16            1    0,250      0,250        215             215

M̲S̲G̲E̲ ̲D̲I̲S̲T̲R̲.̲O̲P̲.̲  

CR16            1    0,250      0,250        215             215
PT88 PRINTER    1    0,030      0,030         25              25

S̲E̲C̲U̲R̲I̲T̲Y̲ ̲L̲O̲6̲ ̲P̲O̲S̲.

PT88 PRINTER    1    0,030      0,030         25              25

D̲O̲C̲.̲ ̲P̲R̲I̲N̲T̲G̲ ̲S̲Y̲S̲.

RX 2700         2    1,200      2̲,̲4̲0̲0̲      1,150           2̲,̲3̲0̲0̲

                     TOTAL      2̲,̲9̲6̲0̲                      2̲,̲7̲8̲0̲


                          TABLE 2.4-10

                      LKSAA MESSAGE SYSTEMS
                            (AREA 12)




                     POWER CONSUMPTION(KW)  HEAT DISSIPATION(Kcal/Hour)
EQUIPMENT        QTY PER UNIT     TOTAL     PER UNIT        TOTAL
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲

COLOUR GRAPHIC
8001            1    0,250      0,250      215             215
PT88            1    0,030      0̲,̲0̲3̲0̲       25              ̲2̲5̲

                     TOTAL      0̲,̲2̲8̲0̲                      2̲4̲0̲


                          TABLE 2.4-11

                  LKSAA SYSTEM SUPERVISOR POS.
                            (AREA 13)


                     POWER CONSUMPTION(KW)  HEAT DISSIPATION(Kcal/Hour)
EQUIPMENT        QTY PER UNIT     TOTAL     PER UNIT        TOTAL
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲

DCD1740 MONITOR 4    0,090      0,360       80             320
TELETEX         1    0,240      0̲,̲2̲4̲0̲      205             2̲0̲5̲

                     TOTAL      0̲,̲6̲0̲0̲                      5̲2̲5̲


                          TABLE 2.4-12

                      LKSAA OTHER EQUIPMENT




                     POWER CONSUMPTION(KW)  HEAT DISSIPATION(Kcal/Hour)
EQUIPMENT        QTY PER UNIT     TOTAL     PER UNIT        TOTAL
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲

CR 16 VDU       2    0,250      0,500         215             430
XTA             20   0,050      1,000          43             860
XCP             4    0,100      0,400          86             344
XCT             2    0,100      0,200          86             172
WALL OUTLET     62   0,010      0,620           8,6           533
MODEM           4    0,100      0̲,̲4̲0̲0̲          86           ̲ ̲ ̲3̲4̲4̲

                     TOTAL      3̲,̲1̲2̲0̲                       ̲2̲,̲6̲8̲3̲


                          TABLE 2.4-13

                   LKSAA RADIO CENTRAL STATION
                            (AREA 9)


                     POWER CONSUMPTION(KW)  HEAT DISSIPATION(Kcal/Hour)
EQUIPMENT        QTY PER UNIT     TOTAL     PER UNIT        TOTAL
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲

XTA             26   0,050      1,300          43           1,118
XCP             2    0,100      0,200          86             172
XCT             2    0,100      0,200          86             172
WALL OUTLET     30   0,010      0,300           8,6           258
MODEM           2    0,100      0̲,̲2̲0̲0̲          86           ̲ ̲ ̲1̲7̲2̲

                     TOTAL      2̲,̲2̲0̲0̲                       ̲1̲,̲8̲9̲2̲


                          TABLE 2.4-14

                     LKSAA RADIO TX-STATION


                     POWER CONSUMPTION(KW)  HEAT DISSIPATION(Kcal/Hour)
EQUIPMENT        QTY PER UNIT     TOTAL     PER UNIT        TOTAL
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲

XTA             32   0,050      1,600          43           1,376
XCP             2    0,100      0,200          86             172
XCT             2    0,100      0,200          86             172
WALL OUTLET     36   0,010      0,360           8,6           310
MODEM           2    0,100      0̲,̲2̲0̲0̲          86           ̲ ̲ ̲1̲7̲2̲

                     TOTAL      2̲,̲5̲6̲0̲                       ̲2̲,̲2̲0̲2̲


                          TABLE 2.4-15
                        LKSAA RX-STATION




                     POWER CONSUMPTION(KW)  HEAT DISSIPATION(Kcal/Hour)
EQUIPMENT                         TOTAL                     TOTAL
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲

CENTRAL COMPUTER (AREA 10)      28,520                     24,530
MESSAGE SERVICE OP. (AREA 16)    2,000                      1,720
TAPE IN/OUT POS. (AREA 6/15)     0,480                        400
MESSAGE SYSTEMS (AREA 12)        2,960                      2,780
SYSTEM SUPERVISOR (AREA 13)      0,280                        240
OTHER EQUIPMENT                  0,600                        525
RADIO CENTRAL (AREA 9)                      ̲3̲,̲1̲2̲0̲                    
                                                                     ̲2̲,̲6̲8̲3̲

                TOTAL           3̲7̲,̲9̲6̲0̲                     3̲2̲,̲8̲7̲8̲


                          TABLE 2.4-16

         FMZ TOTAL POWER CONSUPTION AND HEAT DISSIPATION



2.4.5    I̲n̲s̲t̲a̲l̲l̲a̲t̲i̲o̲n̲ ̲a̲n̲d̲ ̲C̲a̲b̲l̲i̲n̲g̲ ̲R̲e̲q̲u̲i̲r̲e̲m̲e̲n̲t̲s̲.̲



2.4.5.1  G̲e̲n̲e̲r̲a̲l̲



         a)  Contractor will provide and install the equipment
             specified in section 2.4.1 and 2.4.2. The equipment
             will be installed in accordance with the customer
             approved Equipment Installation Drawings (EID).

         b)  The installation of the workstation cables and
             the 10 AE workstations (option) are to be made
             in accordance with the criterias defined in AMSG
             719.

         c)  Customer will prepare the facilities in accordance
             with the approved site preparation requirements.
             This includes installation of metallic conduits
             for the Local Area Network (option) according to
             contractors specifications.



2.4.5.2  F̲M̲Z̲ ̲R̲o̲o̲m̲s̲:̲

         a)  Customer will provide the facilities specified
             in the I.F.B. or "Lastenheft". The proposal is
             based on that the FMZ is equipped with computer
             floors and that contractors installations in this
             area are not subject to AMSG 719. It is assumed
             that customer provides a UPS system for at least
             the ZVA and Crypto Computer.

         b)  Contractor will install all signal cables connected
             to his equipment below the raised floors in customer
             installed cable ducts.

         d)  Customer will provide power and signal line filtering
             to and from the FMZ area if so required by AMSG
             719.

         e)  The Line Switching facility (Schaltzplatz and Handvermittung)
             is regarded as the division line between Contractor
             and Customer concerning cabling. Customer will
             provide and run the communication cables (Tx, Ttx,
             Funk etc. ) from modems and cryptos and all other
             cables from Customer furnished equipment up to
             the line switch, except for the cable connections
             from the telex terminals to the Handvermittlung,
             which will be provided and run by the contractor.



