top - download
⟦a8b91f60c⟧ Wang Wps File
Length: 123230 (0x1e15e)
Types: Wang Wps File
Notes: CPS/AUX/036 (Site 02)
Names: »3036A «
Derivation
└─⟦5d3cf8feb⟧ Bits:30006213 8" Wang WCS floppy, CR 0332A
└─ ⟦this⟧ »3036A «
WangText
…0c……00……00……00……00…G…02…G
F…0a…F…0c…F…0e…E…08…E
D…0c…D…06…C…0b…C…02…C…06…B…0c…B
A…09…A…0c…A…02…A…07…@…0d…@…01…@…05…@…06…?…0d…?
?…06…>…0a…>…00…>…05…=…0b…=…0f…=
<…08…<…09…<…0f…<…00…<…05…;…0a…;…00…;…06…:…0c…:…02…9…08…9…0e…9 8…08…8…0b…8…0d…8…02…8…05…7…08…7…0c…7…0e…7…86…1 …02… …02…
…02…
3036A/ktd …02… CPS/AUX/036
…02… NPP/811201…02……02…#
CAMPS INSTALLATION PROCEDURES
SITE 02…02……02…CAMPS
3.1. R̲e̲c̲e̲i̲p̲t̲ ̲o̲f̲ ̲t̲h̲e̲ ̲E̲q̲u̲i̲p̲m̲e̲n̲t̲ ̲b̲y̲ ̲S̲i̲t̲e̲
3.1.1 I̲n̲c̲o̲m̲i̲n̲g̲ ̲I̲n̲v̲e̲n̲t̲o̲r̲y̲/̲I̲n̲s̲p̲e̲c̲t̲i̲o̲n̲
a) Site will perform an incoming inventory of the
equipment according to the packing lists found
in colli No. 1 (see 2.1.3 above).
b) Before the containers are moved to the installation
site, inspect the containers for any visual damage
during the transportation.
c) Record the results of a) and b). Return one copy
of the results to the personnel of the transportation
company and hand over one copy to CR's installation
team.
b) All equipment should remain packed during site
internal transportation and only be unpacked close
to the installation site.
When the racks are as close as possible to the
installation site, the racks are unpacked according
to section 5.2.1 and the equipment inspected for
any visual damages.
If, however, the space along the access route is
limited, the racks can be unpacked before transportation
to the installation site.
For unpacking instructions refer to section 5.2.1.
c) After unpacking, the front and rear doors of the
racks must be removed. Check that serial numbers
in the racks correspond to the serial numbers of
the doors.
d) Be careful not to damage the gaskets when removing
the doors.
e) Depending on means of transportation, 4 eyelets
can be mounted in the top of the rack in the position
of the removed 4 ea 1/2 - 13 x 2" bolts.
3.1.4 S̲i̲g̲n̲i̲n̲g̲ ̲f̲o̲r̲ ̲R̲e̲c̲e̲i̲p̲t̲ ̲o̲f̲ ̲E̲q̲u̲i̲p̲m̲e̲n̲t̲
H/N will sign for the receipt of the equipment and
together with the remarks (ref. 3.1.c) and 3.2.e))
return one set of these documents to the personnal
of the transportation company.
CAMPS INSTALLATION PROCEDURES
SITE 02
CPS/AUX/036
Niels Peder Pedersen
Kurt Nybroe-Nielsen
SHAPE (4), GJ, OE, KM, HAU, BHB, IJO, NPP,
(2),
Conf. Mgmt., QA, PAB
Install. Mgr. 821201
Issue 1
821201
3036A/ktd …02… CPS/AUX/036
…02… NPP/821201…02……02…ii
CAMPS INSTALLATION PROCEDURES
SITE 02…02……02… CAMPS
821201 All Issue 1 of Document
3036A/ktd …02… CPS/AUX/036
…02… NPP/821201…02……02…iii
CAMPS INSTALLATION PROCEDURES
SITE 02…02……02… CAMPS
T̲A̲B̲L̲E̲ ̲O̲F̲ ̲C̲O̲N̲T̲E̲N̲T̲S̲
TITLE PAGE ....................................
i
REVISION RECORD ................................
ii
TABLE OF CONTENTS .............................. iii
ABBREVIATIONS .................................. vii
1 INTRODUCTION .................................
1
1.1 SCOPE ....................................
1
1.2 DOCUMENT FORMAT ..........................
1
1.3 REFERENCES ...............................
2
2 MAIN SITE INSTALLATION PREPARATIONS ..........
3
2.1 SHIPMENT OF EQUIPMENT ....................
3
2.1.1 Disassembly and Packing ..............
3
2.1.2 Transportation to Site ...............
6
2.1.3 Receipt of Equipment at Main Site ....
7
2.1.3.1 Receipt ..........................
7
2.1.3.2 Incoming Inventory/Inspection ....
8
2.1.3.3 Distribution of Equipment ........
8
2.2 PREPARATION OF INSTALLATION MAIN AT SITE .
9
2.2.1 Preparations by CR ...................
9
2.2.2 Preparations by Site ................. 10
2.3 INSTALLATION OPERATIONS .................. 11
3 INSTRUCTIONS TO THE MAIN SITE ................ 16
3.1 TRANSPORTATION TO INSTALLATION SITE ...... 16
3.2 INSTALLATION PREPARATIONS AND SUPPORT .... 17
3.3 SHIPMENT CONTAINERS ...................... 18
4 TOOLS AND TEST EQUIPMENT ..................... 18
5 INSTALLATION OF MAIN SITE EQUIPMENT .......... 21
5.1 GENERAL .................................. 21
5.2 MECHANICAL RACK ASSEMBLY ................. 22
5.2.1 Unpacking of Racks ................... 22
5.2.2 Transportation to Installation Site .. 24
5.2.3 Removal of Upper Crates and D-Fans ... 24
5.2.4 Removal of Mains Switches ............ 26
5.2.5 Mounting of Levellers ................ 26
5.2.6 Mounting of Gaskets .................. 26
5.2.7 Levelling and Bolting of Racks ....... 27
5.2.8 Inspection/Repair of Gaskets ......... 27
3036A/ktd …02… CPS/AUX/036
…02… NPP/821201…02……02…iv
CAMPS INSTALLATION PROCEDURES
SITE 02…02……02… CAMPS
5.2.9 Mounting of Power Line Filters
Rack A, B and E ...................... 28
5.2.10 Remounting of Upper Crates and D-Fans 28
5.2.11 Remounting of Mains Switches ........ 28
5.3 INSTALLATION OF EXTERNAL POWER CABLES
AND MOUNTING OF CONDUITS ................. 29
5.3.1 Power Cables Rack A .................. 29
5.3.2 Power Cables Rack B .................. 29
5.3.3 Power Cables Rack E .................. 29
5.4 INSTALLATION OF EXTERNAL SIGNAL CABLES AND
MOUNTING OF CONDUITS AT RACK C, D & F .... 30
5.4.1 Rack D, Sup./Maint./User Pos. Cables . 30
5.4.2 Cable Bunch Rack C to Rack D ......... 31
5.4.3 Rack F (LSM/Other Cables) ............ 31
5.5 REMOUNTING OF RACKS ...................... 32
5.5.1 Mounting of Disk Drives .............. 32
5.5.2 Mounting of Floppy Disk Station ...... 32
5.5.3 Mounting of Stat. Mux. ............... 33
5.5.4 Mounting of Modules .................. 33
5.6 INSTALLATION AND TERMINATION OF INTERNAL
SIGNAL CABLES ............................ 33
5.6.1 Internal Signal Cables ............... 33
5.7 TERMINATION OF EXTERNAL SIGNAL CABLES .... 53
5.8 CONNECTION OF INTERNAL POWER CABLES ...... 59
5.9 POWER UP AND CHECK OUT ................... 66
5.9.1 Groundings ........................... 66
5.9.2 CAMPS PDB ............................ 66
5.9.3 Disk Drives........................... 67
5.9.4 Mains Switch Rack A Switch 2 ......... 68
5.9.5 Mains Switch Rack B Switch 2 ......... 69
5.9.6 Mains Switch Rack B Switch 1 ......... 70
5.9.7 Mains Switch Rack C Switch 2 ......... 70
5.9.8 Mains Switch Rack D Switch 1 ......... 71
5.9.9 Mains Switch Rack E Switch 2 ......... 71
5.9.10 Mains Switch Rack E Switch 1 ........ 72
5.9.11 Mains Switch Rack G Switch 1 ........ 72
5.9.12 Mains Switch Rack D Switch 2 ........ 72
5.9.13 Turn On ............................. 73
5.9.14 Verify Supply Voltage on PU Crates .. 73
5.9.15 Verify Supply Voltage on CU Crate ... 73
3036A/ktd …02… CPS/AUX/036
…02… NPP/821201…02……02…v
CAMPS INSTALLATION PROCEDURES
SITE 02…02……02… CAMPS
5.10 INSPECTION OF SWITCH SETTINGS AND STATUS
LEDS .....................................
73
5.10.1 Switch Settings .....................
74
5.10.2 Led Indicators ......................
74
5.11 INSTALLATION OF DELTA VDU ................
79
5.11.1 Power Plug Connections ..............
79
5.11.2 Termination of Opto Cables ..........
79
5.11.3 Mounting of Keyboard and Keys .......
80
5.12 INSTALLATION OF TRACOR MSP ..............
81
5.12.1 Power Plug Connections ..............
81
5.12.2 Termination of Opto Cables ..........
81
5.13 INSTALLATION OF PTP/PTR .................
82
5.14 TEST OF SUP/USER TERMINALS ..............
83
5.14.1 Test of Delta VDU ...................
83
5.14.2 Operational Test ....................
84
5.14.3 Test of Tracor MSP ..................
85
5.14.4 Operational Test ....................
86
5.15 TEST OF PTP/PTR .........................
86
5.16 H/W TEST PROCESSOR/LINE TERM. UNITS .....
86
5.16.1 PU #1(CU/TDX #2 Functional Test .....
86
5.16.2 Watchdog Processor Functional Test ..
87
5.17 INVENTORY CHECK .........................
87
6 INSTALLATION OF REMOTE TERMINAL EQUIPMENT
SITE 02A ......................................
88
6.1 SHIPMENT OF EQUIPMENT .....................
88
6.1.1 Disassembly and Packing ...............
88
6.1.2 Transportation to Site ................
90
6.1.3 Receipt of Equipment Site 02A .........
91
6.2 PREPARATION OF INSTALLATION AT CRT 02A ....
91
6.2.1 Preparations by CR ....................
91
6.2.2 Preparations by Site ..................
92
6.3 INSTRUCTIONS TO SITE 02A ..................
93
6.3.1 Receipt of Equipment by CRT Site ......
93
6.3.2 Incoming Inventory/Inspection .........
93
3036A/ktd …02… CPS/AUX/036
…02… NPP/821201…02……02…vi
CAMPS INSTALLATION PROCEDURES
SITE 02…02……02… CAMPS
6.4 INSTALLATION PREPARATIONS AND SUPPORT .....
94
6.5 SHIPMENT CONTAINERS .......................
95
6.6 INSTALLATION OF REMOTE TERMINAL EQUIPMENT
95
6.7 UNPACKING .................................
96
6.8 TRANSPORTATION TO INSTALLATION SITE .......
96
6.9 MOUNTING OF LEVELLERS .....................
98
6.10 MOUNTING OF POWER LINE FILTER ............
98
6.11 REMOUNTING OF STAT. MUX. .................
98
6.12 INSTALLATION OF INTERNAL POWER/SIGNAL
CABLES ...................................
99
6.13 INSTALL. ESTERNAL POWER/SIGNAL CABLES
AND MOUNTING OF FITTINGS .................
99
6.13.1 Left Hand Rear Bottom Penetration ....
99
6.13.2 Right Hand Rear Bottom Penetration ... 100
6.13.3 Aux. Connections and Modem Cable ..... 100
6.13.4 Right Hand Front Penetrations ........ 100
6.13.5 User Terminal Cables/Left Hand Rear
Penetration .......................... 100
6.14 MOUNTING OF MODULES ...................... 100
6.15 INSTALLATION OF DELTA VDU ................ 102
6.15.1 Power Plug Connections ............... 102
6.15.2 Termination of Opto Cables ........... 102
6.15.3 Mounting of Keyboard and Keys ........ 103
6.16 INSTALLATION OF TRACOR MSP ............... 103
6.16.1 Power Plug Connections ............... 103
6.16.2 Termination of Opto Cables ........... 104
6.17 POWER UP AND CHECK OUT ................... 105
6.18 TEST OF DELTA VDU ........................ 106
6.19 TEST OF TRACOR MSP ....................... 107
6.20 OPERATIONAL TEST OF USER TERMINALS ....... 107
6.20.1 Test of Crypto/Analog Line ........... 107
6.20.2 Test of VDU .......................... 108
6.20.3 Test of MSP .......................... 109
6.21 INVENTORY CHECK .......................... 109
3036A/ktd …02… CPS/AUX/036
…02… NPP/821201…02……02…vii
CAMPS INSTALLATION PROCEDURES
SITE 02…02……02… CAMPS
A̲B̲B̲R̲E̲V̲I̲A̲T̲I̲O̲N̲S̲
A̲B̲B̲R̲E̲V̲I̲A̲T̲I̲O̲N̲S̲:̲
ATBB As To Be Built
BPJF Black Patch Jack Field
CAMPS Computer Aided Message Processing System
CR Christian Rovsing A/S
DIAG Diagram
Doc Document
DWG Drawing
EMI Electromagnetic Interference
H/W Hardware
IDF Intermediate Distribution Frame
ILLUS Illustrations
J-Box Junction Box
LED Light Emitting Diode
LIA-N Line Interface Adapte
LSM Low Speed Medium
LTU Line Termination Unit
LTUX-S Line Termination Unit/TDX Bus
L/L ADP Low Level Adapter
MMD Mini Module Drive
MSP Medium Speed Printer
M&D Maintenance and Diagnostic
PDB Power Distribution Board
PDP Power Distribution Panel
PLF Power Line Filter
PTP Paper Tape Puncher
PTR Paper Tape Reader
STAT.MUX Statistical Multiplexer
Sup.Term. Supervisor Terminal
TARE Telegraph Automatic Relay Equipment
TDX Telecommunication Data Exchange
VDU Visual Display Unit
W-NUMBER Cable Identification Number
1 I̲N̲T̲R̲O̲D̲U̲C̲T̲I̲O̲N̲
1.1 S̲C̲O̲P̲E̲
This document describes how CR will perform the installation
of the CAMPS equipment and gives instructions to site
concerning receipt of equipment and arrrangements to
be made by the site concerning CR's presence during
installation
1.2 D̲O̲C̲U̲M̲E̲N̲T̲ ̲F̲O̲R̲M̲A̲T̲
a) The document is structured in the following sections:
- Section 1: Introduction
- Section 2: Installation Preparations
- Section 3: Instruction to Main Site
- Section 4: Installation Tools and Test
Equipment
- Section 5: Installation of Main Site Equipment
- Section 6: Installation of Remote Terminal
Equipment Site 02A
b) Section 2 provides a short description of how the
equipment is packed and indicates to the site the
size of arriving shipment in form of quantity,
size, and weight of containers in the shipment.
A description of the preparations to be made by
CR and the Site is also provided in this section.
c) Section 3 contains the instructions to Site concerning
the coming installation.
d) Section 4 lists the tools and test equipment used
during installation.
e) Sections 5 and 6 contain a step-by-step instruction
of how to install and interconnect the CAMPS major
assemblies with reference to the As-To-Be-Built
drawings. Procedures for power-up and installation
check-out are included. Sections 5 and 6 will be
updated after installation has been accomplished
and incorporated in the installation manual to
be delivered after provisional site acceptance.
1.3 R̲E̲F̲E̲R̲E̲N̲C̲E̲S̲
1. CAMPS Hardware Assembly
Breakdown/Hardware Tree
Doc. No. CPS/SDS/017
2. CAMPS Site Level Maintenance Manual
Doc. No. CPS/TCM/005
3. Inventory List
Doc. No. CPS/AUX/?
4. OPTO-Cable Termination Procedure
Doc. No. CPS/TCN/029
5. Site Survey Procedure and Checklist
800626
6. Factory Acceptance Procedure
Doc. No. CPS/TPR/001
7. CAMPS USER MANUAL
Doc. No. CPS/OPM/001
8. CAMPS TRANSPORTATION PLAN
Doc. No. CPS/PLN/007
9. CAMPS PACKING PROCEDURE
Doc. No. CPS/AUX/021
10. ATBB DRAWINGS
Doc. No. PAB/CPS/ATB/002
11. ATBB Drawings Remote Terminals Site 02A
Doc. No. PAH/CPS/ATB/201
12. CAMPS REMOTE TERMINALS H/W BREAKDOWN
Doc. No. CRT/SDS/002
13. CIVIL WORKS REQUIREMENTS SITE 02
Doc. No. PAB/CPS/CWR/002
2 M̲A̲I̲N̲ ̲S̲I̲T̲E̲ ̲I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲P̲R̲E̲P̲A̲R̲A̲T̲I̲O̲N̲S̲
2.1 S̲H̲I̲P̲M̲E̲N̲T̲ ̲O̲F̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲
2.1.1 D̲i̲s̲a̲s̲s̲e̲m̲b̲l̲y̲ ̲a̲n̲d̲ ̲P̲a̲c̲k̲i̲n̲g̲
The CAMPS equipment for the Main Site will be shipped
to site disassembled and packed as follows:
- Rack Assemblies (ABC, DEFG) are seperated in individual
racks and packed in a wooden container.
