CAMPS SITE DESIGN CONCEPT
…02…KM/810612…02…CAMPS
T̲A̲B̲L̲E̲ ̲O̲F̲ ̲C̲O̲N̲T̲E̲N̲T̲S̲
1 SCOPE................................... 4
1.1 GENERAL REQUIREMENTS.............. 4
2 EQUIPMENT AND SITE DATA................. 4
2.1 EQUIPMENT......................... 4
2.2 POWER............................. 4
2.3 EMP PROTECTION.................... 5
2.4 RED CONCEPT....................... 5
3 POWER CABLING........................... 5
3.1 GENERAL DESIGN SPECIFICATIONS..... 5
3.2 CAMPS ROOM........................ 5
3.3 USER TERMINALS.................... 6
4 SIGNAL CABLING......................... 7
4.1 GENERAL DESIGN SPECIFICATIONS.... 7
4.2 CAMPS ROOM....................... 7
4.3 USER TERMINALS................... 8
5 GROUNDING.............................. 9
5.1 GENERAL DESIGN SPECIFICATIONS.... 9
5.2 CAMPS ROOM....................... 9
5.3 USER TERMINALS................... 9
…01…1̲ ̲ ̲S̲C̲O̲P̲E̲
This document outlines the ACE COMSEC Requirements
for the CAMPS Equipment Installation and specifies
the overall site design criteria, to be reflected in
the CWR and A-T-B-B drawings.
1.1 G̲E̲N̲E̲R̲A̲L̲ ̲R̲E̲Q̲U̲I̲R̲E̲M̲E̲N̲T̲S̲
The CAMPS Equipment is to be installed in accordance
with relevant paragraphs of AMSG 719B, including:
ADP-INSTALLATION Paragraphs 330, 331, with references:
305b-c, 240
OPTO-Systems Paragraphs 370, 371
2̲ ̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲ ̲A̲N̲D̲ ̲S̲I̲T̲E̲ ̲D̲A̲T̲A̲
2.1 E̲Q̲U̲I̲P̲M̲E̲N̲T̲
Racks, VDU's, printers and PTR/PTP are EMI shielded
and therefore equipped with power line filters and
signal line filters or optical interface (except for
the frequency stabilizer rack). Sketch No. 1 shows
a typical CAMPS room layout.
2.2 P̲O̲W̲E̲R̲
All power in the CAMPS room is filtered (pink power)
The filter is located prior to the PDB (see sketch
no 2).
The user terminals will be supplied with black or pink
power.
2.3 E̲M̲P̲ ̲P̲R̲O̲T̲E̲C̲T̲I̲O̲N̲
At most sites the CAMPS room is located within an EMP
area i.e. power is filtered, all signal lines are filtered
etc.
2.4 R̲E̲D̲ ̲C̲O̲N̲C̲E̲P̲T̲
At all sites the CAMPS room is located within a red
area or class I area. Some user terminals are also
located in a red area and some are n̲o̲t̲.
3̲ ̲ ̲P̲O̲W̲E̲R̲ ̲C̲A̲B̲L̲I̲N̲G̲
3.1 G̲E̲N̲E̲R̲A̲L̲ ̲D̲E̲S̲I̲G̲N̲ ̲S̲P̲E̲C̲I̲F̲I̲C̲A̲T̲I̲O̲N̲S̲
Standard power cables laid in unperforated sheet metal
ducts with lids or conduits (fixed or flexible), below
raised floors, on the wall or below the ceiling are
to be specified since a pick up within the nearfield
of each piece of equipment could cause reradiation
of line emission within the CAMPS room. The filter
at the entrance to the CAMPS Room will prevent line
emission detectable outside the CAMPS room.
3.2 C̲A̲M̲P̲S̲ ̲R̲O̲O̲M̲
a) Sketch no. 3 shows a typical cable duct layout
concerning power distribution. A discussion of
the layout follows.
b) Metal power cable ducts (not inside ceiling) shall
be connected to the EMI rack only and isolated
at the PDB by an insulated bush.
c) The separation between power and signal cables
and power and other cables or metalwork follows
the AMSG719B paragraph 305b separation criteria:
Power - Signal (Opto, copper) in Parallel:
15 cm
Power - other cables or metalwork in Parallel:
15 cm
Crossing of other cables (red/black) or metalwork
must be done at right angles with a minimum separation
of 1,5 cm.
On the walls standoff insulators must be provided,
so that the cable is at least 1,5 cm from the wall
at any point.
d) The EMI racks are provided with power line filters
at which the power cables terminate. Either bottom
or top cable entrance to the racks will be provided.
At sites with raised floor the cables are to enter
from bottom and at sites not provided with computer
floor the entrance is from the top
e) The frequency stabilizer rack is treated as a black
piece of equipment by COMSEC. It must therefore
be placed, so that a 1 m separation from red equipment
can be maintained (racks, VDU etc.).