             Contractor will install the line switch and terminate
             all cables at the line switch panels. Contractor
             will install all cables from the line switch to
             the ZVA computer and terminal equipment delivered
             by Contractor.

         The signal cable connections are to be performed as
         follows:

         1.  Standard RS 232C cables between the ZVA Computer
             and the "Schaltplatz". CR will provide cables and
             connectors and install and terminate cables. Conduits,
             if requires, will be provided and installed by
             AA.

         2.  Standard RS 232C cables between the Schaltplatz
             and the Handvermittlung. CR will provide cables
             and connectors and install and terminate cables.
             Conduits, if required, will be provided and installed
             by AA.

         3.  Standard RS 232C cables between CR provided terminal
             equipment and the Handvermittlung. CR will provide
             cables and connectors and install and terminate
             cables. Conduits, if required, will be provided
             and installed by AA.

         4.  Standard RS 232 C cables between AA provided telex
             terminals and the Handvermittlung. CR will provide
             cables and connectors, install cables and terminate
             cables at AA equipment and at the Handvermittlung.
             Conduits, if required, will be provided and installed
             by AA.

         5.  Communication cables to be connected to the ZVA
             computer (Standard RS 232C cables from modems to
             Schaltplatz). AA will provide cables and connectors,
             install cables and terminate cables at the AA equipment.
             CR will terminate cables at the Schaltplatz. Conduits
             if requires will be provided and installed by AA.

         6.  Red and black RS 232C cables between crypto-units
             and the Schaltplatz. AA will provide Cables and
             Connectors and install and terminate cables. CR
             will terminate cables at the Schaltplatz. Conduits
             if required will be provided and installed by AA.



         f)  All cables installed by CR in the FMZ and Computer
             room shall be of a halogenfree type, in accordance
             with regulations from the Bundesbaudirektion.

2.4.5.3  C̲a̲b̲l̲e̲ ̲R̲o̲u̲t̲i̲n̲g̲ ̲t̲o̲ ̲A̲E̲-̲W̲o̲r̲k̲s̲t̲a̲t̲i̲o̲n̲s̲ ̲(̲O̲p̲t̲i̲o̲n̲)̲

         a)  Contractor will install the cables in conduits
             provided and installed by customer.

         b)  Contractor has based his proposal on installation
             often AE workstations including Standard V24 Interface
             Cabling (refer to chapter 4). The cables are to
             be routed from the ZVA Computer in the FMZ to the
             AE workstations. The cable are assumed to be run
             in conduits installed in the corridors. The cable
             routing and location of AE workstations are to
             be decided on a Site survey.



2.4.5.4  A̲E̲ ̲W̲o̲r̲k̲s̲t̲a̲t̲i̲o̲n̲s̲ ̲o̲r̲ ̲C̲e̲l̲l̲s̲ ̲(̲O̲p̲t̲i̲o̲n̲)̲

         a)  Customer will provide the facilities specified
             in the I.F.B. or "Lastenheft".

         b)  Customer will provide power and ground in accordance
             with AMSG 719 for these rooms. Customer is required
             to install a power outlet with ground in the vicinity
             of each terminal device.

         c)  Contractor will connect the terminals to the power
             outlets and to the Interface Cable from the Computer.



2.4.5.5  R̲a̲d̲i̲o̲ ̲C̲o̲n̲t̲r̲o̲l̲ ̲C̲e̲n̲t̲r̲e̲

         a)  Customer will provide the facilities specified
             in the I.F.B or "Lastenheft". It is assumed that
             the room is equipped with computerfloor.

         b)  Customer will provide power and ground according
             to contractors specifications.

         c)  Contractor will provide, terminate and install
             all signal cables in the radio control centre,
             including the x-net for the workstations. Customer
             will provide the appropriate plugs for customer
             provided equipment.



         R̲E̲ ̲a̲n̲d̲ ̲T̲X̲ ̲S̲t̲a̲t̲i̲o̲n̲s̲

         a)  Customer will provide the facilities specified
             in the I.F.B or "Lastenheft".

         b)  Customer will provide power and ground according
             to contractors specifications.

         c)  Contractor will provide, terminate and install
             all signal cables at the RX and TX sites, except
             the antenna cables for the RX and TX equipment.
             Customer will provide the appropriate plugs for
             customer provided equipment.



2.4.6    P̲h̲y̲s̲i̲c̲a̲l̲ ̲L̲o̲c̲a̲t̲i̲o̲n̲ ̲o̲f̲ ̲t̲h̲e̲ ̲E̲q̲u̲i̲p̲m̲e̲n̲t̲ ̲i̲n̲ ̲t̲h̲e̲ ̲F̲M̲Z̲

         In order to obtain a functional layout of the equipment
         in the FMZ, CR proposes that the equipment is located
         as shown on figure 2.4-17. As one can see, the only
         major change to the original layout is the location
         of the radio control centre and the handvermittlung.
         The reason for this change is the fact that the radio
         control equipment will have some high speed connections
         to the central computer via the patch and cryptoes.
         These lines have a length restriction according to
         R5232C which would be difficult to meet with the original
         location of the radio control centre. Taking into consideration
         that the handvermittlung deals only with low speed
         lines, CR see no technical problems in the new position
         proposed.














































                      FIGURE 2.4.-17
            FMZ PHYSICAL LOCATION OF EQUIPMENT



2.5      D̲O̲C̲U̲M̲E̲N̲T̲A̲T̲I̲O̲N̲



2.5.1    D̲o̲c̲u̲m̲e̲n̲t̲a̲t̲i̲o̲n̲ ̲R̲e̲q̲u̲i̲r̲e̲m̲e̲n̲t̲ ̲A̲n̲a̲l̲y̲s̲i̲s̲



2.5.1.1  G̲e̲n̲e̲r̲a̲l̲ ̲R̲e̲q̲u̲i̲r̲e̲m̲e̲n̲t̲s̲

         Contractor shall supply all necessary information for
         Operation, Maintenance and Repair of the system.

         Basic documentation shall be written in the German
         language.

         The documentation shall contain:

         -   Overview
             o   Documentation Tree
             o   System Overview
             o   Hardware Overview
             o   Software Overview

         -   System Description

         -   Message Flow Description

         -   User Manuals

         -   Operator Manuals including all Error Messages and
             corrective procedures

         -   Functional Description and As Built documentation
             for Hardware and Software

         -   Interface Control Documents

         -   Maintenance Manuals for Hardware and Software



2.5.1.2  P̲r̲o̲g̲r̲a̲m̲ ̲D̲o̲c̲u̲m̲e̲n̲t̲a̲t̲i̲o̲n̲ ̲R̲e̲q̲u̲i̲r̲e̲m̲e̲n̲t̲s̲

         The German language shall be used for the documentation
         of the Application Programs.