- Disk Units, Multiplexers, Power Linefilters and
Modules are removed from the racks and shipped
in their own containers.
- Cables between racks are generally shipped as part
of one of the racks.
- Terminal equipment (VDU, MSP, PTP/PTR and auxiliary
equipment (tables, storage cabinet) are shipped
in their own containers.
- Site spare parts are individually packed and are
shipped together with the main equipment.
Above packing scheme will result in the shipment composition
described in Table 2.1. The table lists quantity of
containers and packed weight and cubage of each container,
together with the total quantity, cubage, and weight
of the shipment. The logistic data given is to be used
by the site for preparation of the receival and for
providing temporary storage area.
Equipment for the remote terminal site 02A will be
transported as part of the main site equipment, dependent
on the geographical location the remote site equipment
will be undloaded, either prior to or after the unloading
of the main site equipment. For logistic data of the
remote site equipment, refer to section 6.
M̲a̲i̲n̲ ̲S̲i̲t̲e̲ ̲I̲n̲s̲t̲a̲l̲l̲e̲d̲ ̲E̲q̲u̲i̲p̲m̲e̲n̲t̲
Total
Total
Item Item Size of Cont. Container Packed Container
D̲e̲s̲c̲r̲i̲p̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲Q̲t̲y̲ ̲ ̲ ̲W̲x̲D̲x̲H̲ ̲(̲c̲m̲)̲ ̲ ̲ ̲ ̲ ̲Q̲t̲y̲ ̲ ̲ ̲ ̲ ̲W̲e̲i̲g̲h̲t̲ ̲(̲k̲g̲)̲ ̲ ̲C̲u̲b̲a̲g̲e̲
̲(̲c̲b̲m̲)̲
Rack A 1 72x126x192 1 300 1.74
Rack B 1 72x126x192 1 295 1.74
Rack C 1 72x126x192 1 315 1.74
Rack D 1 72x126x192 1 305 1.74
Rack E 1 72x126x192 1 280 1.74
Rack F 1 72x126x192 1 270 1.74
Rack G 1 72x126x192 1 255 1.74
MMD DISK DRIVE 2 63x95x62 2 185 0.74
SMD DISK DRIVE 1 63x95x62 1 92 0.37
MSP 8 65x74x39 8 296 1.50
VDU 18 65x80x55 18 774 5.16
PTP/PTR 1 63x69x62 1 43 0.27
CR80S, 1M MODULE 43 29x38x35 7 35 0.27
CR80S, 2M MODULE 5 29x38x35 2 9 0.04
CR80S, PSU 5 29x38x35 5 27 0.19
CR80M, 1M MODULE 22 54x32x61
CR80M, 2M MODULE 1 54x32x61 …0e…3 40 0.32…0f…
CR80M, 1M ADAPTER 21 54x32x61 2 18 0.18
CR80M, PSU 6 68x68x48 3 44 0.67
FD STATION 1 67x85x50 1 27 0.28
PLF 3 30x48x32 2 26 0.10
STORAGE CABINET 1 60x65x210 1 …0f…103 0.85…0e…
100x130x2 1
DISK PACK 6 48x50x25 6 33 0.36
TERMINAL CABLES 10 123x83x12 10 485 1.23
CABLES 54x32x61 1 10 0.09
STAT. MUX. 1 54x32x61 1 5 0.11
INSTALL. MATERIAL 54x32x61 2 ̲ ̲4̲8̲
̲0̲.̲2̲2̲
4,332 25.28
Table 2.1 (sheet 1)
Logistic Data…01…
S̲p̲a̲r̲e̲s̲,̲ ̲T̲e̲s̲t̲ ̲E̲q̲u̲i̲p̲m̲e̲n̲t̲ ̲&̲ ̲D̲o̲c̲u̲m̲e̲n̲t̲s̲
Total Total
Item Item Size of Cont. Container Packed Container
D̲e̲s̲c̲r̲i̲p̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲Q̲t̲y̲ ̲ ̲ ̲W̲x̲D̲x̲H̲ ̲(̲c̲m̲)̲ ̲ ̲ ̲ ̲ ̲Q̲t̲y̲ ̲ ̲ ̲ ̲ ̲W̲e̲i̲g̲h̲t̲ ̲(̲k̲g̲)̲ ̲ ̲C̲u̲b̲a̲g̲e̲
̲(̲c̲b̲m̲)̲
CR80S, 1M MODULE 1 29x38x35 1 1 0.04
CR80S, PSU 1 29x38x35 1 6 0.04
CR80M, 1M MODULE 6 54x32x61 …0f…1 13 0.11…0e…
CR80M, 1M ADAPTER 3 54x32x61
CR80M, PSU 1 68x68x48 1 8 0.22
CR80S, FAN UNIT 1 20x55x40 1 7 0.04
CR80M, FAN UNIT 1 67x85x50 1 12 0.28
KIT FOR VDU 1
MSP UNIT 1
P/N: 54147711 1
- : 54152501 1
- : 54275307 1
- : 54275710 1
- : 54277306 1
- : 54277713 1 54x32x61 1 20 0.11
PSU FOR FD 1
PCB SA800-2 1
LOGIC MODULE 1
PUNCH LOGIC 1
POS LOGIC 1
READ HEAD ASSY 1
PUNCH MOTOR 1
MODEM UNIT 1
OSCILLOSCOPE 1 42x78x32 1 11 0.10
COMTESTER 1 42x53x23 1 ̲6̲ 0̲.̲0̲5̲
84 0.99
MAIN SITE EQUIPMENT 4,332 25.28
REMOTE TERMINAL 02A EQUIPMENT 570 3.00
SPARES ̲ ̲ ̲8̲4̲ ̲0̲.̲9̲9̲
TOTAL 4̲,̲9̲8̲6̲ 2̲9̲.̲2̲7̲
Table 2.1 (sheet 2)
Logistic Data
2.1.2 T̲r̲a̲n̲s̲p̲o̲r̲t̲a̲t̲i̲o̲n̲ ̲t̲o̲ ̲S̲i̲t̲e̲
The CAMPS equipment will be carried to site by truck.
The equipment will be loaded at CR's plant in Copenhagen
and transported directly to site without any transshipment.
CR will use an experienced transportation company for
the conveyence.
The truck used will be an aircushion vehicle type with
the dimensions indicated in Table 2.2.
T̲r̲u̲c̲k̲ T̲r̲u̲c̲k̲ ̲+̲ ̲l̲o̲a̲d̲
̲
Weight 9 tons 14 tons
Size (m) 3.75Hx2.50Wx9.75L
Axle load, front 2 tons 6 tons
Axle load, rear 5 tons 10 tons
Table 2.2…01…Truck Dimensions
2.1.3 R̲e̲c̲e̲i̲p̲t̲ ̲o̲f̲ ̲E̲q̲u̲i̲p̲m̲e̲n̲t̲ ̲a̲t̲ ̲t̲h̲e̲ ̲M̲a̲i̲n̲ ̲S̲i̲t̲e̲
2.1.3.1 R̲e̲c̲e̲i̲p̲t̲
a) The receipt of the equipment at the main site will
be performed by CR's installation team. The team
or a CR representative will arrive one day in advance
of the truck carrying the equipment. The transportation
company (2 men) will assist CR in moving equipment
to the installation area.
b) The shipment will be notified according to the
transportation plan as follows:
1. CR will request a customs form 302, 30 days
in advance of the shipment.
2. SHAPE will reforward the request to the site
who will issue the form 302 and submit it to
SHAPE.
3. SHAPE will submit the completed form 302 together
with an authorization to ship as scheduled
in the notificaion telex per 1. above.
4. CR will send a notice of shipment per telex
to SHAPE at the day of the shipment, with the
arrival day at site of the equipment.
c) The shipment will be accompanied by the following
shipping documents according to ref 1:
- A complete set of packing lists
- Proforma Invoice
- Shipping Letter
- Customs Form 302
- Authorization to Ship telex
All containers are marked with a package number.
A set of above documents are contained in package
No. 1 and a set is enclosed in an envelope on the
outside of package No. 1.
2.1.3.2 I̲n̲c̲o̲m̲i̲n̲g̲ ̲I̲n̲v̲e̲n̲t̲o̲r̲y̲/̲I̲n̲s̲p̲e̲c̲t̲i̲o̲n̲
1) CR will perform an incoming inventory check of
the equipment according to the packing lists found
in package No. 1.
2) Before the containers are moved to the installation
site, the containers will be inspected for any
visual damages.
3) The results of the above mentioned 1) and 2) will
be recorded and a copy will be given to the transportation
company.
2.1.3.3 D̲i̲s̲t̲r̲i̲b̲u̲t̲i̲o̲n̲ ̲o̲f̲ ̲E̲q̲u̲i̲p̲m̲e̲n̲t̲
The transportation company will distribute the received
equipment as follows:
1) U̲s̲e̲r̲ ̲T̲e̲r̲m̲i̲n̲a̲l̲s̲
The 14 VDU and 4 MSP user terminals are distributed
to the respective installation sites.
The terminals are unpacked and left on the installation
sites (tables) and the empties are removed.
2) S̲u̲p̲p̲/̲M̲a̲i̲n̲t̲.̲ ̲T̲e̲r̲m̲i̲n̲a̲l̲s̲
The 4 VDU and 4 MSP supp/maint terminals are stored
in the CAMPS equipment room and left unpacked.
3) R̲a̲c̲k̲s̲/̲S̲t̲o̲r̲a̲g̲e̲ ̲C̲a̲b̲i̲n̲e̲t̲
The 7 EMI racks and the storage cabinet are moved
into the CAMPS equipment room.
4) P̲T̲P̲/̲P̲T̲R̲
The PTP/PTR is stored in the encryption area and
left unpacked on the allocated table.
5) T̲e̲r̲m̲i̲n̲a̲l̲ ̲T̲a̲b̲l̲e̲s̲
5 terminal tables are stored in the CAMPS equipment
area.
5 terminal tables for the user termials are stored
according to instructions from H/N.
6) O̲t̲h̲e̲r̲ ̲S̲e̲p̲a̲r̲a̲t̲e̲l̲y̲ ̲P̲a̲c̲k̲e̲d̲ ̲E̲q̲u̲i̲p̲m̲e̲n̲t̲
Other separately packed equipment such as cables,
disk drives, modules, spares, etc, are stored in
the temporary storage area. Ref. site survey report.
2.2 P̲R̲E̲P̲A̲R̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲A̲T̲ ̲T̲H̲E̲ ̲M̲A̲I̲N̲ ̲S̲I̲T̲E̲
2.2.1 P̲r̲e̲p̲a̲r̲a̲t̲i̲o̲n̲s̲ ̲b̲y̲ ̲C̲R̲
a) The CR installation team plans to arrive one day
in advance of the equipment. Prior to the planned
arrival, the officer in charge of CAMPS is informed
by telex.
b) Upon arrival, the local CAMPS officer in charge
will give a briefing, addressing the following
subjects:
- Access to site and house rules
- Location of applicable areas such as storage
area, parking and unloading area, CAMPS equipment
area, etc.
- The support requested by contractor, ref. 2.2.2.
- Introduction of the installation team to relevant
local personnel.
- Information regarding local facilities such
as cafeteria, telephones, medical aid, etc.
c) The installation team will present the planned
major steps of the installation efforts. Ref section
5: Step-by-step procedures.
d) Full identification of the delivery team (transportation
company) including names and truck licence will
be provided to SHAPE at least ten days prior to
delivery.
e) Names and clearances of the potential installation
team will be provided to SHAPE one month before
start of the installation.
2.2.2 P̲r̲e̲p̲a̲r̲a̲t̲i̲o̲n̲s̲ ̲b̲y̲ ̲S̲i̲t̲e̲
a) The CAMPS equipment rooms are prepared for installation
of the equipment according to the civil works requirements
and this is verified at the site verification inspection
which is scheduled to take place 1 month prior
to start of installation.
b) A conference room should be provided for the introductory
briefing, other arrangements to be made for CR's
presence at site are described in section 3.
These arrangements have been accessed during the
site surveys and are to be discussed and finalized
during the site verification meetings.
2.3 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲O̲P̲E̲R̲A̲T̲I̲O̲N̲S̲
The installation of a complete CAMPS system requires
that the installation operations are performed in a
certain sequence.
Figure 2.1 shows the installation effort structured
in operations and with a time schedule for each operation.
A brief summary of the operations are given below:
1 T̲r̲a̲v̲e̲l̲t̲i̲m̲e̲
2 A̲r̲r̲i̲v̲a̲l̲/̲I̲n̲t̲r̲o̲d̲u̲c̲t̲i̲o̲n̲
3 M̲e̲c̲h̲a̲n̲i̲c̲a̲l̲ ̲R̲a̲c̲k̲ ̲A̲s̲s̲e̲m̲b̲l̲y̲
The equipment racks (Rack A-G) will after arrival
to the site be moved to the CAMPS equipment area
and unpacked. The racks will be aligned and bolted
together to form the 3-bay computer unit (Rack
A-B-C) and the 4-bay line termination unit (Rack
D-E-F-G).
All terminals and the terminal tables will be distributed
to their respective installation sites.
Figure 2.1
Installation Schedule
4 E̲x̲t̲e̲r̲n̲a̲l̲ ̲P̲o̲w̲e̲r̲ ̲C̲a̲b̲l̲e̲s̲
The power cables coming from the CAMPS power distribution
board will be terminated in the power line filters
of Rack A, B, and E.
5 E̲x̲t̲e̲r̲n̲a̲l̲ ̲S̲i̲g̲n̲a̲l̲ ̲C̲a̲b̲l̲e̲s̲
Opto fibre cables coming from the user terminals
entering rack D through the CR installed conduits
will be distributed to their respective termination
points in racks C, D, E, and F.
Cables from rack D to the supervisory and maintenance
positions will be installed.
All metallic cables coming from the customer delivered
LSM terminals as well as the metallic cables coming
from other connections (e.g. SCARS, CCIS, etc)
will be installed in the filter box of rack F through
the CR installed metallic conduit.
Interrack cables between the computer and line
termination units will be installed.
6 I̲n̲t̲e̲r̲n̲a̲l̲ ̲S̲i̲g̲n̲a̲l̲ ̲C̲a̲b̲l̲e̲s̲
All internal signal cables in the computer and
line termination units, dismounted during the transportation,
will be reinstalled. Cables not dismounted will
be checked for being properly connected.
7 T̲e̲r̲m̲i̲n̲a̲t̲i̲o̲n̲ ̲o̲f̲ ̲E̲x̲t̲e̲r̲n̲a̲l̲ ̲S̲i̲g̲n̲a̲l̲ ̲C̲a̲b̲l̲e̲s̲
All opto fibre cables to be connected on front
of the line termination unit (rack D) will be terminated
with special opto connectors.
Metallic interface cables to be connected in the
filterbox of rack F are to be terminated by customer.
8 I̲n̲s̲t̲a̲l̲l̲a̲t̲i̲o̲n̲ ̲o̲f̲ ̲R̲e̲m̲o̲t̲e̲ ̲T̲e̲r̲m̲i̲n̲a̲l̲s̲ ̲S̲i̲t̲e̲ ̲0̲2̲A̲
The user terminals at CRT 02A will be installed
and connected to the stat. mux. rack. A local test
will be performed.
9 I̲n̲t̲e̲r̲n̲a̲l̲ ̲P̲o̲w̲e̲r̲ ̲C̲a̲b̲l̲e̲s̲
All internal power cables dismounted during transportation
will be reinstalled in the computer and line termination
unit.
10 P̲o̲w̲e̲r̲ ̲U̲p̲ ̲a̲n̲d̲ ̲T̲e̲s̲t̲
Powering up the computer and line termination units
will be performed in a certain sequence in order
to check that power groups and phases are correctly
distributed.
To ensure that the hardware will be able to support
all required CAMPS functions, a functional test
will be carried out according to the specified
site verification procedure.
11 I̲n̲s̲t̲a̲l̲l̲a̲t̲i̲o̲n̲ ̲o̲f̲ ̲T̲e̲r̲m̲i̲n̲a̲l̲s̲
All opto fibre cables for the User-, Maintenance-,
and Supervisory Terminals will be terminated with
special opto connectors. Before connecting the
cables to the optical modem boards, the cables
will be checked for supplying enough light emission.
The terminals will be powered up and tested locally.
12 T̲e̲s̲t̲ ̲o̲f̲ ̲T̲e̲r̲m̲i̲n̲a̲l̲s̲
All installed terminals including the PTP/PTR will
be tested according to the site acceptance test
procedure.
13 T̲e̲s̲t̲ ̲o̲f̲ ̲R̲e̲m̲o̲t̲e̲ ̲T̲e̲r̲m̲i̲n̲a̲l̲s̲
The remote terminals at CRT 02A will be tested
against the main site equipment.
14 P̲a̲c̲k̲i̲n̲g̲
Packing of CR test equipment, cleaning, mounting
of doors, etc.
15 I̲n̲v̲e̲n̲t̲o̲r̲y̲ ̲C̲h̲e̲c̲k̲
The CR installation team will conduct an inventory
check of all delivered CAMPS equipment, including
documents, test equipment and spare parts.
This inventory check will be witnessed by the customer.
16 C̲O̲M̲S̲E̲C̲ ̲T̲E̲S̲T̲
The CR installation team will run the system during
the one day COMSEC test in the CAMPS rack. COMSEC
will be trained for one day in running the user
terminals for further COMSEC test of these terminals.