Note that there might be Host Nation provided black
equipment or cables in the CAMPS room. If so, it
must be specified in the site documentation received
from SHAPE.
f) Power outlets near each piece of equipment are
to be specified. The power outlets shall be a 3
wire type (line + neutral + GND) with break of
line only.
The power outlets can be mounted in the false floor,
on the wall or on the ceiling depending on the
facility in question.
3.3 U̲S̲E̲R̲ ̲T̲E̲R̲M̲I̲N̲A̲L̲S̲
a) A power outlet near each piece of equipment is
to be specified. The power outlet shall be a 3wire
type (Line + neutral + GND) with break of line
only.
b) The user terminals will either be supplied with
black or pink power. In both cases the separation
criteria are to be maintained.
4̲ ̲ ̲S̲I̲G̲N̲A̲L̲ ̲C̲A̲B̲L̲I̲N̲G̲
4.1 G̲E̲N̲E̲R̲A̲L̲ ̲D̲E̲S̲I̲G̲N̲ ̲S̲P̲E̲C̲I̲F̲I̲C̲A̲T̲I̲O̲N̲S̲
a) OPTO-cables in plastic ducts, since only physical
protection is required, below raised floors, on
the wall or below the ceiling (not inside false
ceiling) are to be specified.
b) Coppercables in plastic ducts require 1m separation
to black cables or metalwork and 15 cm to power
or other pink cables. Coppercables in ferrous shield
(waterpipe, or ferrous metal duct) requires 15
cm separation to metalwork or black cables.
4.2 C̲A̲M̲P̲S̲ ̲R̲O̲O̲M̲
a) Sketch No 4 shows a typical cable duct layout concerning
signal cable distribution. A discussion of the
layout follows:
b) OPTO-cables to supervisor positions are run in
plastic ducts below raised floors and in case false
floors are not provided on the walls or below the
ceilings. Only physical protection against damage
is to be specified where OPTO cables leave the
duct (rack, supervisor position)
c) Coppercables to the maintenance position are run
in a separate ferrous duct or pipe, which can be
placed next to the OPTO-duct. A termination (junction
box o.e) of the duct or pipe is to be specified
where the coppercable leaves the shield. CR will
install flexible conduit from this point if necessary
(rack, maintenance position).
d) Ducting for the coppercables to low speed teleprinters,
SCARS, CCIS and TARE are not to be specified by
CR, but must be taken into consideration with regard
to space and entrance to rack F in the CWR. CR
will specify the electrical and mechanical interface
to the racks in the CWR and As-To-Be-Built Drawings.
e) Either bottom or top cable entrance will be provided
to the EMI racks as specified in paragraph 3.2.d.
The connection between the two bays of racks (processor
and line termination racks) will be installed by
CR as a flexible ferrous conduit, which is to be
considered as a part of the EMI shield.
4.3 U̲S̲E̲R̲ ̲T̲E̲R̲M̲I̲N̲A̲L̲S̲
a) OPTO-cables to user terminals are to be run in
metal ducts or pipes outside the CAMPS room. Pull-boxes
for every 20m must be specified and ducts must
not be welded or otherwise locked (sealed) until
CR has completed the CAMPS installation. When leaving
the CAMPS room the wall penetration must be at
right angles.
Inside the CAMPS room plastic ducts are to be specified.
b) The OPTO cable will be terminated at the user terminal
by CR's installation team.
The OPTO-cable is installed by Host Nation up to
the location of the terminal and precut to a certain
length. (to be specified)
5̲ ̲ ̲G̲R̲O̲U̲N̲D̲I̲N̲G̲
5.1 G̲E̲N̲E̲R̲A̲L̲ ̲D̲E̲S̲I̲G̲N̲ ̲S̲P̲E̲C̲I̲F̲I̲C̲A̲T̲I̲O̲N̲S̲
a) A common secure ground connection point (Copper
or similar) will be provided in the CAMPS room
in order to achieve a star point configuration.The
secure ground will also act as safety ground and
must therefore comply to national regulations.
b) User terminals will either be connected to a secure
ground or to a safety ground.
c) The secure ground will be connected primarily to
PLF case and to the grounding point of each piece
of equipment.
5.2 C̲A̲M̲P̲S̲ ̲R̲O̲O̲M̲
SHAPE or Host Nation will provide a common secure ground
terminal (copperbar, o.e. in the CAMPS room PDB), and
distribute it to power outlets and equipment racks
either as the third wire of a 3wire power cable or
as a separate wire run within the same conduit.
5.3 U̲S̲E̲R̲ ̲T̲E̲R̲M̲I̲N̲A̲L̲S̲
Host Nation will provide 3 pin power outlets for user
terminals, the third wire of which will provide either
a secure or safety ground. The ground wire may be the
third wire of a 3 wire power-cable from the PDB to
the power outlet or a separate wire run within the
same conduit.