         Each program and module shall contain:


         -   A short description

         -   Functional Flow

         -   Data flow (Input/Output parameters, global and
             local data)

         -   Connection to other programs (f.ex. call of and
             by a module)

         -   Test plan, Test Documentation

         -   Error handling

         -   Complete program listings

         A typical example of program documentation shall be
         supplied with the proposal, representative for the
         contractors production and quality of the documentation.



2.5.1.3  W̲o̲r̲k̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲s̲ ̲R̲e̲q̲u̲i̲r̲e̲m̲e̲n̲t̲s̲

         Work procedures for users and operators shall conform
         to the following requirements:

         -   German language shall be used

         -   Generally understandable

         -   Short and unambigous

         -   With examples

         -   Maximum 1 page per work procedure

         -   Flexible breakdown

         -   Loose pages in binders

         -   Extensive Keyword Index

         -   Handy and solid document

         -   Short instructions to be placed at work positions




2.5.1.4  O̲p̲e̲r̲a̲t̲i̲o̲n̲a̲l̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲s̲ ̲R̲e̲q̲u̲i̲r̲e̲m̲e̲n̲t̲s̲

         For operating the equipment is required:

         -   German language shall be used

         -   Generally understandable

         -   Short and unambigous

         -   Extensively illustrated

         -   Maximum 1 page per operational procedure

         -   Handy and solid document

         -   Short instruction/checklist for correcting failures
             to be placed at the equipment



2.5.2    D̲o̲c̲u̲m̲e̲n̲t̲a̲t̲i̲o̲n̲ ̲P̲r̲o̲p̲o̲s̲a̲l̲

         The documentation management, the contents and the
         structure of the proposed documentation is described
         in detail in the LKSAA Documentation Plan in Appendix
         B of the technical proposal. Please refer to this Appendix.

         The list below shows the proposed documentation and
         the language to be used for each type of document.
         "G" denotes the German Language, and "E" denotes the
         English language.

                                                 L̲a̲n̲g̲u̲a̲g̲e̲  Q̲t̲y̲

         1   Project Implementation Plan         E         3
         2   System Requirement Specification    G         3
         3   Interface Control Documents         G         3
         4   System Design Specification         E         3
         5   Acceptance Test Plan                G         3
         6   Acceptance Test Specification       G         3
         7   Acceptance Test Procedure           G         3
         8   Acceptance Test Report              G         3
         9   Documentation Plan                  E         3
         10  System Users Manuals                G         3
         11  Network Operator Manuals            G         3
         12  Maintenance Manual                  G         3
         13  Module Description Manuals          E         3
         14  Approved Spare Parts List           E         3


         15  System Description Manuals          G         3
         16  Peripheral Equipment Manuals        E         3
         17  Hardware Assembly Breakdown Manual  E         3
         18  Programming Development Manual      E         3
         19  Software As-Built Documentation     E         3
         20  Training Program Plan               G         3
         21  Site Preparation and
             Installation Document               G         3
         22  Radio Control Operator Manual       G         3
         23  Radio Control Maintenance           G         3
         24  User Reference Card                 G        20

         Above documents will be delivered in the quantity indicated
         at no cost to AA. Before end of SRS phase AA must,
         however, specify the correct quantity of documents
         to be delivered. Quantities exceeding the contractual
         quantity will be changed at 150 DM each document.

         Optionally, documentation proposed in the English language
         can be translated and delivered in the German language
         at a price to be negotiated.
         Work Procedures and Operational Procedures will be
         delivered, supplementing User Manuals and Operator
         Manuals, as described in the Requirements Analysis,
         paragraph 2.5.1.3 and 2.5.1.4



         Examples of program documentation are considered company
         proprietary information and is therefore not supplied
         with this proposal.

         Examples may eventually be shown according to later
         agreements.

         The program documentation method is described in detail
         as Guidelines for Package Design in Volume II, Part
         1, Section 2.6.2. Please refer to this section for
         further information.


2.6      M̲E̲T̲H̲O̲D̲S̲ ̲A̲N̲D̲ ̲T̲O̲O̲L̲S̲


2.6.1    S̲y̲s̲t̲e̲m̲ ̲D̲e̲s̲i̲g̲n̲ ̲a̲n̲d̲ ̲H̲a̲r̲d̲w̲a̲r̲e̲ ̲C̲o̲n̲f̲i̲g̲u̲r̲a̲t̲i̲o̲n̲

         Relevant experience is described in Volume I, section
         2.2.6.1



2.6.2    S̲o̲f̲t̲w̲a̲r̲e̲ ̲D̲e̲s̲i̲g̲n̲,̲ ̲D̲e̲v̲e̲l̲o̲p̲m̲e̲n̲t̲ ̲a̲n̲d̲ ̲I̲n̲t̲e̲g̲r̲a̲t̲i̲o̲n̲



2.6.2.1  D̲e̲v̲e̲l̲o̲p̲m̲e̲n̲t̲ ̲M̲e̲t̲h̲o̲d̲



2.6.2.1.1    S̲y̲s̲t̲e̲m̲ ̲D̲e̲v̲e̲l̲o̲p̲m̲e̲n̲t̲ ̲B̲a̲s̲e̲l̲i̲n̲e̲s̲

         The following sections describe the baselines applicable
         at the system level.

         At lower levels than the system level a number of baselines
         are defined.

         The software implementation will be divided into a
         number of sub-phases where each completed subphase
         will establish a baseline.

         The system development cycle is presented in Figure
         2.6.2-1

         Whenever this section specifies CR internal reviews,
         AA participation is assumed.























































                      Figure 2.6.2-1
                 System Development Cycle


2.6.2.1.2    S̲y̲s̲t̲e̲m̲ ̲R̲e̲q̲u̲i̲r̲e̲m̲e̲n̲t̲ ̲B̲a̲s̲e̲l̲i̲n̲e̲

         The system requirement definition phase will be completed
         by a System Requirements Review (SRR). The objective
         of this review is to ensure the compliance and completeness
         of the system requirements. After AA's approval of
         the System Requirements Specification, and associated
         Interface Control Documents, these will establish the
         baseline for all subsequent development activities.



2.6.2.1.3    S̲y̲s̲t̲e̲m̲ ̲D̲e̲s̲i̲g̲n̲ ̲B̲a̲s̲e̲l̲i̲n̲e̲

         During the system design phase, the system requirements
         are broken down into subsystems and components of software
         to ensure

         a)  that the system design specification represents
             a complete and optimal synthesis of the system
             requirements

         b)  that the system is complete and feasible, and

         c)  that a technical direction is provided to the implementation

         An internal CHRISTIAN ROVSING A/S System Design Review
         (SDR) will be scheduled.

         After approval of the system design specification by
         the LKSAA program management, this will establish the
         design requirement baseline.



2.6.2.1.4    P̲r̲e̲l̲i̲m̲i̲n̲a̲r̲y̲ ̲D̲e̲s̲i̲g̲n̲ ̲B̲a̲s̲e̲l̲i̲n̲e̲

         The actual design of subsystems and software components
         identified during the system design will be divided
         into two phases; the preliminary phase, and the detailed
         design phase. Due to the schedule it will be considered
         to amalgamate the Preliminary Design Baseline and the
         Detailed Design Baseline.