17 T̲R̲A̲V̲E̲L̲T̲I̲M̲E̲
3 I̲N̲S̲T̲R̲U̲C̲T̲I̲O̲N̲S̲ ̲T̲O̲ ̲T̲H̲E̲ ̲M̲A̲I̲N̲ ̲S̲I̲T̲E̲
This section contains instructions to the main site
concerning the site assistance and support to CR during
installation. As stated above these instructions are
to be discussed and finalized during the site verification
meetings.
3.1. T̲R̲A̲N̲S̲P̲O̲R̲T̲A̲T̲I̲O̲N̲ ̲T̲O̲ ̲I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲S̲I̲T̲E̲
a) The equipment will be moved to the installation
site by the transportation company.
The site will assist the installation team/CR representative
as follows:
- Escort the transportation personnel.
- Point out the rooms for the 10 CR delivered
user terminal tables.
- Point out the equipment entry route.
- See to that the corridors on the entry route
are cleared.
- See to that the installation areas are cleared.
- See to that all site provided terminal tables
are cleared.
- Provide site truck/trolley/pushwaggon as available
upon request by the transportation company.
3.2 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲P̲R̲E̲P̲A̲R̲A̲T̲I̲O̲N̲S̲ ̲A̲N̲D̲ ̲S̲U̲P̲P̲O̲R̲T̲
The site is requested to provide the following preparations
and support prior to or during CR's presence at site.
1 Clear the CAMPS installation area.
2 Provide/clear tables for the user terminals to
be installed on customer provided tables.
3 Clear the equipment entry route from unloading
area to CAMPS equipment room and from unloading
area to storage area. The equipment entry route
is described in the site survey report.
4 Provide escort of the transportation personnel.
5 Provide temporary storage area for the equipment
specified in Table 2.1. The storage area required
is specified in the site survey report.
6 Provide access to site, access badges to be ready
at arrival of the installation team. Request for
access and identification credentials of the team
members will be forwarded through SHAPE.
7 Provide access to commercial telephone and telex
allowing for international communication. The use
to be reimbursed by CR.
8 Provide access to canteens or messes for CR personnel.
9 Provide emergency medical aid in case of accidents.
10 Provide access to reproduction facilities, if available.
11 Provide office space and furniture including desks,
chairs, and cabinets for classified and non-classified
material. Space and furniture for two persons are
required. Also storage space for tools and test
equipment (locked room or cabinets) is requested.
12 Provide site truck/trolley/pushwaggon for transportation
in the corridors, if available and upon request.
3.3 S̲H̲I̲P̲M̲E̲N̲T̲ ̲C̲O̲N̲T̲A̲I̲N̲E̲R̲S̲
As explained in section 2.1, the equipment is shipped
in several different continers; many of these are reusable.
It is, therefore, recommended that the site stores
1-2 empty containers for later use.
The installation team will point out the containers
which are recommended for later reuse to the SHAPE/site
representatives and the remaining containers will be
discarded by CR.
4 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲T̲O̲O̲L̲S̲ ̲A̲N̲D̲ ̲T̲E̲S̲T̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲
Besides a set of common standard multipurpose hand-tools,
the below listed tools and test equipments (table 4.1
and 4.2) will be used during the installation and checkout
of the CAMPS System.
Item 1-13 of table 4.1 is used for Opto-Cable termination.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
REF.
INSTALL.
I̲T̲E̲M̲ ̲ ̲D̲E̲S̲C̲R̲I̲P̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲P̲A̲R̲A̲.̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 CABLE KNIFE WEIDMULLER AM. 1 5.11.2
2 CABLE HAND-STRIPPER EXELITE # 100/101-S 5.11.2
3 KEVLAR SCISSORS EROP 24 5.11.2
4 T-STRIPPER IDEAL 45…0e….…0f…125(YELLOW) 5.11.2
5 HOT COIL/TRAFO ITT 5.11.2
6 FISH LINE 5.11.2
7 FERULE CRIMPING TOOL METRIC/AMPHENOL 5.11.2
8 FIBRE CLEAVER ITT SAPHIRE BLADE 5.11.2
9 SNAPPING TOOL METRIC/VERSITRON(58-59) 5.11.2
10 MICROSCOPE STRUERS/A23140 5.11.2
11 POLISHING FIXTURE METRIC/OFTI NR. 1 5.11.2
12 POLISHING FIXTURE METRIC/OFTI NR. 2 5.11.2
13 HEAT-GUN MASTERMITE 5.11.2
14 CRIMPING TOOL STOCKO W248 5.3
15 WRENCH 130mm BACHO 5.2
16 WRENCH 150mm BACHO 5.2
17 PIPE WRENCH 150mm BACHO 5.2
18 DRILLING MACHINE BACHO 5.2
19 HIGH SPEED DRILLS SET 3-16mm 5.2
20 STANDARD HOLE SAW 48mm STARRETT 5.2/5.3
21 STANDARD HOLE SAW 76mm STARRETT 5.2/5.3
22 STANDARD HOLE SAW 29mm STARRETT 5.2/5.3
23 CRIMPING TOOL STOCKO W236 5.3
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
TABLE 4.1
INSTALLATION TOOLS.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
REF.
INSTALL.
I̲T̲E̲M̲ ̲ ̲D̲E̲S̲C̲R̲I̲P̲T̲I̲O̲N̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲P̲A̲R̲A̲.̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 MULTIMETER FLUKE DMM 8020A 5.0
2 DATA COMM. TESTER TEKTRONIX 834 5.10,
5.11
3 TEST SET 921-T NU DATA 921-T 5.10
-
5.17
4 OPTICAL MULTIMETER PHONDDYNE 11XE 5.15
5 OSCILLOSCOPE TEKTRONIX 465 B 5.0
6 V24 MONITOR MODULE CR 5.14
7 V2V LOOPBACK ADAPTER CR 5.14
8 LTU LOOPBACK ADAPTER CR 5.14
9 LTUX-S LOOPBACK ADAPTER CR 5.14
10 LIA-N LOOPBACK ADAPTER CR 5.14
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
TABLE 4.2
TEST EQUIPMENT.
5 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲S̲I̲T̲E̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲
5.1 G̲E̲N̲E̲R̲A̲L̲
The following step by step installation procedure contains
a detailed instruction set of how to install the CR
delivered computer racks, supervisory positions, maintenance
position, and user terminals.
The major tasks of the installation sequence are:
5.2 Mechanical rack assembly
5.3 Termination of external power cables and mounting
of conduits
5.4 Installation of external signal cables and
mounting of conduits rack C, D, and F.
5.5 Remounting of racks
5.6 Installation and termination of internal signal
cables
5.7 Installation of external signal cables
5.8 Connection of internal power cables
5.9 Power up and check out
5.10 Inspection of status leds
5.11 Installation of Delta VDU
5.12 Installation of Tracor MSP
5.13 Installation of PTP/PTR
5.14 Test of Supp/User Terminals
5.15 Test of PTP/PTR
5.16 H/W Test Processor/Line term. units
5.17 Inventory check
Throughout the installation instruction, references
are made to the ATBB-Drawings (Doc. PAB/CPS/ATB/002)
and the CAMPS Hardware Breakdown/Hardware Tree (Doc.
CPS/SDS/017).
5.2 M̲E̲C̲H̲A̲N̲I̲C̲A̲L̲ ̲R̲A̲C̲K̲ ̲A̲S̲S̲E̲M̲B̲L̲Y̲
5.2.1 U̲n̲p̲a̲c̲k̲i̲n̲g̲ ̲o̲f̲ ̲R̲a̲c̲k̲s̲
a) Each of the 7 EMI racks for the main site are separately
packed in the original wooden container. The racks
should remain packed during site internal transportation
and only be unpacked close to the installation
site, but if the space along the access route is
limited, the racks can be unpacked before transportation
to the installation site. The racks are unpacked
as follows:
b) Remove the top cover of the wooden container by
demounting the 3 EA 1/4 x 2 1/2" bolts on each
side of the container and the 4 EA 1/2 - 13 x 2"
bolts, one in each top corner (see Figure 5.2.1).
c) The 4 walls of the container are removed by loosening
the 21 EA 1/4 x 2 1/2" bolts on each short side.
d) The rack is bolted to the container bottom in each
corner by a 1/2 - 13 x 2 1/2" bolt.
e) These bolts are removed from under the container
bottom.
Figure 5.2.1
Unpacking Procedure - EMI Rack
5.2.2 T̲r̲a̲n̲s̲p̲o̲r̲t̲a̲t̲i̲o̲n̲ ̲t̲o̲ ̲I̲n̲s̲t̲a̲l̲l̲a̲t̲i̲o̲n̲ ̲S̲i̲t̲e̲
a) After unpacking, the front and rear doors of the
racks must be removed. Check that serial numbers
in
the racks correspond to the serial numbers of the
doors.
b) Be careful not to damage the gaskets of the doors.
c) Depending on means of transportation, 4 eyelets
can be mounted in the top of the rack in the position
of the removed 4 ea 1/2 - 13 x 2" bolts.
d) 5 terminal tables out of the CR delivered 10 tables
are moved into the CAMPS area for the maintenance
and supervisor positions.
e) The storage cabinet is moved into the CAMPS area.
f) All terminals (18 ea VDU and 8 ea MSP) are distributed
to their respective installation sites, unpacked
and the empties removed.
5.2.3 R̲e̲m̲o̲v̲a̲l̲ ̲o̲f̲ ̲U̲p̲p̲e̲r̲ ̲C̲r̲a̲t̲e̲s̲ ̲a̲n̲d̲ ̲M̲-̲F̲a̲n̲s̲
a) To get access for bolting the single racks into
3 bay and 4 bay units, the upper crate in racks
B and C must be removed.
b) Dismount all connected front and rear cables.
c) Dismount the power cables on the rear side of the
M-fan in racks B and C.
Loosen the 4 6mm front screws and pull out the
fan units from the front of the racks.
d) Loosen the 8 (M-crate) 6mm front screws and pull
out the crates by the handles from the front of
the racks.
Figure 5.2.2
Mounting of Gaskets
5.2.4 R̲e̲m̲o̲v̲a̲l̲ ̲o̲f̲ ̲M̲a̲i̲n̲s̲ ̲S̲w̲i̲t̲c̲h̲e̲s̲
a) To get access for bolting the rack in the bottom,
the mains switches in rack B, C, E, and G must
be removed.
b) Dismount the power cables and the ground wire on
the rear side of the mains switches.
c) Loosen the 4 6mm front screws and pull out the
mains switches from the front of the racks.
5.2.5 M̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲L̲e̲v̲e̲l̲l̲e̲r̲s̲
The 4 levellers are mounted from under the racks two
by two, by tilting the racks (see ATBB drawing 115)
The levellers are mounted to a distance of 40 mm between
the bottom of the rack and the floor.
5.2.6 M̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲G̲a̲s̲k̲e̲t̲s̲
a) To secure a correct shielding between the racks,
gasket strips must be mounted before boltering
the racks into 3 or 4 BAY units. See fig. 5.2.2.
The gaskets, having pressure sensitive tape adhesive,
must be applied at room temperature as follows:
b) Clean the mounting surface for old glue, if necessary,
with a laquer thinner (acetone or tri-chlorethylene).
c) Cut and trim the gasket strip with scissors.
d) Peel off the protective paper backing.
e) Be sure that the strip is in correct position and
then press down firmly.
5.2.7 L̲e̲v̲e̲l̲l̲i̲n̲g̲ ̲a̲n̲d̲ ̲B̲o̲l̲t̲i̲n̲g̲ ̲o̲f̲ ̲R̲a̲c̲k̲s̲
a) The racks are aligned one by one to allow the 1/4-20
x 7/8 LG bolts to pass through the frames of the
cabinets.
b) The single racks A, B, and C are bolted together
to form the 3-bay processor rack assembly.
c) The single racks D, E, F, and G are bolted together
to form the 4-bay line termination rack assembly
(for details ref. ATBB drawings 110/115).
d) When all bolts are placed (24 bolts between each
pair of racks), the bolts are tightened crosswise.
e) Observe that a min. of 50 mm space must be kept
between rack C and rack D.
f) When all bolts have been tightened, the levellers
must again be adjusted to ensure equal distribution
of the floor load.
C̲A̲U̲T̲I̲O̲N̲: Before tightening the bolts, check that
all gaskets between the racks are
undamaged.
5.2.8 I̲n̲s̲p̲e̲c̲t̲i̲o̲n̲/̲R̲e̲p̲a̲i̲r̲ ̲o̲f̲ ̲G̲a̲s̲k̲e̲t̲s̲
a) If by accident parts of the gaskets are damaged
during transportation, these parts must be exchanged
to secure a correct shielding. The demolated part
of the gaskets are cut by a knife and removed.
b) For mounting details see 5.2.6.
5.2.9 M̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲P̲o̲w̲e̲r̲ ̲L̲i̲n̲e̲ ̲F̲i̲l̲t̲e̲r̲s̲ ̲R̲a̲c̲k̲ ̲A̲,̲ ̲B̲,̲ ̲a̲n̲d̲ ̲E̲
a) Place the power line filter (PLF) below the two
knockouts in the top of the rack (see ATBB drawing
121)
The 2 1/2" male adaptor, welded to the PLF, must
be inserted through the left hand knockout
b) Place the tightening nut from the outside of the
EMI rack.
c) Insert the 2 1/2" to 1 1/2" reducing bushing through
the right hand knockout into the PLF.
d) Mount the 1 1/2" steel tube into the reducing bushing.
It is very important to the shielding effectiveness
that the fittings are extremely tightened.
5.2.10 R̲e̲m̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲U̲p̲p̲e̲r̲ ̲C̲r̲a̲t̲e̲s̲ ̲a̲n̲d̲ ̲M̲-̲f̲a̲n̲s̲
a) The upper crates of rack B and C are reinserted
and tightened by the 8 6mm front screws.
b) The M-fans of rack B and C are reinserted and tightened
by the 4 6mm front screws.
c) Connect the ground wires of the crates and fans.
All removed signal cables are to be reinstalled during
step 5.6.
5.2.11 R̲e̲m̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲M̲a̲i̲n̲s̲ ̲S̲w̲i̲t̲c̲h̲e̲s̲
a) The mains switches are reinserted from the front
of the racks and tightened by the 4 6mm front
screws.
b) Reconnect the ground wires to the panel mounting
rails.
The internal power cables are to be reinstalled during
step 5.8.
5.3 INSTALLATION OF EXTERNAL POWER CABLES AND MOUNTING
OF C̲O̲N̲D̲U̲I̲T̲S̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲
C̲A̲U̲T̲I̲O̲N̲
BEFORE TERMINATING THE EXTERNAL POWER CABLES, ASSURE
THAT THE MAIN CIRCUIT BREAKER IN THE CAMPS PDB IS DISCONNECTED.
5.3.1 P̲o̲w̲e̲r̲ ̲C̲a̲b̲l̲e̲s̲ ̲R̲a̲c̲k̲ ̲A̲
a) Mount the 1 1/2" steel tube through the outer nut
and washer into the metallic cable duct above rack
A. Fasten the steel tube by the inner nut from
inside the cable duct (see ATBB drawing no. 121).
b) The 48 mm metallic conduit is mounted on the fittings
of the J-box (metallic cable duct) and the power
line filter and tightened by the 4 clamps.
c) Power cables Nos. 1, 2 and 3 together with the
insolated ground wire are pulled through the cable
inlet into the power line filter (see ATBB drawing
121).
d) To get access to the PLF, remove the metallic cover
fastened by 4 screws during transportation. The
remaining 26 screws are shipped attached to the
inside wall of PLF. The cables and the ground wire
are dismantled and terminated with cable shoes.
For details of the connection to the terminal board
ref. ATBB drawing 121.
5.3.2 P̲o̲w̲e̲r̲ ̲C̲a̲b̲l̲e̲s̲ ̲R̲a̲c̲k̲ ̲B̲
Repeat step 5.3.2 for power cables No. 4, 5, 6, and
the insulated ground wire in rack B, Power Line Filter.
5.3.3 P̲o̲w̲e̲r̲ ̲C̲a̲b̲l̲e̲s̲ ̲R̲a̲c̲k̲ ̲E̲
Repeat step 5.3.2 for power cables no. 7, 8, 9, and
the insulated ground wire in rack E, Power Line Filter.
5.4 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲E̲X̲T̲E̲R̲N̲A̲L̲ ̲S̲I̲G̲N̲A̲L̲ ̲C̲A̲B̲L̲E̲S̲ ̲A̲N̲D̲ ̲M̲O̲U̲N̲T̲I̲N̲G̲
̲O̲F̲ ̲C̲O̲N̲D̲U̲I̲T̲S̲ ̲A̲T̲ ̲R̲A̲C̲K̲ ̲C̲,̲ ̲D̲,̲ ̲A̲N̲D̲ ̲F̲.̲
5.4.1 R̲a̲c̲k̲ ̲D̲,̲ ̲S̲u̲p̲.̲/̲M̲a̲i̲n̲t̲.̲/̲U̲s̲e̲r̲ ̲P̲o̲s̲.̲ ̲C̲a̲b̲l̲e̲s̲
C̲A̲U̲T̲I̲O̲N̲
Be specially careful when installing the opto fibre
cables. Min. bending radius is 13 mm.
a) Opto cables W811-812/W815-817/W847-849 are installed
in the PVC duct between rack D and the maint./sup.
positions in the CAMPS area. See ATBB dwg. 110.
b) Mount the fittings for the PVC conduit to the cable
duct above rack D (see ATBB drawing 116).
c) Mount the fittings for the other end of the PVC
conduit in the left hand knockout of rack D.
d) Mount the 75 mm PVC conduit between the cable duct
and the waveguide.
e) Opto cables W811-812/W815-817/W847-849 are pulled
through the left hand penetration of rack D into
the internal PVC cable duct.
f) Opto cables W811-812 are run through the internal
cable duct and out through the right hand penetration
of rack D.
The opto cables enter rack C together with the
interrack cables and are terminated on the front
side of the adapter crate through the cable channel
assembly. See ATBB dwg. 117.
g) Opto cables W815-817/W847-849 are run through the
internal cable ducts of the line termination racks
and terminated on the front side of the TDX-crates
according to ATBB dwg. 125.
h) Opto cables W819-832/W851-854 coming from the user
terminals are pulled through the left hand bottom
penetration and into rack D. The opto cables are
run through the internal cable ducts of the line
termination racks and terminated on the front of
the TDX-crates according to ATBB dwg. 125.
5.4.2 C̲a̲b̲l̲e̲ ̲B̲u̲n̲c̲h̲ ̲R̲a̲c̲k̲ ̲C̲ ̲t̲o̲ ̲R̲a̲c̲k̲ ̲D̲
a) Mount the male adapter between the two 90…0e…o…0f… fittings.
Adjust for correct distance between knockouts in
rack C and D (see ATBB drawing 115/116). Mount
the 30 mm male adapter through the knockout into
the 90…0e…o…0f… fitting. Tighten fittings by the inner
nut.
b) Cables W904-914, stored in rack D during transportation,
are pulled through the metallic conduit into rack
C and distributed according to ATTB dwg. 117.
c) Yellow label on cables means pin 1 (ground) connected.
This end must be connected in rack C.
5.4.3 R̲a̲c̲k̲ ̲F̲ ̲(̲L̲S̲M̲/̲O̲t̲h̲e̲r̲ ̲C̲a̲b̲l̲e̲s̲)̲
a) Mount the 2 1/2" steel tube through the outer nut
into the right hand penetration of rack F and the
filter box. Tighten the fitting from inside the
filterbox by the inner nut (see ATBB drawing 116).
b) Repeat step a) for the left hand penetration of
rack F.
c) Repeat step a) for the other end of the conduit
to be mounted in the ferrous duct above rack F
(see ATBB drawing 110/116).
d) Mount the 75 mm metallic conduit on the outside
of the steel tubes and tighten it by the clamps.
e) The low speed medium (LSM) cables W855-859 and
W814 for the PTP/PTR are pulled through the waveguide
of the metallic duct, through the left hand pene-
tration of rack F and into the filter box (see
ATBB drawing 125).
f) Other cables: W731 CCIS
W732 SCARS
W733 CRT
W741-742 Colocated Tare
W813 OCR
are pulled through the waveguide of the metallic
duct, through the right hand penetration of rack
F and into the filter box.
g) The metallic cables are now ready for termination
by H/N.
h) When the metallic cables have been connected by
H/N, see ATTB drawing 125, the cables will be finally
marked with cable No. markers.
5.5 R̲E̲M̲O̲U̲N̲T̲I̲N̲G̲ ̲O̲F̲ ̲R̲A̲C̲K̲S̲
5.5.1 M̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲D̲i̲s̲k̲ ̲D̲r̲i̲v̲e̲s̲
The 3 separately packed disk drives, 1 MMD for rack
A, 1 SMD for rack B, and 1 MMD for rack C are unpacked
and installed according to the instructions in the
CAMPS Packing Procedure, ref. doc. CPS/AUX/021.
5.5.2 M̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲F̲l̲o̲p̲p̲y̲ ̲D̲i̲s̲k̲ ̲S̲t̲a̲t̲i̲o̲n̲
a) Remove the front panel located below the watchdog
crate. (Pos. 1A2A6).
b) The floppy disk cabinet containing the two floppy
disk drives is installed on the two slides.
c) The cabinet is locked by mounting and tightening
the front panel by the 6 6mm screws.
5.5.3 M̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲S̲t̲a̲t̲.̲ ̲M̲u̲x̲.̲
a) The separately packed stat. mux is mounted in its
housing left during the transportation in rack
G.
b) The stat. mux. slided into the housing from the
front and locked by the left-hand and righthand
locking screws.
5.5.4 M̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲M̲o̲d̲u̲l̲e̲s̲
a) For correct physical positioning of the separately
packed modules, refer to the packing list. The
packing list states the serial No. of the unit,
the crate assy No., the slot No. in the crate and
the address of the physical position in the system.
b) The modules are slided into the print guide and
when the edge connector of the print has entered
the connector of the motherboard, the modules are
fastened by the two fixing screws on the front
of the modules.
5.6 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲A̲N̲D̲ ̲T̲E̲R̲M̲I̲N̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲I̲N̲T̲E̲R̲N̲A̲L̲ ̲S̲I̲G̲N̲A̲L̲ ̲C̲A̲B̲L̲E̲S̲
5.6.1 I̲n̲t̲e̲r̲n̲a̲l̲ ̲S̲i̲g̲n̲a̲l̲ ̲C̲a̲b̲l̲e̲s̲
a) Tables 5.6.2 through 5.6.19 list all internal signal
cables in the 3-bay processor rack assembly, and
the 4-bay line termination rack assembly, e.g.
also cables not dismounted during transportation.
b) The philosophy is to install/terminate or check
all cables within one crate at a time, starting
with processor crate assy No. 1.
c) The left-hand side of each table states the exact
location of a specific cable to be connected or
checked.
d) The right-hand side "going to/coming from" indicates
the termination point for the other end of the
cable.
e) It is recommended, after having connected one cable
according to the left-hand side of the table, that
the cable is laid down in the cable trays in the
direction of the termination point for the other
end (ref. the right-hand side of the table).
f) The termination at the other end of the cable is
performed when this step in the step-by-step procedure
is reached.
g) The column ILLUS "Cable Illustrations" refers to
the page No. in the CAMPS HARDWARE BREAKDOWN (CPS/SDS/017)
showing the physical cables with types of connectors.
h) The column DIAG "Cable Diagram" refers to the page
No. in the CAMPS HARDWARE BREAKDOWN (CPS/SDS/017)
showing the position of the actual cable in the
system.
i) For details of the interrack cabling see ATBB drawings
117 and 118.
U̲n̲d̲e̲r̲ ̲R̲E̲M̲A̲R̲K̲S̲ ̲p̲l̲e̲a̲s̲e̲ ̲n̲o̲t̲e̲:̲
D̲I̲S̲C̲O̲N̲ Cable has been disconnected.
The cable is not removed
from the rack cable tray
and the connector is to be
found near by the termination
point.
C̲O̲N̲ Cable has not been disconnected.
Check for correct W-number
in b̲o̲t̲h̲ ̲e̲n̲d̲s̲.
I̲ Internal Cable inside the
same rack. Cable must be
connected/checked in b̲o̲t̲h̲
̲e̲n̲d̲s̲ according to the right-
and left-hand part of the
table.
R̲A̲C̲K̲ ̲(̲A̲,̲ ̲B̲,̲ ̲C̲,̲ ̲e̲t̲c̲) Cable has been withdrawn
during transportation and
is now found in e.g. rack
A.
T̲a̲b̲l̲e̲ ̲5̲.̲6̲.̲2̲
P̲R̲O̲C̲E̲S̲S̲O̲R̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲#̲ ̲1̲ ̲R̲A̲C̲K̲ ̲A̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲
I̲l̲l̲u̲s̲ D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲ ̲ ̲
W 1 MIA A1A1A27 J2 CIA-A B A2A1A32 J1
46
51 CON
W 3 CCA A1A1A23 J1 CCA B A2A1A25 J1
46
51 RACK
C
CCBA B A2A4A10 J1
46
51 RACK
C
W 4 TIA A1A1A25 J1 X-NET A A1A1A8 J1
46
51 I
W 5 TIA A1A1A26 J1 X-NET A A1A1A9 J1
46
51 I
W13 MIA A1A1A27 J1 WCA B A2A4A11 J1
48
51 CON
W95 TSP A1A1A24 J1 THERMO A A1A1A10 *
50
53 DISCON
W96 TSA A1A1A24 J2 THERMO A A1A1A9 *
50
53 DISCON
* part of unit
T̲a̲b̲l̲e̲ ̲5̲.̲6̲.̲3̲
X̲-̲N̲E̲T̲ ̲O̲U̲T̲L̲E̲T̲S̲ ̲R̲A̲C̲K̲ ̲A̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W17 X-NET A1A1A8 1-2 X-NET C A3A3A11 1-2 48 25/51 CON
W18 X-NET A1A1A8 4-5 X-NET C A3A3A11 4-5 48 25/51 CON
W19 X-NET A1A1A9 1-2 X-NET C A3A3A12 1-2 48 25/51 CON
W20 X-NET A1A1A9 4-5 X-NET C A3A3A12 4-5 48 25/51 CON
T̲a̲b̲l̲e̲ ̲5̲.̲6̲.̲4̲
D̲I̲S̲K̲ ̲D̲R̲I̲V̲E̲ ̲R̲A̲C̲K̲ ̲A̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W 9 DISK 1A1A5 J3 DCA B A2A1A30 J1 47 51 RACK
B
W12 DISK 1A1A5 J2 DCA B A2A1A30 J2 47 51 RACK
B
T̲a̲b̲l̲e̲ ̲5̲.̲6̲.̲5̲
C̲H̲A̲N̲N̲E̲L̲ ̲U̲N̲I̲T̲ ̲R̲A̲C̲K̲ ̲B̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W 1 CIA-A A2A1A32 J1 MIA A A1A1A27 J2 46 51 RACK
A
W 2 CIA-B A2A1A31 J1 MIA C A3A1A27 J2 46 51 RACK
C
W 3 CCA A2A1A25 J1 CCBA B A2A4A10 J1 46 51 RACK
C
W 3 CCBA A2A4A10 J1 CCA C A3A1A23 J1 46 51 RACK
C
W 6 SFA A2A1A27 J1 FD B A2A5 J2 47 51 I
W 7 DCA A2A1A28 J1 DISK C A3A8 J3 47 51 DISCON
W 8 DCA A2A1A29 J1 DISK B A2A7 IJ3 47 51 I
W 9 DCA A2A1A30 J1 DISK A A1A5 J3 47 51 DISCON
W10 DCA A2A1A28 J2 DISK C A3A8 J2 47 51 DISCON
W11 DCA A2A1A29 J2 DISK B A2A7 IJ2 47 51 I
W12 DCA A2A1A30 J2 DISK A A1A5 J2 47 51 DISCON
W23 LIA A2A1A23 J3 BP8 C A3A5A24 J2 48 51 DISCON
W24 LIA A2A1A23 J1 BP8 C A3A5A24 J1 48 51 DISCON
W25 LIA A2A1A22 J1 BP8 C A3A5A25 J1 48 51 DISCON
W26 LIA A2A1A21 J1 BP8 C A3A5A25 J2 48 51 DISCON
W97 TSP A2A1A26 J1 THERM B A2A11 * 50 53 DISCON
W98 TSP A2A1A26 J2 THERM B A2A10 * 50 53 DISCON
* part of unit
T̲a̲b̲l̲e̲ ̲5̲.̲6̲.̲6̲
W̲A̲T̲C̲H̲D̲O̲G̲ ̲C̲R̲A̲T̲E̲ ̲R̲A̲C̲K̲ ̲B̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W 3 CCBA A2A4A10 J1 CCA B A2A1A25 J1 46 51 RACK
C
W13 WCA A2A4A11 J1 MIA A A1A1A27 J1 48 51 RACK
A
W14 WCA A2A4A11 J2 MIA C A3A1A27 J1 48 51 RACK
C
W27 WCA A2A4A11 J4 BP8 C A3A5A25 J3 48 51 DISCON
W28 WCA A2A4A11 J3 BP8 C A3A5A25 J4 48 51 DISCON
T̲a̲b̲l̲e̲ ̲5̲.̲6̲.̲7̲
P̲R̲O̲C̲E̲S̲S̲O̲R̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲#̲ ̲2̲ ̲R̲A̲C̲K̲ ̲C̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W 2 MIA A3A1A27 J2 CIA-B B A2A1A31 J1 46 51 DISCON
W 3 CCA A3A1A23 J1 CCB C A3A16 J1 46 51 DISCON
W 3 CCA A3A1A23 J1 CCA B A2A1A25 J1 46 51 CON
W14 MIA A3A1A27 J1 WCA B A2A4A11 J2 48 51 DISCON
W15 TIA A3A1A25 J1 X-NET C A3A11 J1 48 51 I
W16 TIA A3A1A26 J1 X-NET C A3A12 J1 48 51 I
W99 TSP A3A1A24 J1 THERM C A3A14 * 50 53 DISCON
W100 TSP A3A1A24 J2 THERM C A3A13 *
50 53 DISCON
* part of unit
T̲a̲b̲l̲e̲ ̲5̲.̲6̲.̲8̲
X̲-̲N̲E̲T̲ ̲O̲U̲T̲L̲E̲T̲S̲ ̲ ̲R̲A̲C̲K̲ ̲C̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W17 X-NET 1A3A11 1-2 X-NET A 1A1A8 1-2 48 25/51 RACK
A
W18 X-NET 1A3A11 4-5 X-NET A 1A1A8 4-5 48 25/51 RACK
A
W19 X-NET 1A3A12 1-2 X-NET A 1A1A9 1-2 48 25/51 RACK
A
W20 X-NET 1A3A12 4-5 X-NET A 1A1A9 4-5 48 25/51 RACK
A
W905 X-NET 1A3A11 1-2 X-NET D 2A1A13 1-2 48 25/51 RACK
D
W906 X-NET 1A3A11 4-5 X-NET D 2A1A13 4-5 48 25/51 RACK
D
W907 X-NET 1A3A12 1-2 X-NET D 2A1A14 1-2 48 25/51 RACK
D
W908 X-NET 1A3A12 4-5 X-NET D 2A1A14 4-5 48 25/51 RACK
D
W904 CCB 1A3A16 J1 CCB D 2A1A19 J1 48 25 RACK
D
T̲a̲b̲l̲e̲ ̲5̲.̲6̲.̲9̲
D̲I̲S̲K̲ ̲D̲R̲I̲V̲E̲ ̲R̲A̲C̲K̲ ̲C̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W 7 DISK 1A3A8 J2 DCA B A2A1A28 J1 47 51 RACK
B
W10 DISK 1A3A8 J3 DCA B A2A1A28 J2 47 51 RACK
B
T̲a̲b̲l̲e̲ ̲5̲.̲6̲.̲1̲0̲
A̲D̲A̲P̲T̲E̲R̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲R̲A̲C̲K̲ ̲C̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W23 BP8 A3A5A24 J2 LIA B A2A1A23 J3 48 51 RACK
B
W24 BP8 A3A5A24 J1 LIA B A2A1A23 J1 48 51 RACK
B
W25 BP8 A3A5A25 J2 LIA B A2A1A22 J1 48 51 RACK
B
W26 BP8 A3A5A25 J1 LIA B A2A1A21 J1 48 51 RACK
B
W27 BP8 A3A5A25 J3 WCA B A2A4A11 J4 48 51 RACK
B
W28 BP8 A3A5A25 J4 WCA B A2A4A11 J3 48 51 RACK
B
W909 L/L-AD A3A5A9 J1 FILTER F 2A3A17 J31 51 RACK
F
W910 L/L-AD A3A5A10 J1 FILTER F 2A3A17 J30 51 RACK
F
W913 L/L-AD A3A5A14 J1 FILTER F 2A3A17 J27 51 RACK
F
W914 L/L-AD A3A5A15 J1 FILTER F 2A3A17 J26 51 RACK
F
T̲a̲b̲l̲e̲ ̲5̲.̲6̲.̲1̲1̲