         The preliminary design baseline (subsystem design)
         is established prior to detailed design in order to



         a)  evaluate the progress and technical adequacy of
             the selected design approach

         b)  determine its compatibility with the requirements,
             and

         c)  establish the existence and compatibility of the
             physical and functional interfaces between system
             components

         During the system design phase subsystems have been
         defined and requirements/functions have been allocated.

         The objectives related to the preliminary design are
         to establish the following baseline documents:

         -   Specification of packages within the subsystems

         -   Allocation of requirements/functions to all packages

         -   Specification of detailed interfaces between subsystem
             and packages

         -   Definition of data

         -   Specification of Data Base Design 

         The level of documentation applied to the subsystems
         is defined in Subsystem Documentation Standard.

         The subsystem/package interfaces will be documented
         in a LKSAA Application Software Interface Control Document.
         Each interface will be specified to the level of the
         applied calling mechanism and passed parameters.

         Global data and files will be documented in a LKSAA
         Software Data Definition Document. Each data item will
         be specified to at least the logical level.

         The Data Base Design Document will define all files
         and their logical contents. In addition the files will
         be allocated to medias in order to obtain optimal performance.

         The preliminary design baseline will be established
         by a Preliminary Design Review (PDR) involving LKSAA
         software team as well as the CR A/S System Engineering
         Department and Quality Assurance Department.



         When the CR A/S management team has approved the baseline
         the detailed design will be initiated.



2.6.2.1.5    D̲e̲t̲a̲i̲l̲e̲d̲ ̲D̲e̲s̲i̲g̲n̲ ̲B̲a̲s̲e̲l̲i̲n̲e̲

         Before the actual implementation is initiated, a Detailed
         Design Review (DDR) internal Christian Rovsing A/S
         will be conducted to

         a)  determine that the detailed design satisfies the
             design requirement baseline.

         b)  establish the exact interface relationship between
             the system components

         After approval the detailed design forms the baseline
         for implementation of the actual software components.

         The documents which represents the baseline for detailed
         design are those produced during preliminary design
         as well as those applicable to the preliminary design.

         The objective with detailed design baseline is to establish
         "as-to-be-coded" design documentation.
         The subsystem design will be designed in further details
         and will be documented in a set of package design documents.

         Packages will be broken down into processes and software
         modules.

         The Software Interface Control Document will be expanded
         to contain a detailed description of each parameter
         in each of the package/subsystem interfaces.

         Likewise the Software Data Definition Document will
         be expanded to contain a detailed definition of each
         data item.

         In order to maintain a current and accurate design
         specification during this and subsequent phases the
         concept of Unit Development Folders (UDFs) will be
         applied.



         The fundamental element in the software design and
         development is the Unit Development Folder (UDF), which
         is an essential working tool for the program developer.

         The UDF begins with the definition of requirements
         to be implemented within the unit, from which preliminary
         and detailed design description is derived and unit
         development test plan(s) describing the development
         testing activity. To this is added a list of test cases
         that will demonstrate that the unit meets the requirements
         and is free of errors and anomalies.

         The detailed design baseline will be established by
         Detailed Design Reviev (DDR) involving the LKSAA software
         team as well as the CR A/S System Engineering Department
         and the Quality Assurance Department.



2.6.2.1.6    I̲m̲p̲l̲e̲m̲e̲n̲t̲a̲t̲i̲o̲n̲ ̲B̲a̲s̲e̲l̲i̲n̲e̲s̲

         When the Software components have been produced these
         shall be tested and integrated into subsystems. The
         baselines are established when the subsystems have
         been approved by the CR A/S QA Department.



2.6.2.1.6.1 C̲o̲d̲e̲ ̲a̲n̲d̲ ̲U̲n̲i̲t̲ ̲T̲e̲s̲t̲ ̲B̲a̲s̲e̲l̲i̲n̲e̲

         The objective of this phase is to produce software
         units which are tested to the extend that they are
         ready for software subsystem integration and test.

         The concept "unit" means an entity consisting of software
         modules, which makes up a functional area.

         The criteria for being ready is that they can pass
         the test defined in the detailed design baseline and
         the software test plan.

         During the process, the design description may be revised
         to make it reflect the coded unit. Thus, as the unit
         evolves from its initial checkout state to a completely
         tested segment of code, the UDF progresses from a "code-to"
         specification to an "as-built" specification. By the
         time the unit is ready for integration with other units,
         the product specification for the unit is complete,
         including updated flow charts or structured pseudo
         code.



         An overview of the contents of UDF test specifications
         and procedures are presented in the following.

         Unit testing involves the testing of each module using
         selected inputs, executing the code, and evaluating
         module outputs.  The primary intent of unit testing
         is to prove that the module solves the right problem.
          

         There are standards of measurement of success of testing
         which always is used to insure that sufficient detailed
         unit testing has been accomplished.  

         The test specification and procedures shall contain
         a description of each test case to be employed in testing
         the unit.  The description must identify any test tools
         or drivers used, a listing of all required test inputs
         to the unit and their values, and the expected output
         
         and acceptance criteria, including numerical outputs
         and other demonstrable results.  Test cases shall address
         the functional capabilities of the unit, and a matrix
         shall be placed into this section which correlates
         requirements and functional capabilities to test cases.
          This matrix will be used to demonstrate that all requirements,
         partial requirements, and functional capability list
         of the unit have been tested.

         Guidelines for evaluation of unit test effectiveness
         is presented overleaf.


 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

PROPERTY         ASSESSMENT
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
Numerical and        It is necessary to demonstrate that the
Mathematical     mechanization of the algorithms and models
Accuracy         meet the prescribed quantified accuracy requirements
                 delineated when preparing the acceptance criteria
                 earlier in development.

Logical Branches All critical logical branches and error conditions
                 in the object coding should have been executed
                 at least once successfully.  The remaining
                 inter-module linkages will be exercised during
                 integration test. If a correction is made,
                 all critical logical branches must be checked
                 again.

Range of             The function being performed by the module
                     
Variables            should be exercised at the expected extremes
                     of the range of input variables and confirmed
                     expected outputs need to be checked.  Unusual
                     input data points and points or ranges
                     of potential failure should be verified.

Computational        All special conditions in the code that
                     could
Integrity            cause erroneous computations to occur need
                     to be checked.  This includes such items
                     as dividing by zero, differencing two nearly
                     equal large numbers, exceeding table limits,
                     etc.

Resource         The timing and core utilization need to be
                 
Utilization      verified to insure that they are consistent
                 with design constraints and overall system
                 requirements.

 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲



         Before integration of "units" a Test Readiness Review
         (TRR) will be held to ensure that the UDFs are complete,
         that the "units" meet their specifications, and that
         the "units" have been exhaustively tested.

         Units shall be approved by the Work Package Manager,
         Software Manager and Quality Assurance.