R̲A̲C̲K̲ ̲D̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W101 BSM-P A1A1A25 J2 BSM-P E A2A9A25 J2 115 121 RACK
E
W101 BSM-P A1A1A25 J2 BSM-P D A1A3A25 J2 115 121 RACK
E
W101 BSM-P A1A3A25 J2 BSM-P D A1A7A25 J2 115 121 RACK
E
W101 BSM-P A1A7A25 J2 BSM-P D A1A9A25 J2 115 121 RACK
E
W101 BSM-P A1A9A25 J2 CCB D A1A20 J1 115 121 RACK
E
W104 BSM-X A1A1A3 J1 TDX CNT D A1A1A2 J1 115 121 I
W105 BSM-X A1A9A3 J1 TDX CNT D A1A9A2 J1 115 121 I
W106 TDX CNT A1A1A2 J2 X-NET D A1A15 J1 116 121 I
W107 TDX CNT A1A9A2 J2 X-NET D A1A25 J1 116 121 I
W108 BSM-P A1A1A25 J3 X-NET D A1A13 J1 116 121 CON
W109 BSM-P A1A1A25 J1 X-NET D A1A14 J1 116 121 CON
W110 BSM-P A1A3A25 J3 X-NET D A1A16 J1 116 121 CON
W111 BSM-P A1A3A25 J1 X-NET D A1A17 J1 116 121 CON
W112 BSM-P A1A7A25 J3 X-NET D A1A21 J1 116 121 CON
W113 BSM-P A1A7A25 J1 X-NET D A1A22 J1 116 121 CON
W114 BSM-P A1A9A25 J3 X-NET D A1A23 J1 116 121 CON
W115 BSM-P A1A9A25 J1 X-NET D A1A24 J1 116 121 CON
W141 X-NET A1A14 1-2 X-NET D A1A17 1-2 116 121 CON
W142 X-NET A1A14 4-5 X-NET D A1A17 4-5 116 121 CON
W143 X-NET A1A13 1-2 X-NET D A1A15 1-2 116 121 CON
W144 X-NET A1A13 4-5 X-NET D A1A15 4-5 116 121 CON
W145 X-NET A1A17 1-2 X-NET D A1A22 1-2 116 121 CON
W146 X-NET A1A17 4-5 X-NET D A1A22 4-5 116 121 CON
W147 X-NET A1A15 4-5 X-NET D A1A16 4-5 116 121 CON
W148 X-NET A1A15 1-2 X-NET D A1A16 1-2 116 121 CON
W149 X-NET A1A22 1-2 X-NET D A1A24 1-2 116 121 CON
W150 X-NET A1A22 4-5 X-NET D A1A24 4-5 116 121 CON
W151 X-NET A1A16 1-2 X-NET D A1A21 1-2 116 121 CON
W152 X-NET A1A16 4-5 X-NET D A1A21 4-5 116 121 CON
W153 X-NET A1A24 1-2 X-NET D A1A25 4-5 116 121 CON
W154 X-NET A1A24 4-5 X-NET D A1A25 1-2 116 121 CON
W155 X-NET A1A21 1-2 X-NET D A1A23 1-2 116 121 CON
W156 X-NET A1A21 4-5 X-NET D A1A23 4-5 116 121 CON
W157 X-NET A1A25 4-5 X-NET E A1A14 1-2 116 95/121 RACK
E
W158 X-NET A1A25 1-2 X-NET E A1A14 4-5 116 95/121 RACK
E
T̲a̲b̲l̲e̲ ̲5̲.̲6̲.̲1̲2̲
R̲A̲C̲K̲ ̲D̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W159 X-NET A1A23 1-2 X-NET E 2A2A13 1-2 116 95/121 RACK
E
W160 X-NET A1A23 4-5 X-NET E 2A2A13 4-5 116 95/121 RACK
E
W247 BP 8 A1A3A24 J2 MUX G 2A4A3 J5 117 123 CON
W248 BP 8 A1A3A23 J1 MUX G 2A4A3 J6 117 123 CON
W249 BP 8 A1A3A23 J2 MUX G 3A4A3 J7 117 123 CON
W904 CCB A1A20 J1 CCB C 1A3A16 J1 115 121 CON
W905 X-NET A1A13 1-2 X-NET C 1A3A11 1-2 116 94/121 CON
W906 X-NET A1A13 4-5 X-NET C 1A3A11 4-5 116 94/121 CON
W907 X-NET A1A14 1-2 X-NET C 1A3A12 1-2 116 94/121 CON
W908 X-NET A1A14 4-5 X-NET C 1A3A12 4-5 116 94/121 CON
W293 TSP A1A3A22 J1 THERMO D A1A18 * 118 127 I
W294 TSP A1A9A22 J1 THERMO D A1A26 * 118 127 I
* part of unit
T̲a̲b̲l̲e̲ ̲5̲.̲6̲.̲1̲3̲
R̲A̲C̲K̲ ̲E̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W101 BSM-P A2A1A25 J2 BSM-P F A3A3A25 J2 115 121 DISCON
W101 BSM-P A2A1A25 J2 BSM-P E A2A3A25 J2 115 121 DISCON
W101 BSM-P A2A3A25 J2 BSM-P E A2A7A25 J2 115 121 DISCON
W101 BSM-P A2A7A25 J2 BSM-P E A2A9A25 J2 115 121 DISCON
W101 BSM-P A2A9A25 J2 BSM-P D A1A1A25 J2 115 121 DISCON
W120 BSM-P A2A7A25 J3 X-NET E A2A19 J1 116 121 CON
W121 BSM-P A2A7A25 J1 x-NET E A2A20 J1 116 121 CON
W122 BSM-P A2A9A25 J3 X-NET E A2A21 J1 116 121 CON
W123 BSM-P A2A9A25 J1 X-NET E A2A22 J1 116 121 CON
W161 X-NET A2A14 1-2 X-NET E A2A16 1-2 116 121 CON
W162 X-NET A2A14 4-5 X-NET E A2A16 4-5 116 121 CON
W163 X-NET A2A13 1-2 X-NET E A2A15 1-2 116 121 CON
W164 X-NET A2A13 4-5 X-NET E A2A15 4-5 116 121 CON
W165 X-NET A2A16 1-2 X-NET E A2A20 1-2 116 121 CON
W166 X-NET A2A16 4-5 X-NET E A2A20 4-5 116 121 CON
W167 X-NET A2A15 1-2 X-NET E A2A19 1-2 116 121 CON
W168 X-NET A2A15 4-5 X-NET E A2A19 4-5 116 121 CON
W169 X-NET A2A20 1-2 X-NET E A2A22 1-2 116 121 CON
W170 X-NET A2A20 4-5 X-NET E A2A22 4-5 116 121 CON
W171 X-NET A2A19 1-2 X-NET E A2A21 1-2 116 121 CON
W172 X-NET A2A19 4-5 X-NET E A2A21 4-5 116 121 CON
W181 X-NET A2A22 1-2 X-NET G A4A14 1-2 116 121 RACK
G
W182 X-NET A2A22 4-5 X-NET G A4A14 4-5 116 121 RACK
G
W183 X-NET A2A21 1-2 X-NET G A4A13 1-2 116 121 RACK
G
W184 X-NET A2A21 4-5 X-NET G A4A13 4-5 116 121 RACK
G
W295 TSP A2A3A22 J1 THERMO E A2A17 *
117 127 I
W296 TSP A2A9A22 J1 THERMO E A2A23 *
117 127
I
* part of unit
T̲a̲b̲l̲e̲ ̲5̲.̲6̲.̲1̲4̲
T̲D̲X̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲5̲ ̲R̲A̲C̲K̲ ̲E̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W201 L/L AD A2A9A7 J1 IDF F A3A17 J1 117 123 RACK
F
W202 L/L AD A2A9A7 J2 IDF F A3A17 J2 117 123 RACK
F
W203 L/L AD A2A9A7 J3 IDF F A3A17 J3 117 123 RACK
F
W204 L/L AD A2A9A7 J4 IDF F A3A17 J4 117 123 RACK
F
W205 L/L AD A2A9A14 J1 IDF F A3A17 J5 117 123 RACK
F
W225 L/L AD A2A9A14 J4 IDF F A3A17 J25 117 123 RACK
F
T̲a̲b̲l̲e̲ ̲5̲.̲6̲.̲1̲5̲
T̲D̲X̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲6̲ ̲R̲A̲C̲K̲ ̲E̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W232 L/L AD A2A7A10 J1 IDF F A3A17 J32 117 123 RACK
F
T̲a̲b̲l̲e̲ ̲5̲.̲6̲.̲1̲6̲
R̲A̲C̲K̲ ̲F̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W101 BSM-P A3A1A25 J2 CCB F A3A16 J1 115 121 CON
W102 CCB A3A16 J1 BSM-P G A4A7A25 J1 115 121 RACK
G
T̲a̲b̲l̲e̲ ̲5̲.̲6̲.̲1̲7̲
F̲I̲L̲T̲E̲R̲ ̲B̲O̲X̲ ̲ ̲R̲A̲C̲K̲ ̲F̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W201 IDF 2A3A17 J1 L/L AD E A2A3A7 J1 117 123 CON
W202 IDF 2A3A17 J2 L/L AD E A2A3A7 J2 117 123 CON
W203 IDF 2A3A17 J3 L/L AD E A2A3A7 J3 117 123 CON
W204 IDF 2A3A17 J4 L/L AD E A2A3A7 J4 117 123 CON
W205 IDF 2A3A17 J5 L/L AD E A2A3A14 J1 117 123 CON
W225 IDF 2A3A17 J25 L/L AD F A3A1A14 J1 117 123 CON
W232 IDF 2A3A17 J32 L/L AD F A3A1A10 J1 117 123 CON
W233 IDF 2A3A17 J33 L/L AD G A4A3 J9 117 123 RACK
F
W909 IDF 2A3A17 J31 L/L AD C A3A5A9 J1 123 CON
W910 IDF 2A3A17 J30 L/L AD C A3A5A10 J1 123 CON
T̲a̲b̲l̲e̲ ̲5̲.̲6̲.̲1̲7̲
F̲I̲L̲T̲E̲R̲ ̲B̲O̲X̲ ̲ ̲R̲A̲C̲K̲ ̲F̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W913 IDF 2A3A17 J27 L/L AD C A3A5A16 J1 123 CON
W914 IDF 2A3A17 J26 L/L AD C A3A5A17 J1 123 CON
OBSERVE THAT THE YELLOW LABELED END OF THE
CABLES BETWEEN IDF AND THE L/L ADP. MUST BE
CONNECTED AT THE L/L ADP.
T̲a̲b̲l̲e̲ ̲5̲.̲6̲.̲1̲8̲
R̲A̲C̲K̲ ̲G̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W102 BSM-P A4A9A25 J2 CCB F A3A16 J1 115 121 RACK
F
W128 BSM-P A4A9A25 J3 X-NET G A4A13 J1 116 121 CON
W129 BSM-P A4A9A25 J1 X-NET G A4A14 J1 116 121 CON
W181 X-NET A4A14 1-2 X-NET E A2A22 1-2 116 121 CON
W182 X-NET A4A14 4-5 X-NET E A2A22 4-5 116 121 CON
W183 X-NET A4A13 1-2 X-NET E A2A21 1-2 116 121 CON
W184 X-NET A4A13 4-5 X-NET E A2A21 4-5 116 121 CON
W233 MUX A4A3 J9 IDF F A3A17 J33 117 123 DISCON
W247 MUX A4A3 J5 BP 8 D A1A3A24 J2 117 123 DISCON
W248 MUX A4A3 J6 BP 8 D A1A3A23 J1 117 123 DISCON
W248 MUX A4A3 J7 BP 8 D A1A3A23 J2 117 123 DISCON
W298 TSP A4A7A22 J1 THERMO G A4A15 * 117 127 I
* part of unit
5.7 T̲E̲R̲M̲I̲N̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲E̲X̲T̲E̲R̲N̲A̲L̲ ̲S̲I̲G̲N̲A̲L̲ ̲C̲A̲B̲L̲E̲S̲
a) All external opto fibre cables located on the front
of the TDX- and adapter crates are cut, withdrawn
to the rear of the rack and terminated with special
opto connectors. For details of opto termination
procedures ref. Doc. No. 4.
b) All external metallic cables located in the filter
box (ref. 4.4) can now be terminated and connected
in the filter box by host nation technicians.
For distribution of the metallic cables inside
the filter box see ATBB drawing 125.
c) When terminated, all opto fibre cables are distributed
through the internal cables channels of the racks
and out through the cable channel assy below the
TDX and adapter crates (see ATBB drawings 117/125)
C̲A̲U̲T̲I̲O̲N̲
Be specially careful when installing the opto fibre
cables. Min. bending radius is 13mm.
d) The opto fibre cables are connected to the opto
T/R adapters from the front of the TDX crates according
to tables 5.7.2 through 5.7.7 (ref. ATBB drawing
125/102).
…86…1 …02… …02… …02… …02… …02…
T̲a̲b̲l̲e̲ ̲5̲.̲7̲.̲2̲
A̲D̲A̲P̲T̲E̲R̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲R̲A̲C̲K̲ ̲C̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲
N̲o̲t̲e̲s̲ ̲ ̲
W811 OPTO T/R 1A3A5A7 VDU MAINT.
POS. CAMPS
AREA
W812 OPTO T/R 1A3A5A8 MSP MAINT.
POS. CAMPS
AREA
T̲a̲b̲l̲e̲ ̲5̲.̲7̲.̲3̲
T̲D̲X̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲#̲ ̲1̲ ̲R̲A̲C̲K̲ ̲D̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲
N̲o̲t̲e̲s̲ ̲ ̲
W815 OPTO T/R 2A1A9A10 VDU ROOM 385 SUP.
P
W819 OPTO T/R 2A1A9A17 VDU ROOM 233 USER
P
W821 OPTO T/R 2A1A9A9 VDU ROOM 253 USER
P
W823 OPTO T/R 2A1A9A16 VDU ROOM 211/212 USER
P
W825 OPTO T/R 2A1A9A8 VDU ROOM 234 USER
P
W827 OPTO T/R 2A1A9A15 VDU ROOM 246 USER
P
W829 OPTO T/R 2A1A9A7 VDU ROOM 281 USER
P
W831 OPTO T/R 2A1A9A14 VDU ROOM 381 USER
P
T̲a̲b̲l̲e̲ ̲5̲.̲7̲.̲4̲
T̲D̲X̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲#̲ ̲2̲ ̲R̲A̲C̲K̲ ̲D̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲
N̲o̲t̲e̲s̲ ̲ ̲
W816 OPTO T/R 2A1A7A10 VDU ROOM 385
SUP.
P
W820 OPTO T/R 2A1A7A17 VDU ROOM 243
USER
P
W822 OPTO T/R 2A1A7A9 VDU ROOM 264A USER
P
W824 OPTO T/R 2A1A7A16 VDU ROOM 213
USER
P
W826 OPTO T/R 2A1A7A8 VDU ROOM 235
USER
P
W828 OPTO T/R 2A1A7A15 VDU ROOM 256
USER
P
W830 OPTO T/R 2A1A7A7 VDU ROOM 378/388 USER
P
W832 OPTO T/R 2A1A7A14 VDU ROOM 386
USER
P
T̲a̲b̲l̲e̲ ̲5̲.̲7̲.̲5̲
T̲D̲X̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲#̲ ̲3̲ ̲R̲A̲C̲K̲ ̲D̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲
N̲o̲t̲e̲s̲ ̲ ̲
W817 OPTO T/R 2A1A3A10 VDU ROOM 385
SUP.
P
T̲a̲b̲l̲e̲ ̲5̲.̲7̲.̲6̲
T̲D̲X̲ ̲C̲R̲A̲T̲E̲ ̲A̲S̲S̲Y̲ ̲#̲ ̲4̲ ̲R̲A̲C̲K̲ ̲D̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲
N̲o̲t̲e̲s̲ ̲ ̲
W847 OPTO T/R 2A1A1A10 MSP ROOM 385 SUP.
P
W848 OPTO T/R 2A1A1A17 MSP ROOM 385 SUP.
P
W849 OPTO T/R 2A1A1A9 MSP ROOM 385 SUP.
P
W851 OPTO T/R 2A1A1A8 MSP ROOM 253 USER
P
W852 OPTO T/R 2A1A1A15 MSP ROOM 235 USER
P
W853 OPTO T/R 2A1A1A7 MSP ROOM 246 USER
P
W854 OPTO T/R 2A1A1A14 MSP ROOM 386 USER
P
5.8 C̲O̲N̲N̲E̲C̲T̲I̲O̲N̲ ̲O̲F̲ ̲I̲N̲T̲E̲R̲N̲A̲L̲ ̲P̲O̲W̲E̲R̲ ̲C̲A̲B̲L̲E̲S̲
a) Tables 5.8.2 through 5.8.8 list all internal power
cables in the processor racks, the line termination
racks, and in the frequency stabilizer rack.
b) Use the tables as an installation step by step
procedure and as a checkout of cables already installed
(see ATBB drawings 117, 118, and 120).
c) All power plugs connected to fans and crates must
be secured by the connector spring mounted on the
male connector.
U̲N̲D̲E̲R̲ ̲R̲E̲M̲A̲R̲K̲S̲ ̲P̲L̲E̲A̲S̲E̲ ̲N̲O̲T̲E̲:̲
I̲ INTERNAL CABLE
Both ends of the cable must
be connected/checked in this
step (ref. left a̲n̲d̲ right
hand side of the table).
C̲O̲N̲ Cable has not been disconnected.
Check for correct W-number.
D̲I̲S̲C̲O̲N̲ Cable has been disconnected.
The cable is not removed from
the rack cable tray. The connector
is to be found near by the
termination point.
R̲A̲C̲K̲ ̲(̲A̲,̲ ̲B̲,̲ ̲C̲,̲ ̲E̲T̲C̲)̲ Cable has been withdrawn during
transportation and is now
found in e.g. rack A.
T̲a̲b̲l̲e̲ ̲5̲.̲8̲.̲2̲
R̲A̲C̲K̲ ̲A̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W40 PROC A1A1 J1 PDP A A1A12 J1 49 52 CONN/I
W41 PROC A1A1 J2 PDP A A1A12 J7 49 52 CONN/I
W42 D-FAN A1A2 J1 PDP A A1A12 J2 49 52 CONN/I
W43 D-FAN A1A2 J2 PDP A A1A12 J6 49 52 CONN/I
W45 PDP A1A12 J3 CHAN B A2A1 J2 49 52 RACK
B
W47 PDP A1A12 J4 D-FAN B A2A2 J2 49 52 RACK
B
W53 DISK A1A5 J1 MAINS A A1A7 J3 49 52 DISCON/I
W58 PDP A1A12 J5 ADAP-P C A3A5A23 J1 49 52 RACK
C
W59 MAINS A1A7 J4 PLF A A1A13 J5 49 52 CON/I
W60 PLF A1A13 J3 MAINS B A2A9 J4 49 52 RACK
D
W61 PLF A1A13 J1 MAINS C A3A10 J4 49 52 RACK
C
W62 MAINS A1A7 J1 PLF B A2A13 J5 49 52 CON
W68 MAINS A1A7 J2 PDP A A1A12 * 49 52 CON
* part of unit
T̲a̲b̲l̲e̲ ̲5̲.̲8̲.̲3̲
R̲A̲C̲K̲ ̲B̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W44 CHAN A2A1 J1 PDP C A3A15 J3 49 52 DISCON
W45 CHAN A2A1 J2 PDP A A1A12 J3 49 52 DISCON
W46 D-FAN A2A2 J1 PDP C A3A15 J4 49 52 DISCON
W47 D-FAN A2A2 J2 PDP A A1A12 J4 49 52 DISCON
W52 MAINS A2A9 J2 WD B A2A4 J1 49 52 DISCON/I
W54 DISK A2A7 J1 PDP B A2A12 J2 49 52 DISCON/I
W56 FD A2A6 J1 PDP B A2A12 J1 49 52 CON/I
W60 MAINS A2A9 J4 PLF A A1A13 J3 49 52 DISCON
W62 PLF A2A13 J5 MAINS A A1A7 J1 49 52 RACK
A
W63 MAINS A2A9 J1 PLF B A2A13 J3 49 52 DISCON/I
W64 PLF A2A13 J1 MAINS C A3A10 J1 49 52 RACK
C
W67 MAINS A2A9 J3 PDP B A2A12 * 49 52 DISCON
* part of unit
T̲a̲b̲l̲e̲ ̲5̲.̲8̲.̲4̲
R̲A̲C̲K̲ ̲C̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W44 PDP A3A15 J3 CHAN B A2A1 J1 49 52 RACK
B
W46 PDP A3A15 J4 D-FAN B A2A2 J1 49 52 RACK
B
W48 PROC A3A1 J1 PDP C A3A15 J1 49 52 DISCON/I
W49 PROC A3A1 J2 PDP C A3A15 J7 49 52 DISCON/I
W50 D-FAN A3A2 J1 PDP C A3A15 J2 49 52 DISCON/I
W51 D-FAN A3A2 J2 PDP C A3A15 J6 49 52 DISCON/I
W55 DISK A3A8 J1 MAINS C A3A10 J3 49 52 DISCON/I
W57 ADAP-P A3A5A22 J1 PDP C A3A17 J2 49 52 I
W58 ADAP-P A3A5A23 J1 PDP A A1A12 J5 49 52 DISCON
W61 MAINS A3A10 J4 PLF A A1A13 J1 49 52 DISCON
W64 MAINS A3A10 J1 PLF B A2A13 J1 49 52 DISCON
W65 PDP A3A15 J5 PDP C A3A17 * 49 52 CON
W66 MAINS A3A10 J2 PDP C A3A15 * 49 52 DISCON
W69 PDP A3A17 J1 S-FAN C A3A7 * 49 52 CON
* part of unit
T̲a̲b̲l̲e̲ ̲5̲.̲8̲.̲5̲
R̲A̲C̲K̲ ̲D̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W301 ASSY 4 A1A1 J15 PDP D A1A19 J3 49 125 CON/I
W302 ADAP-P A1A1A20 J1 PDP D A1A19 J4 49 125 CON/I
W303 ASSY 3 A1A3 J15 PDP D A1A19 J1 49 125 CON/I
W304 ADAP-P A1A3A20 J1 PDP D A1A19 J2 49 125 CON/I
W305 ASSY 2 A1A7 J15 PDP D A1A27 J3 49 125 CON/I
W306 ADAP-P A1A7A20 J1 PDP D A1A27 J4 49 125 CON/I
W307 ASSY 1 A1A9 J15 PDP D A1A27 J1 49 125 CON/I
W308 ADAP-P A1A9A20 J1 PDP D A1A27 J2 49 125 CON/I
W331 MAINS A1A12 J4 PLF E A2A26 J2 49 125 CON
W332 MAINS A1A12 J1 PLF E A2A26 J4 49 125 CON
W351 PDP A1A19 J5 S-FAN D A1A5 * 49 125 CON
W352 MAINS A1A12 J2 PDP D A1A19 * 49 125 CON
W353 PDP A1A27 J5 S-FAN D A1A14 * 49 125 CON
W354 MAINS A1A12 J3 PDP D A1A27 * 49 125 CON
* part of unit
T̲a̲b̲l̲e̲ ̲5̲.̲8̲.̲6̲
R̲A̲C̲K̲ ̲E̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W313 ASSY 6 A2A7 J15 PDP E A2A24 J3 49 125 CONN/I
W314 ADAP-P A2A7A20 J1 PDP E A2A24 J4 49 125 CONN/I
W315 ASSY 5 A2A9 J15 PDP E A2A24 J1 49 125 CONN/I
W316 ADAP-P A2A9A20 J1 PDP E A2A24 J2 49 125 CONN/I
W331 PLF A2A26 J2 MAINS D A1A12 J4 49 125 RACK
D
W332 PLF A2A26 J4 MAINS D A1A12 J1 49 125 RACK
D
W333 MAINS A2A12 J4 PLF E A2A26 J6 49 125 DISCON/I
W334 MAINS A2A12 J1 PLF E A2A26 J1 49 125 DISCON/I
W336 PLF A2A26 J5 MAINS G A4A12 J4 49 125 RACK
G
W356 MAINS A2A12 J2 PDP E A2A18 * 49 125 DISCON
W357 PDP A2A24 J5 S-FAN E A2A11 * 49 125 CONN
W358 MAINS A2A12 J3 PDP E A2A24 * 49 125 DISCON
* part of unit
T̲a̲b̲l̲e̲ ̲5̲.̲8̲.̲7̲
R̲A̲C̲K̲ ̲G̲
G̲O̲I̲N̲G̲ ̲T̲O̲/̲C̲O̲M̲M̲I̲N̲G̲ ̲F̲R̲O̲M̲
Cable
̲N̲o̲ ̲ ̲ M̲o̲d̲u̲l̲e̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ M̲o̲d̲u̲l̲e̲ R̲a̲c̲k̲ L̲o̲c̲a̲t̲i̲o̲n̲ J̲-̲N̲o̲ I̲l̲l̲u̲s̲
D̲i̲a̲g̲ N̲o̲t̲e̲s̲ ̲ ̲
W321 ASSY11 A4A7 J15 PDP G A5A16 J3
CON/I
W322 ADAP-P A4A7A20 J1 PDP G A5A16 J4 CON/I
W323 ADAP-P A4A9A23 J1 PDP G A5A16 J2 CON/I
W336 MAINS A4A12 J4 PLF E A2A26 J5 DISCON
W363 MUX A4A3 * PDP G A5A16 J6 CON/I
W364 PDP A5A16 J5 S-FAN G A4A11 * CON
W365 MAINS A4A12 J3 PDP G A5A16 * DISCON
* part of unit
5.9 P̲O̲W̲E̲R̲ ̲U̲P̲ ̲A̲N̲D̲ ̲C̲H̲E̲C̲K̲ ̲O̲U̲T̲
Before powering up, verify that a̲l̲l̲ ̲s̲w̲i̲t̲c̲h̲e̲s̲ on a̲l̲l̲
e̲q̲u̲i̲p̲m̲e̲n̲t̲ are i̲n̲ ̲p̲o̲s̲i̲t̲i̲o̲n̲ ̲o̲f̲f̲ or O.
5.9.1 G̲r̲o̲u̲n̲d̲i̲n̲g̲s̲
a) Measure with an Ohm-meter that no short circuit
exists between the safety group (cabinets) and
the lines of circuit no. 1 through 9 and 1a through
3a.
b) Remount the lids of the power line filters by the
30 screws.
c) Start the powering up in the below sequence, starting
at the CAMPS power distribution board (PDB):
5.9.2 C̲A̲M̲P̲S̲ ̲P̲D̲B̲
T̲U̲R̲N̲ ̲O̲N̲: Main circuit breaker
T̲U̲R̲N̲ ̲O̲N̲: Miniature circuit breakers
C̲H̲E̲C̲K̲O̲U̲T̲: No fuses in the CAMPS PDB blown due to
short circuit in the installation.
5.9.3 D̲i̲s̲k̲ ̲D̲r̲i̲v̲e̲s̲
To examine that the 3 disk drives are supplied from
3 separate phases proceed in the below sequence:
a) D̲i̲s̲k̲ ̲#̲1̲ ̲(̲M̲M̲D̲)̲ ̲R̲A̲C̲K̲ ̲A̲
1) T̲U̲R̲N̲ ̲O̲N̲: Power switch 1 (left hand) on the
front of the mains switch located
in the bottom of rack A.
2) C̲H̲E̲C̲K̲: "Power on" lamp lit on mains switch.
3) T̲U̲R̲N̲ ̲O̲N̲:̲ Rear power switch disk drive No.
1 located in rack A.
4) C̲H̲E̲C̲K̲: Disk running and "ready" lamp in
front of disk lit (wait for
30 sec.).
5) T̲U̲R̲N̲ OFF: Miniature circuit breaker (CAMPS
PDB) corresponding to power circuit
no. 1 for disk 1 (see ATBB drawing
120).
6) C̲H̲E̲C̲K̲: Disk 1 powered down.
7) Leave the miniature circuit breaker in position
OFF.
b) D̲i̲s̲k̲ ̲#̲2̲ ̲(̲S̲M̲D̲)̲
Repeat step 5.9.3a-1 through a-2 for disk drive
#2 (rack B).
3) T̲U̲R̲N̲ ̲O̲N̲:̲ Rear switches "AC power" and "power
supply".
4) C̲H̲E̲C̲K̲:̲ Disk running. (No ready lamp if
no disc pack mounted).
Proceed by repeating step 5.9.3a-5 thru a-7 for
circuit no. 2.
c) D̲i̲s̲k̲ ̲#̲3̲ ̲(̲M̲M̲D̲)̲
Repeat step 5.9.3 a-1 through a-7 for disk drive
#3 (rack C).
d) Turn on the 3 miniature circuit breakers in the
CAMPS PDB one by one.
e) Check that all disks are operating.
f) T̲U̲R̲N̲ ̲O̲F̲F̲: Miniature circuit breaker in CAMPS
PDB for circuit no. 1, 2 and 3.
5.9.4 M̲a̲i̲n̲s̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲a̲c̲k̲ ̲A̲ ̲S̲w̲i̲t̲c̲h̲ ̲2̲ ̲C̲i̲r̲c̲u̲i̲t̲ ̲N̲o̲.̲ ̲4̲
1) T̲U̲R̲N̲ ̲O̲N̲: Power switch No. 2 (right hand) on
front of the mains switch in rack A.
2) C̲H̲E̲C̲K̲: "Power on" lamps lit.
3) T̲U̲R̲N̲ ̲O̲N̲:̲ Supply A (right hand) and supply B
(left hand) on the rear of the M-fan
located in rack A (A1A2).
4) C̲H̲E̲C̲K̲:̲ Fan running/green lamp in front lit.
5) T̲U̲R̲N̲ ̲O̲N̲:̲ Power supply A (right hand) and power
supply B (left hand) on the rear of
the processor crate in rack A (A1A1).
6) C̲H̲E̲C̲K̲:̲ Green "power on" lamp above switches
lit.
7) T̲U̲R̲N̲ ̲O̲N̲:̲ Power supply A (left hand) and power
supply B (right hand) from the front
of the processor crate.
8) C̲H̲E̲C̲K̲:̲ All 5 power indicator lamps lit on
front of the power supplies.
(All 10 lamps lit when A o̲r̲ B in
poss. on).
9) T̲U̲R̲N̲ ̲O̲N̲:̲ Supply A (right hand) on the rear of
the M-fan located in rack B.
10) C̲H̲E̲C̲K̲:̲ Fan running/corresponding green lamp
in front lit.
11) T̲U̲R̲N̲ ̲O̲N̲:̲ Power supply A (right hand) on the
rear of the channel unit crate in rack
B (A2A1).
12) C̲H̲E̲C̲K̲:̲ Green "power on" lamp above switch
lit.
13) T̲U̲R̲N̲ ̲O̲N̲:̲ Power supply A (left hand) from the
front of the CU.
14) C̲H̲E̲C̲K̲:̲ All 5 power indicator lamps lit on
front of the power supply.
15) T̲U̲R̲N̲ ̲O̲N̲:̲ Power switch on adapter power supply,
right hand part on the rear of the
adapter crate in rack C (A3A5A23).
16) C̲H̲E̲C̲K̲:̲ "Power on" lamps lit on left hand section
of the adapter crate (2 L/L adapters
and 2 Opto T/R)
17) T̲U̲R̲N̲ ̲O̲F̲F̲:̲ Miniature circuit breaker in CAMPS
PDB corresponding to power circuit
for mains switch in rack A. Leave the
circuit breaker in position OFF.
5.9.5 M̲a̲i̲n̲s̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲a̲c̲k̲ ̲B̲ ̲S̲w̲i̲t̲c̲h̲ ̲2̲ ̲C̲i̲r̲c̲u̲i̲t̲ ̲N̲o̲.̲ ̲5̲
1) T̲U̲R̲N̲ ̲O̲N̲: Right hand power switch on front of
the mains switch in rack B.
2) C̲H̲E̲C̲K̲: Green "power on" lamp above switch
lit.
3) T̲U̲R̲N̲ ̲O̲N̲: Switch on power supply located on the
rear of the watchdog crate (A2A4).
4) C̲H̲E̲C̲K̲:̲ Green "Power on" lamp above switch
lit.
Fans running (build-in fans right hand
side of the crate).
5) T̲U̲R̲N̲ ̲O̲F̲F̲:̲ Miniature circuit breaker in CAMPS
PDB corresponding to power circuit
for switch 1 in mains switch rack B.
Leave the miniature circuit breaker
in position OFF.
5.9.6 M̲a̲i̲n̲s̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲a̲c̲k̲ ̲B̲ ̲S̲w̲i̲t̲c̲h̲ ̲1̲ ̲C̲i̲r̲c̲u̲i̲t̲ ̲N̲o̲.̲ ̲2̲
Left hand power switch on front of the mains switch
in rack B is in position ON. Turn on the mini circuit
breaker in CAMPS PDB for circuit No. 2.
1) T̲U̲R̲N̲ ̲O̲N̲:̲ Main switch on the rear side of floppy
disk station.
2) C̲H̲E̲C̲K̲:̲ "Power on" lamp lit and blower inside
both floppy disk drives running.
(Power on lamp lit behind the PDP).
3) T̲U̲R̲N̲ ̲O̲F̲F̲:̲ CAMPS PDB mini circuit breaker circuit
No. 2.
5.9.7 M̲a̲i̲n̲s̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲a̲c̲k̲ ̲C̲ ̲S̲w̲i̲t̲c̲h̲ ̲2̲ ̲C̲i̲r̲c̲u̲i̲t̲ ̲N̲o̲.̲ ̲6̲
S-FAN will be in poss. on and starts running.
Repeat step 5.9.4 item 1 thru 8 for the mains switch
and equipment in rack C (right hand switch).
9) T̲U̲R̲N̲ ̲O̲N̲:̲ Supply B (left hand) on the rear of
the M-fan in rack B.
10) C̲H̲E̲C̲K̲:̲ Fan running/green lamp in front of
fan lit.
11) T̲U̲R̲N̲ ̲O̲N̲:̲ Power supply B (left hand) on the rear
of the channel unit crate in rack B.
12) C̲H̲E̲C̲K̲:̲ Green "power on" lamp above switch
lit.
13) T̲U̲R̲N̲ ̲O̲N̲:̲ Power supply B (right hand) from the
front of the CU.
14) C̲H̲E̲C̲K̲:̲ All 5 power indicator lamps lit on
front of the power supply.
15) T̲U̲R̲N̲ ̲O̲N̲:̲ Power switch on adapter power supply,
left hand part on the rear of the adapter
crate in rack C (A3A5A22).
16) C̲H̲E̲C̲K̲:̲ "Power on" lamps lit on right hand
section of the adapter crate (2 L/L
adapters)
17) T̲U̲R̲N̲ ̲O̲F̲F̲:̲ Miniature circuit breaker in CAMPS
PDB corresponding to power circuit
for switch 2 in mains switch rack C.
5.9.8 M̲a̲i̲n̲s̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲a̲c̲k̲ ̲D̲ ̲S̲w̲i̲t̲c̲h̲ ̲1̲ ̲C̲i̲r̲c̲u̲i̲t̲ ̲N̲o̲.̲ ̲7̲
1) T̲U̲R̲N̲ ̲O̲N̲:̲ Power switch No. 1 (left hand) on front
of the mains switch in rack D.
2) C̲H̲E̲C̲K̲:̲ Green "power on" lamp above switch
lit.
3) T̲U̲R̲N̲ ̲O̲N̲:̲ Power switch on the rear main power
panel of TDX crate assy #1 (2A1A9).
Power switch on the front of the main
power supply TDX crate assy #1.
4) C̲H̲E̲C̲K̲:̲ +/-12V and 5V lamps on main power supply
lit.
5) T̲U̲R̲N̲ ̲O̲N̲:̲ Power switch on the rear adapter power
supply TDX crate assy #1.
6) C̲H̲E̲C̲K̲:̲ Green power lamps on all adapter modules
in TDX crate assy #1 lit.
7) T̲U̲R̲N̲ ̲O̲N̲:̲ Rear power switch on S-fan located
below TDX crate assy #1.
8) C̲H̲E̲C̲K̲:̲ Fan running
9) Repeat step 5.9.8 item 3 thru 6 for TDX crate assy
#2 (2A1A7).
5.9.9 M̲a̲i̲n̲s̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲a̲c̲k̲ ̲E̲ ̲S̲w̲i̲t̲c̲h̲ ̲2̲ ̲C̲i̲r̲c̲u̲i̲t̲ ̲N̲o̲.̲ ̲7̲
1) T̲U̲R̲N̲ ̲O̲N̲:̲ Power switch No. 2 (right hand) on
front of the mains switch in rack E.
2) T̲U̲R̲N̲ ̲O̲F̲F̲:̲ Miniature circuit breaker in CAMPS
PDB corresponding to power circuit
for PLF line 7.