         After approval of the units these make up the baseline
         from which integration and test are initiated.



2.6.2.1.6.2 S̲u̲b̲s̲y̲s̲t̲e̲m̲ ̲I̲n̲t̲e̲g̲r̲a̲t̲i̲o̲n̲ ̲a̲n̲d̲ ̲T̲e̲s̲t̲ ̲B̲a̲s̲e̲l̲i̲n̲e̲

         The objective of this baseline is to achieve fully
         integrated and tested subsystems to be delivered to
         LKSAA System Engineering for system integration and
         verification.

         The subsystem integration is based on the software
         integration plan and associated test specifications
         and procedures.

         Integration testing verifies the linkages between the
         software modules which make up entire functions, programs,
         and system. Integration testing begins when individual
         units/modules start to be merged together according
         to the top-down methodology described below.

         Integration testing is satisfied when the entire program
         responds properly and the module to module interfaces
         are shown to have been defined and implemented correctly,
         in addition to execution timing and core storage assessment.

         It is during integration testing that it is shown that
         varied inputs representative of the ranges required
         for overall performance produce the expected results
         and that the total software package meets the performance
         and design requirements.

         The sequence of integration of the modules, units,
         elements or subroutines into larger and larger testable
         packages or groups is simply the application of the
         top-down concept to achieve a systematic verification
         process.



         The t̲o̲p̲-̲d̲o̲w̲n̲ approach to integration starts with the
         testing of the highest level system segment once it
         is coded. Since this segment will normally invoke or
         include lower level segments, code must exist for the
         next lower level segment. This code, called a program
         stub, may be empty, may output a message for debugging
         purposes each time it is executed, or may provide a
         minimal subset of the functions required. These stubs
         are later expanded into full functional segment, which
         in turn require lower level segments. Integration is,
         therefore, a continous activity throughout the development
         process. During testing, the system executes the segments
         that have been completed and uses the stubs where they
         have not been completed. It is this characteristic
         of continous integration that reduces the need for
         special test data drivers. The developing system itself
         can support testing because
         all the code that is to be exectued before the newly
         added segments has previously been integrated and tested
         and can be used to feed test data to the new segments.
         For this reason, most problems are localized to the
         recently added code. As the new segments are tested
         within the developing system, the control architectue
         and system logic are also tested.

         In general top-down offers the following advantages:

         -   simple individual tests

         -   simple identificaiton of suspect areas

         -   no need to develop special versions of any program
             except for all the stubs

         Below some guidelines are presented for developing
         integration test cases to insure that the desired level
         of confidence in the overall software product has been
         obtained from the integration test phase.

         Insure that:

         -   All components are available and that they have
             been unit tested

         -   Module interfaces are completely defined and properly
             implemented

         -   Modules which perform more than one function meet
             applicable requirements and acceptance cirtieria



         -   Necessary inputs and outputs are properly handled

         -   The expected ranges of output are evaluated with
             respect to the input range of variables between
             modules

         -   There are no unsatisfied external references

         -   Program entities change only those other entities
             that have been designed to be changed or that act
             as communication media

         -   Subroutines preserve and restore all common locations
             and register they use, as desired

         -   Shared storage is protected

         -   Communication is maintained between dependent loops
             so that proper sequencing is maintained

         -   Error conditions are detected and properly identified
             in messages

         To establish a baseline and application software, subsystem
         test report will be produced. This will be reviewed
         and approved by CR A/S Quality Assurance Department.
         Upon approval the system integration and test phase
         will be initiated.



2.6.2.1.7    S̲y̲s̲t̲e̲m̲ ̲V̲e̲r̲i̲f̲i̲c̲a̲t̲i̲o̲n̲ ̲B̲a̲s̲e̲l̲i̲n̲e̲

         At the time of completion of system integration and
         verification, a System Verification Review is conducted
         to verify that the system performes as required, and
         that product specification, manuals, and handbooks
         are accurate.



2.6.2.1.8    S̲y̲s̲t̲e̲m̲ ̲A̲c̲c̲e̲p̲t̲a̲n̲c̲e̲ ̲B̲a̲s̲e̲l̲i̲n̲e̲s̲

         The formal system acceptance phase has been separated
         into a number of sub-phases each resulting in a baseline.
         The Acceptance baselines are:



         -   In Plant Software Test baseline (System Factory
             Acceptance Test)

         -   Site Provisional Acceptance baseline

         -   Site Acceptance Test



2.6.2.1.9    I̲m̲p̲l̲e̲m̲e̲n̲t̲a̲t̲i̲o̲n̲ ̲S̲t̲r̲a̲t̲e̲g̲o̲r̲y̲

         This section will address the strategy to be applied
         in order to assure that all requirements will be implemented
         accordingly.

         In order to assure that all requirements are identified
         the LKSAA system requirements identified in the LKSAA
         System Requirements Specification and subsequent ICDs
         will be allocated to the pertinent software subsystems.
         This is done during system design and will be contained
         in a Verification Control Documents.

         To assure that the requirements are implemented in
         the software subsystems/packages the requirements will
         be allocated to each package/module in Unit Development
         Folders (UDF).

         The above requirements allocation will be verified
         during the preliminary/detailed design reviews. All
         the unit/packages test cases shall include testing
         of these requirements. During system integration and
         verification the Verification Control Document will
         be used to track the requirements via the test procedures
         and results.

         To assure that the requirments are i`mplemented in
         the subsystems/items the requirements will be allocated
         to each subsystem/item in the Product specifications
         or the Subsystem Specifications. The detailed design
         review will verify that the requirements are accounted
         for. The test cases developed for the items and subsystems
         will tet the allocated requirements. During the system
         integration and verification the VCD will be used to
         track the requirements.


2.6.2.2  S̲o̲f̲t̲w̲a̲r̲e̲ ̲P̲a̲c̲k̲a̲g̲e̲ ̲D̲e̲s̲i̲g̲n̲

         The design of the application software packages will
         be specified according to the following guidelines.