5.9.10 M̲a̲i̲n̲s̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲a̲c̲k̲ ̲E̲ ̲S̲w̲i̲t̲c̲h̲ ̲1̲ ̲C̲i̲r̲c̲u̲i̲t̲ ̲N̲o̲.̲ ̲9̲
1) T̲U̲R̲N̲ ̲O̲N̲:̲ Power switch No. 1 (right hand) on
front of the mains switch in rack E.
2) Repeat step 5.9.8 item 3 through 8 for TDX crate
assy #5 (2A2A9) and the S-fan (2A2A11).
3) Repear step 5.9.8 item 3 through 6 for TDX crate
assy #6 (2A2A7).
4.9.11 M̲a̲i̲n̲s̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲a̲c̲k̲ ̲G̲ ̲S̲w̲i̲t̲c̲h̲ ̲1̲ ̲C̲i̲r̲c̲u̲i̲t̲ ̲N̲o̲.̲ ̲9̲
1) T̲U̲R̲N̲ ̲O̲N̲:̲ Power switch No. 1 (left hand) on front
of the mains switch in rack G.
2) Repeat step 5.9.8 item 3 through 8 for TDX crate
assy #11 (2A4A7) and the S-fan (2A4A11).
3) T̲U̲R̲N̲ ̲O̲N̲:̲ Power switch on adapter power supply
on rear of the adapter crate.
4) T̲U̲R̲N̲ ̲O̲N̲:̲ Remove the front panel of the stat.
mux. (2A4A3).
Turn on the power switch located on
the front of the mux. left-hand side.
5) C̲H̲E̲C̲K̲:̲ Fan in mux. running.
Lamp "AT" on indicator panel lit.
6) T̲U̲R̲N̲ ̲O̲F̲F̲:̲ Miniature circuit breaker in CAMPS
PDB corresponding to power circuit
for PLF line 9.
5.9.12 M̲a̲i̲n̲s̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲a̲c̲k̲ ̲D̲ ̲S̲w̲i̲t̲c̲h̲ ̲2̲ ̲C̲i̲r̲c̲u̲i̲t̲ ̲N̲o̲.̲ ̲8̲
1) T̲U̲R̲N̲ ̲O̲N̲:̲ Power Switch No. 2 (right hand) on
the front of the mains switch in rack
D.
2) Repeat step 5.9.8 item 3 through 8 for TDX crate
assy #3 (2A1A3) and the S-fan (2A1A5).
3) Repeat step 5.9.8 item 3 through 6 for TDX crate
assy #4 (2A1A1).
5.9.13 T̲U̲R̲N̲ ̲O̲N̲:̲ All the miniature circuit breakers in the
CAMPS PDB switched off in step 5.9.4, 5.9.5,
5.9.7, 5.9.9, and 5.9.11.
5.9.14 V̲e̲r̲i̲f̲y̲ ̲S̲u̲p̲p̲l̲y̲ ̲V̲o̲l̲t̲a̲g̲e̲ ̲o̲n̲ ̲P̲U̲ ̲C̲r̲a̲t̲e̲s̲
All voltages used in the processor units are verified
by a digital multimeter.
The measurement is carried out on the front panel of
the crate configuration adapter (CCA) located on the
rear side of the PU crates (1A1A23 and 1A3A23). The
voltages are checked to be within below limits:
5V = 5.1 - 5.3V
+12V = 12.1 - 12.3V
-12V = 12.1 - 12.3V
+24V = 22.8 - 25.2V
-24V = 22.8 - 25.2V
5.9.15 V̲e̲r̲i̲f̲y̲ ̲S̲u̲p̲p̲l̲y̲ ̲V̲o̲l̲t̲a̲g̲e̲ ̲o̲n̲ ̲C̲U̲ ̲C̲r̲a̲t̲e̲
All voltages used in the channel unit are verified
by a digital multimeter. The measurements are carried
out on the front panel of the CCA located on the rear
side of the CU crate (1A2A1A25). The voltages are checked
to be within below limits:
+24V = 22.8 - 25.2V
+12V = 12.6 - 12.8V
+5V = 5.68 - 5.72V
-12V = 12.6 - 12.8V
-24V = 22.8 - 25.2V
5.10 I̲N̲S̲P̲E̲C̲T̲I̲O̲N̲ ̲O̲F̲ ̲S̲W̲I̲T̲C̲H̲ ̲S̲E̲T̲T̲I̲N̲G̲S̲ ̲A̲N̲D̲ ̲S̲T̲A̲T̲U̲S̲ ̲L̲E̲D̲S̲
In order to receive a preliminary impression on the
condition of the system after powering up use the below
tables for a visual check of the status leds.
If any discrepancies, refer to the CAMPS Site Level
Maintenance Manual, Doc. No. 2.
5.10.1 S̲w̲i̲t̲c̲h̲ ̲S̲e̲t̲t̲i̲n̲g̲s̲
Before checking the status leds, all switches must
be placed in correct positions:
U̲N̲I̲T̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲S̲W̲I̲T̲C̲H̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲N̲O̲R̲M̲A̲L̲ ̲P̲O̲S̲S̲
MAP S2 MAIN/NRM NRM
S3 DIS/EN EN
CUCP CU BUS A AUTO
CU BUS B -
DISK CTRL 1 -
DISK CTRL 2 -
DISK CTRL 3 -
LTU 1-5 -
ST.FD. CTLR -
CCBA S1 EN/DIS EN
BSM-X S1 BUS BUS 2
S2 AUTO/MAN/OFF MAN
LTUX-S CH1-CH4 ON
CCA RESET DOWN
After power up press MC on PROC 1 and 2.
5.10.2 L̲e̲d̲ ̲I̲n̲d̲i̲c̲a̲t̲o̲r̲s̲
The following table list the normal condition of the
equipment led indicators.
UNIT LED NORM. COND. NOTE
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
M̲A̲P̲ POWER ON
TEST OFF ON
FOR
APP.
10
SEC.
AFTER
POWER
UP
P. FAIL OFF
NO CPU OFF BLINKING
A
FEW
SEC.
AFTER
TEST
OFF
CB DMA OFF
DC DMA OFF
PUDIS OFF ON
=
SWITCH
S3
IN
POSS.
DIS.
INH OFF ON = SWITCH S2
IS OR HAS BEEN
IN POSS.
MAINT.
HALT OFF ON
=
SWITCH
S2
IN
POSS.
MAINT.
MAINT OFF ON
=
SWITCH
S2
IN
POSS.
MAINT.
C̲P̲U̲/̲C̲A̲C̲H̲E̲ POWER ON
CACHE OFF ON
TEST OFF ON
FOR
APP.
1
SEC.
AFTER
POWER
UP
R̲A̲M̲ POWER ON
S̲T̲I̲ POWER ON
TEST OFF ON
FOR
APP.
10
SEC.
AFTER
POWER
UP
BUSY OFF
HIDMA OFF
P.ERR OFF
C.ERR OFF
M.ERR OFF
RX STAT OFF
M̲I̲A̲ POWER ON
ENABLE ON OFF = SWITCH S3
ON MAP IN POSS.
DIS.
T̲I̲A̲ POWER ON
TEST ON (ON FOR A FEW
SEC. AFTER POWER
UP)
UNIT LED NORM. COND. NOTE
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
C̲C̲A̲ POWER ON
BUSY OFF
M̲B̲T̲ POWER ON
D̲I̲S̲K̲ ̲C̲T̲R̲L̲ POWER ON
TEST OFF ON
FOR
APP.
10
SEC.
AFTER
POWER
UP
ABUS OFF
BBUS OFF
BUSY OFF
S̲T̲.̲F̲D̲.̲C̲T̲R̲L̲ POWER ON
TEST ON
ABUS OFF
BBUS OFF
BUSY ON
FRONT LED OFF
C̲U̲C̲P̲ POWER ON
AUTO CTRL ON OFF: ONE OF THE
SWITCHES N̲O̲T̲
IN AUTO
DIS (A OR B) OFF ON: SWITCH IN
POSS. DIS.
AUTO ON OFF:
SWITCH
IN
POSS.
DIS.
BUS A OFF
BUS B OFF
L̲T̲U̲ POWER ON
TEST OFF ON
FOR
APP.
10
SEC.
AFTER
POWER
UP
BUS A OFF
BUS B OFF
BOOTL. OFF…86…1 …02…
…02… …02… …02…
UNIT LED NORM. COND. NOTE
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
C̲I̲A̲-̲A̲/̲B̲ POWER ON
P.FAIL OFF
W̲C̲A̲ POWER ON
ENABLE ON OFF:
SWITCH
S1
IN
POSS.
DIS
D̲C̲A̲ POWER ON
B̲S̲M̲-̲X̲ POWER ON
EXT.POWER ON
BUS 1 ON/OFF ONLY
BUS
1
O̲R̲
BUS
2
ACTIVE
BUS 2 OFF/ON
AUTO OFF OFF:
S2
IN
POSS.
MAN.
OR
OFF
MAN ON ON: S2 IN POSS.
MAN. OR OFF
T̲D̲X̲.̲C̲O̲N̲T̲ POWER ON
TEST OFF ON
FOR
APP.
10
SEC.
AFTER
POWER
UP
REC.ST. OFF
TR.ST. OFF
FUSE OFF
O̲P̲T̲O̲ ̲T̲/̲R̲ POWER ON
RCVL ON RED
LIGHT
(NO
TERM.
CONN)
RTS ON
CTS OFF
SYNC ON RED
LIGHT
(NO
TERM.
CONN)
L̲/̲L̲ ̲A̲D̲A̲P̲ POWER ON
L̲T̲U̲X̲-̲S̲ POWER ON
TEST OFF ON
FOR
APP.
10
SEC.
AFTER
POWER
UP
TDX.ST OFF
CH 1-4 ON OFF:
SWITCH
1-4
OFF
UNIT LED NORM. COND. NOTE
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
…02…M̲M̲D̲ START/READY ON
FAULT/CLEAR OFF
WRITE PROT. OFF ON:
SWITCH
ACTIVATED
S̲M̲D̲ START OFF
READY ON
FAULT OFF
WRITE PROT. OFF ON:
SWITCH
ACTIVATED
W̲D̲ ̲C̲R̲A̲T̲E̲ POWER ON TERMINATOR
BOARD
INSIDE
CRATE
5.11 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲D̲E̲L̲T̲A̲ ̲V̲D̲U̲
a) The terminals are distributed to the installation
sites according to ATBB drawings 102, 105, and
110.
b) Supervisory and maintenance terminals must be placed
on CR provided tables.
c) For two of the SUP. POSS. in the CAMPS area, a
table mounted PDP must be installed.
5.11.1 P̲o̲w̲e̲r̲ ̲P̲l̲u̲g̲ ̲C̲o̲n̲n̲e̲c̲t̲i̲o̲n̲s̲
Power plug connections must be exchanged to fit host
nation provided power outlets.
P̲O̲W̲E̲R̲ ̲C̲O̲R̲D̲ ̲F̲R̲O̲M̲ ̲D̲E̲L̲T̲A̲ 3̲-̲P̲I̲N̲N̲E̲D̲ ̲P̲L̲U̲G̲
Brown Phase
Blue Neutral
Green/Yellow Ground
5.11.2 T̲e̲r̲m̲i̲n̲a̲t̲i̲o̲n̲ ̲o̲f̲ ̲O̲p̲t̲o̲ ̲C̲a̲b̲l̲e̲s̲
a) Before terminating the opto cable, a rubber tubing,
size 8 x 12 x 250 mm, must be mounted on the cable,
see ATBB dwg. 130.
b) The opto fibres are to be pulled through the rear
waveguide (port 3) into the VDU.
(See ATBB dwg. 130).
c) The two fibres must be terminated with special
opto connectors.
For detailed termination procedures see ref. 4
doc.
d) In case of opto splicing this will be done by mounting
of an adapter between the two male connectors,
using the same kind of male connectors as for the
terminals.
e) Before connecting the two fibres to the optical
modem board in the VDU, the black receiver cable
with the opto connector must be checked for supplying
enough light emission.
The transmitter of the opto T/R in the TDX crate
is used as source for the opto fibre (black cable
connected).
f) In case the light emission exceeds - 34.6 dBm,
the cable will be terminated with a new pair of
OPTO connectors. If still outside tolerance the
cable will be marked as Bad and a new cable must
be installed.
g) Connect the black fibre in the VDU end to the 11XE
fiber optic power meter and verify that the optical
power output does not exceed -34.6dBm.
h) To get access to the optical modem board located
inside the VDU, unlock the two snappers on the
rear and lift the terminal access cover of the
VDU.
i) The white fibre must be connected to the transmitter
jack ("out") and the black fibre to the receiver
jack ("in") (see ATBB drawing 130).
j) The opto cable must be permanently marked with
cable No during the termination procedure.
5.11.3 M̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲K̲e̲y̲b̲o̲a̲r̲d̲ ̲a̲n̲d̲ ̲K̲e̲y̲s̲
a) The keyboard cable is connected to the female cannon
plug located on the lower right hand front of the
terminal. The connector is secured by the two front
screws.
b) Remove the two keys placed on the inside of the
terminal access cover and insert the keys in the
key-lock on front of the terminal.
5.12 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲T̲R̲A̲C̲O̲R̲ ̲M̲S̲P̲
5.12.1 P̲o̲w̲e̲r̲ ̲P̲l̲u̲g̲ ̲C̲o̲n̲n̲e̲c̲t̲i̲o̲n̲s̲
Repeat step 5.11.1 for the power plug of the MSP.
5.12.2 T̲e̲r̲m̲i̲n̲a̲t̲i̲o̲n̲ ̲o̲f̲ ̲O̲p̲t̲o̲ ̲C̲a̲b̲l̲e̲s̲
Repeat step 4.11.2 item a) thru e).
f) To get access to the optical modem board located
inside the printer, unlock the two snappers in
front of the printer and lift the cover of the
printer.
g) Install the fibres through the rear connector entry
hole, route through the optical cable entry hole
and connect the white fibre to the transmitter
("output") and the black fibre to the receiver
("input"). (See ATBB dwg. 130).
h) The opto cable must be permanently marked with
cable number during the termination procedure.
i) Install the paper and the ribbon according to the
instructions in the operator's manual.
j) Remount the Piston spring between the lid and the
bottom, by rotating it clockwise into the screw
thread in the bottom of the printer. The Piston
is connected to the lid by the two Philips screws
and the hinge mounted in the lid.
k) Remove the two keys placed on the outside of the
lid and insert the keys in the key-lock on front
of the terminal.
5.13 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲P̲T̲P̲/̲P̲T̲R̲
a) The PTP/PTR is installed in the off-line encryption
area (ref ATBB drawing 105).
b) The 3/4" 45…0e…o…0f… fitting is mounted in the J-box and
fastened from inside the J-box by the nut.
c) The metallic conduit is mounted to the fitting
by means of the hose lock and the lock nut.
d) Repeat step b) and c) for mounting of the conduit
to the PTP/PTR (see ATBB drawing 131).
e) The metallic interface cable coming from the filter
box is pulled through the conduit into the PTP/PTR.
The cable will be terminated by a cannon plug according
to the pin assignment table 5.3.2 page 5.5 in the
ATBB Doc.
f) The cable is connected according to ATBB drawing
131.
5.14 T̲E̲S̲T̲ ̲O̲F̲ ̲S̲U̲P̲/̲U̲S̲E̲R̲ ̲T̲E̲R̲M̲I̲N̲A̲L̲S̲
5.14.1 T̲e̲s̲t̲ ̲o̲f̲ ̲D̲e̲l̲t̲a̲ ̲V̲D̲U̲
a) Connect the power plug to the wall outlet.
b) Turn on the "power on/off" switch located on the
lower right front of the terminal.
c) Operate the keylock switch to the ON position (right
hand front panel).
d) Immediately after power up the terminal executes
a series of system diagnostics. If all are working
properly, the power-up menu will be displayed on
the screen within 10 seconds.
e) Adjust the intensity and focus until the characters
are clear and bright. Do not advance the intensity
too far or the display area may be highlighted.
f) Adjust the audible alarm for the desired sound
level (control shift and the G key).
g) When all the terminals have been switched on and
locally tested, the transmitter of the optical
modem board in the VDU, the white opto cable, and
the opto connection to the TDX crate must be checked
for supplying enough light emission.
h) Connect one by one all the white fibres terminated
in the opto T/R located in the TDX crates to the
11XE fibre optic power meter and check that the
optical power outlet does not exceed -34.6dBm.
5.14.2 O̲p̲e̲r̲a̲t̲i̲o̲n̲a̲l̲ ̲T̲e̲s̲t̲
a) Assure that the required terminal functions and
characteristics are correctly stored by checking
the contents of the configuration menu.
Correct CAMPS Application contents to be:
DEL/BS - N̲ PRT CR DLY -
0̲
ECHO - N̲ PRT LF AFT CR -
N̲
CR-XOFF - N̲ PRT PROT DATA -
N̲
XMT SO SEQ - N̲ PRT BSY -
N̲
MEM RELEASED - Y̲ PRT BUSY-HIGH -
N̲
LEFT MARGIN - 0̲0̲ PRT FF -
N̲
BAUDOT - N PRT BUF (0,1,2,3) -
0̲
VRU?X̲7̲2̲6̲0̲ WHATRU? CAMPS CLK 0̲0̲0̲0̲0̲0̲
I/O HOST PTR
CHAR 7̲ 7̲
PARITY E̲ E̲
STOP BITS C̲ C̲
BAUD RATE G̲ G̲
b) The terminal is logged on to the system
according to procedures stated in the
Operator's Manual.
c) Messages are sent/rec. between the terminal
and other terminals.