 PACKAGE DESIGN SPECIFICATION…01……01…TABLE OF CONTENTS OUTLINE

         1  GENERAL
           1.1  PURPOSE AND SCOPE
           1.2  APPLICABLE DOCUMENTS AND PROJECT REFERENCES

             1.2.1  APPLICABLE DOCUMENTS
             1.2.2  PROJECT REFERENCES

           1.3  TERMS AND ABBREVIATIONS
             1.3.1  TERMS
             1.3.2  ABBREVIATIONS

         2  SUMMARY OF REQUIREMENT
           2.1  PACKAGE DESCRIPTION
           2.2  PACKAGE FUNCTIONS
             2.2.1  MAIN FUNCTIONS (NORMAL OPERATION)
             2.2.2  FUNCTIONAL RESPONSIBILITIES
               2.2.2.1  INITIALIZATION, CLOSE DOWN, AND RESTART
               2.2.2.2  CHECK POINTING AND RECOVERY
               2.2.2.3  ERROR DETECTINg AND ERROR HANDLING
               2.2.2.4  INTEGRITY OF OPERATION
               2.2.2.5  DATA COLLECTION (LOG, STATISTICS, AND
                        REPORTS)
               2.2.2.6  SECURITY

           2.3  CHARACTERISTICS
             2.3.1  TIMING
             2.3.2  THROUGHPUT
             2.3.3  FLEXIBILITY
             2.3.4  ACCURACY

         3  ENVIRONMENTS
           3.1  EQUIPMENT
           3.2  SOFTWARE
             3.2.1  SYSTEM SOFTWARE
             3.2.2  DEVELOPMENT SUPPORT SOFTWARE

           3.3  INTERFACES
             3.3.1  EXTERNAL INTERFACES
             3.3.2  PACKAGE INTERFACE



           3.4  FUNCTIONS MAINTAINED BY OTHER PACKAGES

         4  PACKAGE DESIGN
           4.1  PACKAGE OVERVIEW
             4.1.1  FUNCTIONAL SPECIFICATION
             4.1.2  SOFTWARE SPECIFICAION
             4.1.3  DATA FLOW AND CONTROL LOGIC
             4.1.4  PACKAGE DATA
             4.1.5  COMMON DATA
             4.1.6  INTERFACES
               4.1.6.1  EXTERNAL INTERFACES
               4.1.6.2  PACKAGE INTERFACES
               4.1.6.3  SUB-PACKAGE INTERFACES

             4.2.x  SUB-PACKAGE SPECIFICATIONS
               4.2.x.1  FUNCTIONAL SPECIFICATION
               4.2.x.2  SOFTWARE STRUCTURE
               4.2.x.3  DATA FLOW AND CONTROL LOGIC
               4.2.x.4  SUB-PACKAGE DATA
               4.2.x.5  SUB-PACKAGE INTERFACE

           4.3  MEMORY LAYOUT



2.6.2.3  S̲o̲f̲t̲w̲a̲r̲e̲ ̲M̲o̲d̲u̲l̲a̲r̲i̲t̲y̲

         The software packages and subpackages are described
         below. The subpackages will be further divided into
         modules and sub-modules. These are not specified in
         the following.

         L̲K̲S̲A̲A̲ ̲A̲p̲p̲l̲i̲c̲a̲t̲i̲o̲n̲ ̲S̲o̲f̲t̲w̲a̲r̲e̲

         2.1     SUPERVISOR VDU PACKAGE

         2.1.1   Common Package Procedures
         2.1.2   Supervisor VDU Control
         2.1.3   Supervisor Function Control
         2.1.4   Supervisor VDU Dialogue
         2.1.5   Supervisor Retrieval
         2.1.6   Supervisor Completion Report
         2.1.7   Supervisor Process Initializ.

         2.2     SUPERVISOR PRINTER

         2.2.1   Supervisor Print Control
         2.2.2   Delivery Control
         2.2.3   Request Control
         2.2.4   Initialization

         2.3     MESSAGE DISTRIBUTION CONTROL OPERATOR VDU FUNCTIONS

         2.3.1   Common
         2.3.2   Delivery VDU Control
         2.3.3   Delivery Function Control
         2.3.4   Delivery VDU Dialogue
         2.3.5   Delivery Retrieval

         2.4     MESSAGE SERVICE OPERATOR PACKAGE

         2.4.1   Common Package Procedures
         2.4.2   Message Service VDU Control
         2.4.3   Message Service Function Control
         2.4.4   Message Service VDU Dialog
         2.4.5   Message Service Retrieval

         2.5     USER VDU FUNCTION

         2.5.1   Common Package Procedures
         2.5.2   VDU Control
         2.5.3   User Function Control


         2.5.4   VDU Dialogue
         2.5.5   Retrieve
         2.5.6   User Message Access Monitoring
         2.5.7   Initialization

         2.6     USER PRINTER

         2.6.1   Common Procedures
         2.6.2   User Print Control
         2.6.3   Print Output

         2.7     OCR

         2.7.1   Optical Character Reader Subpackage

         3       MESSAGE DISTRIBUTION

         3.1     Message Distribution Subpackage

         4       TRAFFIC HANDLING

         4.1     AAS Analysis
         4.2     ACS Conversion
         4.3     TCS Transport Control
         4.4     ITS Incoming Transprot
         4.5     OTS Outgoing Transport

         5       LOGGING

         5.1     Common
         5.2     Log Collect
         5.3     Log Trace

         6       STORAGE AND RETRIEVAL

         6.1     Common Package
         6.2     Online Storage
         6.3     Online Retrieval
         6.4     Offline Retrieval
         6.5     Dump
         6.6     Supervisor Commands

         7       STATISTICS PACKAGE

         7.1     Common Package
         7.2     Collect
         7.3     Main Program
         7.4     Dump
         7.5     Generation
         7.6     Delivery



         8       TABLE MANAGEMENT

         8.1     Common Procedures
         8.2     Search
         8.3     Update
         8.4     TMP Monitor
         8.5     TMP Main Module

         9       COMMON SYSTEM FUNCTION

         9.1     Common
         9.2     Utility
         9.3     Queue Monitor
         9.4     Timer Monitor
         9.5     Message Monitor
         9.6     Coroutine Monitor
         9.7     System Call Monitor

         10      OFFLINE MODULES

         10.1    System Generation
         10.2    Format Generation
         10.3    Table Generation

         11      MESSAGE MANAGEMENT SYSTEM

         11.1    Common Procedures
         11.2    Command Handling
         11.3    Internal Message Format File Handling
         11.4    Storage + Retrieval
         11.5    Checkpoint + Recovery
         11.6    Disk I/O

         12      SYSTEM STATUS AND CONTROL

         12.1    OLD - Online Diagnostics
         12.2    CMI - Command Interpreter
         12.3    WDP - Watchdog Firmware
         12.4    EHD - Error Handler and Command Dispatcher
         12.5    TEMCO - Terminal Monitoring and Control
         12.6    DEMCO - Device Monitoring and Control
         12.7    CEMCO - Channel Monitoring and Control
         12.8    WAMCO - Watchdog Monitoring and Control
         12.9    CFH - Configuration Handler
         12.10   Common



         13      I/O CONTROL

         13.1    Format Handler VDU
         13.2    Format Handler PRT
         13.3    LTU Handler
         13.4    LTU Function VDU
         13.5    LTU Function, Low Speed Lines
         13.6    LTU Function, OCR
         13.7    STI Handler
         13.8    CRYPTO Handler
         13.9    Watchdog Interface



2.6.2.4  S̲t̲r̲u̲c̲t̲u̲r̲e̲ ̲o̲f̲ ̲t̲h̲e̲ ̲P̲D̲S̲

         The PDS has been divided into four chapters. The objectives
         for each chapter are presented below.

         Chapter 1 shall contain a presentation (purpose and
         scope) of the specification, define the baseline documents
         and define terms/abbreviations used within the specification.

         Chapter 2 shall define the package functions and characteristics
         to be implemented. The functions shall be described
         at a level similar to the SRS and SDS. Chapter 2 shall
         define what functions are to be implemented and not
         how these are implemented.

         Chapter 3 shall define what the package environments
         are. How interfaces are implemented shall not be described
         in chapter 3.

         Chapter 4 shall contain the actual design which implements
         the functional requirements described in chapter 2
         and 3.

         It should be noted that chapter 2 and 3 of the package
         specifications will be used to replace the package
         definition in the SDS (section 5.x).

         At package level section 4.1 of the package specification
         is equivalent to chapter 4 of the SDS at system level,
         while section 4.2.x of the package specification is
         equivalent to section 5.x of the SDS.

         S̲e̲c̲t̲i̲o̲n̲s̲ ̲a̲t̲ ̲t̲h̲e̲ ̲P̲D̲S̲

         S̲e̲c̲t̲i̲o̲n̲ ̲1̲.̲1̲

         a)  Purpose Statement. Describe the purpose of the
             Package Specification using the following as a
             guide. The Package Specification for (Project Name)
             (Project Number) is written to fulfil the following
             objectives:

             1)  To provide detailed definition of the Package
                 functions and software architecture.

             2)  To provide user operational and development
                 personnel details of the ongoing analysis.



             3)  To define in detail the interfaces with other
                 packages and to describe their facilities.

         b)  Scope Statement. Descripe the scope of the document
             by using the following as a guide.

             1)  What level of detail does the Package Specification
                 contain?

             2)  Where can higher/lower level design specifications
                 be found?

             3)  What interfaces/data are defined within the
                 specification and what interface/dates are
                 defined elsewhere?

         S̲e̲c̲t̲i̲o̲n̲ ̲1̲.̲2̲

         All documents which represent a baseline shall be defined.

             Other documents which do not directly represent
             requirements shall be listed as reference documents.

             S̲e̲c̲t̲i̲o̲n̲ ̲1̲.̲3̲

             This section shall contain a list of all abbreviations
             and key terms pertinent to the document.

             C̲h̲a̲p̲t̲e̲r̲ ̲2̲ ̲(̲G̲e̲n̲e̲r̲a̲l̲)̲

             Chapter 2 and its sections shall specify requirements
             pertinent to the package level.

             The documentation in chapter 2 shall be able to
             answer the following questions:

             a)  What am I part of?
             b)  What am I? (What are my functions?)
             c)  With whom do I interact?

             C̲h̲a̲p̲t̲e̲r̲ ̲2̲ ̲(̲S̲p̲e̲c̲i̲f̲i̲c̲)̲

             Section 2.1 shall contain a description of the
             package and its inter-relationships with other
             packages and/or system interfaces. A chart showing
             the package and its inter-relationships shall be
             resented.



             Section 2.2 shall describe the function to be performed
             by the package (on package level). The functions
             to be described are basically those derived from
             the SRS and the SDS.

             Section 2.2.1 shall describe the function performed
             under normal operation, while section 2.2.2 shall
             describe the functions to be performed by the package
             under special circumstances such as initialization,
             recovery, security, etc.

             Section 2.2.2 shall be seen in relation to section
             3.4. It is important to distinguish between functions
             which are performed by a package itself and functions
             which are pertinent to a package, but performed
             by other packages. Examples are log/statistics
             collection and message check pointing.

             Only functions performed by the package itself
             shall be contained in section 2.2.2.

             Section 2.3 shall specify the characteristics of
             the packages which are timing, throughput, flexibility
             and accuracy.

             a)  Timing. Describe any requirements for timing
                 on the package. The following requirements
                 should be considered:

                 1)  Throughout time.

                 2)  Response time to queries and for update
                     of data files.

                 3)  Response time of major sub-system functions.

                 4)  Sequential relationship of sub-system functions.

                 5)  Priorities imposed by inputs or changes
                     in modes of operation.

                 6)  Requirements for varying traffic load.

                 7)  Sequencing and interleaving programs and
                     systems (including the ability to interrupt
                     a program without loss of data).



             b)  Throughput. Describe the processing capacity
                 (connectivity) of the package.

             c)  Flexibility. Describe the requirements for
                 the package to deal with changing situations
                 e.g. operational changes, and interaction with
                 new or improved systems. Identify those components
                 and procedures which may be subject to change.

             d)  Accuracy and Validity. Describe the requirements
                 for package accuracy. These requirements must
                 cover the following areas of concern:

                 1)  Accuracy of input data.

                 2)  Accuracy of transmitted data.

             C̲h̲a̲p̲t̲e̲r̲ ̲3̲

             Chapter 3 shall address the following four main
             issues:

             -   equipment environment

             -   software environment

             -   package interfaces

             -   functions maintained by other packages

             a)  E̲q̲u̲i̲p̲m̲e̲n̲t̲ ̲E̲n̲v̲i̲r̲o̲n̲m̲e̲n̲t̲. Describe the equipment
                 required for the operation of the package,
                 and include a description of the equipment
                 presently available. Discuss the characteristics
                 of any additional equipment required. Related
                 the requirement for equipment to the requirements
                 stated in the SRS. The follwoing items should
                 be described:

                 1)  Processor(s) (number of each on/off line
                     and size of internal storage).

                 2)  Storage media (number of disk units, tape
                     units, etc.).

                 3)  Input/output (I/O) devices (number of each
                     on/off line).

                 4)  Communications net (line speeds).



             b)  The software environment has been separated
                 into the two categories:

                 1)  System software

                 2)  Development Software

                 The system software is defined to consist of
                 the following components DAMOS, IOC, CSF, and
                 MMS.

                 Other LKSAA software packages using these components
                 shall not specify their interfaces to these
                 packages (Refer below, section 3.3.2).

                 The development support software are defined
                 to include all software required to implement
                 and test the software package.

             c)  I̲n̲t̲e̲r̲f̲a̲c̲e̲s̲. Section 3.3.1 shall reference system
                 interfaces e.g. ICDs.

                 Section 3.3.2 shall identify interfaces to
                 other software packages (excl. DAMOS, IOC,
                 CSF, and MMS). The section shall not give a
                 detailed specification of interfaces, as these
                 are contained in section 4 of the PDS and in
                 separate ICDs.

             d)  F̲u̲n̲c̲t̲i̲o̲n̲s̲ ̲M̲a̲i̲n̲t̲a̲i̲n̲e̲d̲ ̲b̲y̲ ̲O̲t̲h̲e̲r̲ ̲P̲a̲c̲k̲a̲g̲e̲s̲

                 Section 3.4 shall contain a description of
                 functions which fulfil the following criterias:

                 1:  functions performed by other packages which
                     have a major importance for the operation
                     of the package.

                 2:  functions performed by other packages for
                     which there is no explicit interface. (supported
                     behind the users back")

                 Examples of functions to be described are:

                 -   security functions
                 -   check pointing function
                 -   recovery functions
                 -   log, statistics and report collection
                 -   error detection and -handling



2.6.2.5  P̲a̲c̲k̲a̲g̲e̲ ̲D̲e̲s̲i̲g̲n̲ ̲S̲t̲a̲n̲d̲a̲r̲d̲

         The following pages are an example of a normal package
         design process.



                    4̲ ̲ ̲P̲A̲C̲K̲A̲G̲E̲ ̲D̲E̲S̲I̲G̲N̲



         (4.1)   P̲A̲C̲K̲A̲G̲E̲ ̲O̲V̲E̲R̲V̲I̲E̲W̲

         Section 4.1 of the package specification has at package
         level the same mission as chapter 4 in the SDS at system
         level.

         In total 4.1 gives the concurrent and sequential processing
         within the package with clear definition of the role
         of each sub-package which are described more detailed
         in section 4.2.x.



         (4.1.1) F̲u̲n̲c̲t̲i̲o̲n̲a̲l̲ ̲S̲p̲e̲c̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

         This should be the first step in the analysis. The
         package functions desolved in section 2.2.1 and 2.2.2
         should be broken down to the level functional which
         justifies allocation of the subpackages described further
         in section 4.2.x.


                          ̲ ̲ ̲ ̲ ̲ ̲ ̲


                          ̲ ̲ ̲ ̲ ̲ ̲ ̲

                 ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

            ̲ ̲ ̲ ̲ ̲ ̲ ̲        ̲ ̲ ̲ ̲ ̲ ̲ ̲        ̲ ̲ ̲ ̲ ̲ ̲ ̲

                   A             B             C
            ̲ ̲ ̲ ̲ ̲ ̲ ̲        ̲ ̲ ̲ ̲ ̲ ̲ ̲        ̲ ̲ ̲ ̲ ̲ ̲ ̲

             ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲             ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲

                      ̲ ̲ ̲ ̲ ̲ ̲ ̲       ̲ ̲ ̲ ̲ ̲ ̲ ̲          ̲ ̲ ̲ ̲ ̲ ̲ ̲


                      ̲ ̲ ̲ ̲ ̲ ̲ ̲       ̲ ̲ ̲ ̲ ̲ ̲ ̲          ̲ ̲ ̲ ̲ ̲ ̲ ̲



                          Common functions



         Where common functions exist within a package the functional
         break-down shall be continued to the level where all
         common functions can be isolated.



         (4.1.2) S̲o̲f̲t̲w̲a̲r̲e̲ ̲S̲t̲r̲u̲c̲t̲u̲r̲e̲

         This section describes the allocation of functions
         onto processes, shared procedures (between two processes),
         monitor procedures (only for CSF, SSC, and DAMOS) or
         co-routines.

         Based on the above software component types sub-packages
         shall be defined.

         For each of the sub-packages the following elements
         shall be contained.

         1)  Functions allocated to the subpackage (refer 4.1.1).

         2)  Software structure which corresponds with the functional
             break-down of section 4.1.1.

         The software structure shall be presented by a chart
         which shows the software break-down. (Similar to chart
         presented in section 4.1.1).



         (4.1.3) D̲a̲t̲a̲ ̲F̲l̲o̲w̲ ̲a̲n̲d̲ ̲C̲o̲n̲t̲r̲o̲l̲ ̲L̲o̲g̲i̲c̲

         Data flow and control logic related to major transaction
         within a package shall be described to the sub-package
         level.

         The functional flow must give the normal flow (as 2.2)
         and the special flow (2.3).

         The tools to document flow/logic are block diagrams
         for process synchronization/communication and HIPO
         for sequential processing.



         (4.1.4) C̲o̲m̲m̲o̲n̲ ̲D̲a̲t̲a̲ ̲E̲l̲e̲m̲e̲n̲t̲s̲ ̲(̲I̲n̲t̲e̲r̲n̲a̲l̲)̲

         This should identify common data element (but not give
         detailed layout in order to make 4.1.5 more readable).





         (4.1.5) E̲x̲t̲e̲r̲n̲a̲l̲ ̲D̲a̲t̲a̲ ̲E̲l̲e̲m̲e̲n̲t̲s̲

         This should identify data shared with other packages
         which are defined in Data Def. Doc.



         (4.1.6) I̲n̲t̲e̲r̲f̲a̲c̲e̲s̲

         The section shall define external interfaces as well
         as software package to package interfaces (excl. DAMOS,
         IOC, CSF, and MMS). At minimum shall be references
         to the appropriate ICDs shall be included.

         Sub-package interfaces shall, furthermore, be identified
         but not specified in details, as this shall take place
         in section 4.2.x.5.

         G̲e̲n̲e̲r̲a̲l̲ ̲C̲o̲m̲m̲m̲e̲n̲t̲s̲ ̲t̲o̲ ̲4̲.̲1̲.̲4̲,̲ ̲4̲.̲1̲.̲5̲,̲ ̲a̲n̲d̲ ̲4̲.̲1̲.̲6̲

         In order to obtain a selfcontained and readable document
         it may be necessary to include detailed information
         in section 4.1.4 - 4.1.6. It shall however be emphasized
         that the master source for definition of data and package
         interfaces are the AMSS data definition document and
         the AMSS software interface control document.



         (4.2.x) S̲u̲b̲-̲p̲a̲c̲k̲a̲g̲e̲ ̲S̲p̲e̲c̲i̲f̲i̲c̲a̲t̲i̲o̲n̲s̲

         This section shall expand the subpackage design, as
         described in section 4.1 to a level where all modules
         (less than 250 source statements, refer SRS) are identified
         and the functions defined.



         (4.2.x.1) F̲u̲n̲c̲t̲i̲o̲n̲a̲l̲ ̲S̲p̲e̲c̲i̲f̲i̲c̲a̲t̲i̲o̲n̲

         This section shall contain a functional break-down
         to such a level that all SW modules can be identified
         taken all functional areas defined in section 2.2 and
         4.1.1 into account.





























                 INTENTIONALLY LEFT BLANK






















































                     Figure 7.1.3…01…LKSAA WBS




                                                       Issue 1.5
LKSAA - VOLUME II                                      SYS/84-06-15
APPENDIX C
TECHNICAL PROPOSAL                                     Page  149








                 ZVA COMPUTER RACK SPECIFICATION

























                DIMENSIONS:

                     H: 1995,5 mm  (36U)
                     W:  597 mm    (19")
                     D: 1040 mm

                WEIGHT:   95 kg.




                                                       Issue 1.5
LKSAA - VOLUME II                                      SYS/84-06-15
APPENDIX C
TECHNICAL PROPOSAL                                     Page  150


















                    INTENTIONALLY LEFT BLANK




                                                       Issue 1.5
LKSAA - VOLUME II                                      SYS/84-06-15
APPENDIX C
TECHNICAL PROPOSAL                                     Page  151


















                    INTENTIONALLY LEFT BLANK




                                                       Issue 1.5
LKSAA - VOLUME II                                      SYS/84-06-15
APPENDIX C
TECHNICAL PROPOSAL                                     Page  152


















                    INTENTIONALLY LEFT BLANK