5.14.3 T̲e̲s̲t̲ ̲o̲f̲ ̲T̲r̲a̲c̲o̲r̲ ̲M̲S̲P̲
a) Connect the power plug to the wall outlet.
b) Turn on the power switch located on
the rear right hand side.
Verify that the power lamp on the front
panel lights.
c) Operate the key-lock switch to the ON
position (left hand side in front).
d) Depress the "line feed" button on the
TCM front panel and verify that line
feed of paper occurs.
e) Press the test button for not more than
4 sec. Verify that all lamps on the
printer lights.
f) Press the test button for at least 5
sec. Verify that the following is printed:
NO ERRORS IN ROM
NO ERRORS IN RAM
66 LINES BARBERPOLE PATTERN
g) Repeat step 5.15.1 item h) and j) for
test of transmitter and opto connections.
5.14.4 O̲p̲e̲r̲a̲t̲i̲o̲n̲a̲l̲ ̲T̲e̲s̲t̲
Arrange to have one or more messages sent to the MSP
and verify message contents with the transmitting station.
Verify during print out that the key-lock switch stops
the printing and that no part of the message is lost
when it is turned on again.
5.15 T̲E̲S̲T̲ ̲O̲F̲ ̲P̲T̲P̲/̲P̲T̲R̲
Testing the PTP/PTR is a part of the PROCESSOR/LINE
TERMINATION TEST. Ref. 5.16.
5.16 H̲/̲W̲ ̲T̲E̲S̲T̲ ̲P̲R̲O̲C̲E̲S̲S̲O̲R̲/̲L̲I̲N̲E̲ ̲T̲E̲R̲M̲.̲ ̲U̲N̲I̲T̲S̲
By means of the M&D- and the Test Drive Software, all
hardware- and interface functions shall be verified.
The following step by step procedure outlines the major
tasks of the testing sequence.
For a detailed description of the test procedure including
informations of test control, test data, expected test
results, test execution procedures, see CPS/TRP/001
FACTORY ACCEPTANCE TEST SPECIFICATIONS AND PROCEDURES.
5.16.1 P̲U̲ ̲#̲1̲/̲C̲U̲/̲T̲D̲X̲ ̲#̲2̲ ̲F̲u̲n̲c̲t̲i̲o̲n̲a̲l̲ ̲T̲e̲s̲t̲
a) CPU Test
b) MAP Test
c) RAM Test
d) Disk/FD/LTU/TDX
5.16.2 W̲a̲t̲c̲h̲d̲o̲g̲ ̲P̲r̲o̲c̲e̲s̲s̲o̲r̲ ̲F̲u̲n̲c̲t̲i̲o̲n̲a̲l̲ ̲T̲e̲s̲t̲
a) WDP Test
b) WDP V24 Interface Test
c) WDP CCBA Interface Test
d) PU #1 CCA Test
e9 PU #2 CCA Test
f) CU CCA Test
g) TU1-10 BSM-X Test
5.17 I̲N̲V̲E̲N̲T̲O̲R̲Y̲ ̲C̲H̲E̲C̲K̲
a) As a final step of the installation procedure,
the CR instalation team will conduct an inventory
check of all delivered CAMPS equipment to verify
that the equipment is complete.
b) This inventory inspection will be witnessed by
the customer.
c) The inventory is performed in accordance with the
updated inventory list prepared by CR.
d) The inventory check will also include delivery
to site of spare parts, test equipment, and documentation.
e) The results are recorded on the inventory list
and signed by both parties.
6 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲R̲E̲M̲O̲T̲E̲ ̲T̲E̲R̲M̲I̲N̲A̲L̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲ ̲S̲I̲T̲E̲ ̲0̲2̲A̲
6.1 S̲H̲I̲P̲M̲E̲N̲T̲ ̲O̲F̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲
6.1.1 D̲i̲s̲a̲s̲s̲e̲m̲b̲l̲y̲ ̲a̲n̲d̲ ̲P̲a̲c̲k̲i̲n̲g̲
The remote terminal equipment, which will be part of
the main site shipment, is shipped to the remote terminal
site 02A as follows:
- Stat. mux. rack is packed in a wooden container.
- Terminal equipment (2 VDUs and 2 MSPs) are shipped
in their own containers.
- Auxiliary equipment (power line filter, modules,
stat. mux., and cables) are shipped in their own
contaners.
Above packing scheme will result in the shipment composition
described in Table 6.1. The table lists quantity of
containers and packed weight and cubage of each container,
together with the total quantity, cubage, and weight
of the shipment. The logistic data given is to used
by the site for preparation of the receival and for
providing temporary storage area.
R̲e̲m̲o̲t̲e̲ ̲S̲i̲t̲e̲ ̲I̲n̲s̲t̲a̲l̲l̲e̲d̲ ̲E̲q̲u̲i̲p̲m̲e̲n̲t̲
Total
Total
Item Item Size of Cont. Container Packed Container
D̲e̲s̲c̲r̲i̲p̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲Q̲t̲y̲ ̲ ̲ ̲W̲x̲D̲x̲H̲ ̲(̲c̲m̲)̲ ̲ ̲ ̲ ̲ ̲Q̲t̲y̲ ̲ ̲ ̲ ̲ ̲W̲e̲i̲g̲h̲t̲ ̲(̲k̲g̲)̲ ̲ ̲C̲u̲b̲a̲g̲e̲
̲(̲c̲b̲m̲)̲
STAT MUX RACK 1 72x126x192 1 385 1.74
MSP 2 65x74x39 2 74 0.38
VDU 2 65x80x55 2 86 0.57
CR80S, 1U MODULE 4
CR80S, 2U MODULE 1 …0e…29x38x35 1 5 0.04…0f…
PLF 1 30x48x32 1 10 0.05
STAT. MUX. 1 54x32x61 1 5 0.11
CABLES - 54x32x61 1 ̲5̲ 0̲.̲1̲1̲
TOTAL 5̲7̲0̲ 3̲.̲0̲0̲
Table 6.1…01…Logistic Data…01…CRT Site 02A
6.1.2 T̲r̲a̲n̲s̲p̲o̲r̲t̲a̲t̲i̲o̲n̲ ̲t̲o̲ ̲S̲i̲t̲e̲
The CAMPS equipment will be carried to site by truck.
The equipment will be loaded at CR's plant in Copenhagen
and transported directly to site without any transshipment.
CR will use an experienced transportation company for
the conveyence.
The truck used will be an aircushion vehicle type with
the dimensions indicated in Table 6.2.
T̲r̲u̲c̲k̲ T̲r̲u̲c̲k̲ ̲+̲ ̲l̲o̲a̲d̲
̲
Weight 9 tons 14 tons
Size (m) 3.75Hx2.50Wx9.75L
Axle load, front 2 tons 6 tons
Axle load, rear 5 tons 10 tons
Table 6.2…01…Truck Dimensions
6.1.3 R̲e̲c̲e̲i̲p̲t̲ ̲o̲f̲ ̲E̲q̲u̲i̲p̲m̲e̲n̲t̲ ̲a̲t̲ ̲R̲e̲m̲o̲t̲e̲ ̲T̲e̲r̲m̲i̲n̲a̲l̲ ̲S̲i̲t̲e̲ ̲0̲2̲A̲
a) Depending on the distance between the main site
and the CRT site, the CR installation team will
perform the receipt of the CRT equipment.
b) In case the team is prevented from being present,
the CRT site will handle the receipt according
to the instructions given in section 6.3.
c) All containers are marked with a number.
A complete set of packing lists is enclosed in
container No. 1 and a set is attached to the outside
of container No. 1.
6.2 P̲R̲E̲P̲A̲R̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲A̲T̲ ̲C̲R̲T̲ ̲0̲2̲A̲
6.2.1 P̲r̲e̲p̲a̲r̲a̲t̲i̲o̲n̲ ̲b̲y̲ ̲C̲R̲
a) Prior to the planned arrival of the installation
team, the officer in charge of the CRT site is
informed by telex or phone call.
b) Upon arrival, the local CRT officer in charge will
give a briefing, addressing the following subjects:
- Access to site and house rules
- Location of applicable areas such as storage
area, parking and unloading area, CRT equipment
area, etc.
- The support requested by contractor, ref. 6.3.
- Introduction of the installation team to relevant
local personnel.
- Information regarding local facilities such
as cafeteria, telephones, medical aid, etc.
c) The installation team will present the planned
major steps of the installation efforts. Ref 6.4
through 6.18.
6.2.2 P̲r̲e̲p̲a̲r̲a̲t̲i̲o̲n̲s̲ ̲b̲y̲ ̲S̲i̲t̲e̲
a) The CRT equipment rooms are prepared for installation
of the equipment according to the civil works requirements.
b) Arrangements to be made for CR's presence at site
are described in section 6.3.
6.3 I̲N̲S̲T̲R̲U̲C̲T̲I̲O̲N̲S̲ ̲T̲O̲ ̲T̲H̲E̲ ̲C̲R̲T̲ ̲S̲I̲T̲E̲ ̲0̲2̲A̲
This section contains instructions to the site concerning
the site assistance and support to CR during installation.
As stated above these instructions are to be discussed
and finalized during the site verification meetings.
6.3.1 R̲e̲c̲e̲i̲p̲t̲ ̲o̲f̲ ̲t̲h̲e̲ ̲E̲q̲u̲i̲p̲m̲e̲n̲t̲ ̲b̲y̲ ̲S̲i̲t̲e̲
In case CR's installation team is prevented from participating
in the receipt of the equipment, the transportation
personnel has been instructed to unpack the equipment
as close as possible to the installation site.
a) The equipment will be moved to the installation
site by the transportation company.
b) The site is requested to assist the transportation
company as follows:
- Escort the transportation personnel.
- Point out the equipment entry route.
- See that the corridors on the entry route are
cleared.
- See that the installation areas are cleared.
- See to that all site provided terminal tables
are cleared.
- Point out the installation sites (location
of rack installation site in the stat. mux.
room).
- Provide site truck/trolley/pushwaggon as available
upon request by the transportation company.
c) Above mentioned arrangements will be discussed
and finalized during the site verification meetings.
6.4 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲P̲R̲E̲P̲A̲R̲A̲T̲I̲O̲N̲S̲ ̲A̲N̲D̲ ̲S̲U̲P̲P̲O̲R̲T̲
The site is requested to provide the following preparations
and support prior to or during CR's presence at site.
1 Clear the CRT installation area.
2 Provide/clear tables for the user terminals to
be installed on customer provided tables.
3 Clear the equipment entry route from unloading
area to CRT equipment room and from unloading area
to storage area.
4 Provide escort of the transportation personnel.
5 Provide temporary storage area for the equipment
specified in table 6-1.
6 Provide access to site, access badges to be ready
at arrival of the installation team. Request for
access and identification credentials of the team
members will be forwarded through SHAPE.
7 Provide access to commercial telephone and telex
allowing for international communication. The use
to be reimbursed by CR.
8 Provide access to canteens or messes for CR personnel,
if available.
9 Provide emergency medical aid in case of accidents.
10 Provide access to reproduction facilities, if available.
11 Provide site truck/trolley/pushwaggon for transportation
in the corridors, if available and upon request.
6.5 S̲H̲I̲P̲M̲E̲N̲T̲ ̲C̲O̲N̲T̲A̲I̲N̲E̲R̲S̲
As explained in section 6.1.1, the equipment is shipped
in different containers; many of these are reusable.
It is, therefore, recommended that the site stores
1-2 empty containers for later use.
The installation team will point out the containers
which are recommended for later reuse to the SHAPE/site
representatives and the remaining containers will be
discarded by CR.
In case the CR installation team is prevented from
participating in the receipt of the equipment, the
transportation company is instructed to leave the containers
recommended for later reuse.
6.6 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲R̲E̲M̲O̲T̲E̲ ̲T̲E̲R̲M̲I̲N̲A̲L̲ ̲E̲Q̲U̲I̲P̲M̲E̲N̲T̲ ̲S̲I̲T̲E̲ ̲0̲2̲A̲
The following step-by-step procedure contains a detailed
instruction set of how to install the CR delivered
equipment for the remote terminal site.
The major tasks of the installation sequence are:
6.7 UNPACKING
6.8 TRANSPORTATION TO SITE
6.9 MOUNTING OF LEVELLERS
6.10 MOUNTING OF POWER LINE FILTER
6.11 REMOUNTING OF STAT. MUX.
6.12 INSTALL. INT. POWER/SIGNAL CABLES
6.13 INSTALL. EXT. POWER/SIGNAL CABLES
6.14 REMOUNTING OF MODULES
6.14 INSTALLATION OF DELTA VDU
6.16 INSTALLATION OF TRACOR MSP
6.17 POWER UP AND CHECK OUT
6.18 TESTS OF DELTA VDU
6.19 TEST OF TRACOR MSP
6.20 OPERATIONAL TEST OF USER TERMINALS
6.21 INVENTORY CHECK
6.7 U̲N̲P̲A̲C̲K̲I̲N̲G̲
a) The EMI Stat. Mux. rack for the remote terminals
is packed in its original wooden container.
The rack should remain packed during site internal
transportation and only be unpacked close to the
installation site, but if the space along the access
route is limited, the rack can be unpacked before
transportation to the installation site. The racks
is unpacked as follows:
b) Remove the top cover of the wooden container by
demounting the 3 ea 1/4 x 2.1/2" bolts on each
side of the continer and the 4 ea 1/2 - 13 x 2"
bolts, one in each top corner (see Figure 6.1-1).
c) The 4 walls of the container are removed by loosening
the 21 ea 1/4 x 2.1/2" bolts on each short side.
d) The rack is bolted to the container bottom in each
corner by a 1/2 - 13 x 2.1/2" bolt.
e) These bolts are removed from under the container
bottom.
6.8 T̲R̲A̲N̲S̲P̲O̲R̲T̲A̲T̲I̲O̲N̲ ̲T̲O̲ ̲I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲S̲I̲T̲E̲
a) After unpacking, the front and rear door of the
rack must be removed. Check that serial number
in
the rack correspond to the serial number of the
doors.
b) Be carefull not to damage the gaskets on the door.
c) Depending on means of transportation, 4 eyelets
can be mounted in the top of the rack in the position
of the removed 4 ea 1/2 - 13 x 2" bolts.
Figure 6.7-1
6.9 M̲O̲U̲N̲T̲I̲N̲G̲ ̲O̲F̲ ̲L̲E̲V̲E̲L̲L̲E̲R̲S̲
a) The 4 levellers are mounted from under the racks
two by two, by tilting the racks (see As Build
drawing 152).
b) The levellers are mounted to a distance of 40 mm
between the bottom of the rack and the floor.
c) The levellers must be adjusted to ensure equal
distribution of the floor load.
6.10 M̲O̲U̲N̲T̲I̲N̲G̲ ̲O̲F̲ ̲P̲O̲W̲E̲R̲ ̲L̲I̲N̲E̲ ̲F̲I̲L̲T̲E̲R̲
a) Place the power line filter (PLF) under the two
front/top knockouts in the rack (see As Build drawing
152).
The 2 1/2" male adaptor, welded to the PLF is to
be inserted through the hand knockout seen from
the front.
b) Place the tightening washer from outside the EMI
rack.
c) Insert the 2.1/2" to 1" reducing bushing and the
outer washer through the knockout into the PLF
through the right hand knockout (see ATBB drawing
152).
d) Mount the 1" to 3/4" reducing bushing and the 3/4"
45…0e…o…0f… fitting into the 2.1/2" to 1" reducing bushing.
It is very important to the shielding that the fittings
are extremely tightened.
6.11 R̲E̲M̲O̲U̲N̲T̲I̲N̲G̲ ̲O̲F̲ ̲S̲T̲A̲T̲.̲ ̲M̲U̲X̲.̲
The only separately packed unit, the Stat. Mux., is
unpacked and installed from the front side into the
stat. mux. housing, see ATBB drawing 155. The stat.
mux. unit is locked by the left-hand and right-hand
locking screws.
6.12 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲I̲N̲T̲E̲R̲N̲A̲L̲ ̲P̲O̲W̲E̲R̲/̲S̲I̲G̲N̲A̲L̲ ̲C̲A̲B̲L̲E̲S̲
All internal signal and power cables are mounted upon
receipt except for the following cables:
a) Due to the removal of the stat. mux. during the
transportation, the 9 interface cables between
the stat. mux and the back panels of the adapter
crate/ filter box must be reconnected:
W7 to stat. mux. modem (from filter box J40)
W8 to stat. mux. terminal 1
W9 - - - - 2
W10 - - - - 3
W11 - - - - 4
W12 - - - - 5
W13 - - - - 6
W14 - - - - 7
W15 - - - - 8
The cables are fastened by the 2 fingerscrews in
the cannon plug.
b) The stat. mux. power cable is connected to the
power distribution panel (J3).
c) The mains switch power cable (J1) is connected
to the power line filter (J1).
6.13 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲E̲X̲T̲E̲R̲N̲A̲L̲ ̲P̲O̲W̲E̲R̲/̲S̲I̲G̲N̲A̲L̲ ̲C̲A̲B̲L̲E̲S̲,̲
A̲N̲D̲ ̲M̲O̲U̲N̲T̲I̲N̲G̲ ̲O̲F̲ ̲F̲I̲T̲T̲I̲N̲G̲S̲
6.13.1 L̲e̲f̲t̲ ̲H̲a̲n̲d̲ ̲R̲e̲a̲r̲ ̲T̲o̲p̲ ̲P̲e̲n̲e̲t̲r̲a̲t̲i̲o̲n̲
a) Place the tightening washer on the 2.1/2" to 1.1/2"
reducing bushing.
b) Insert the reducing bushing from the outside through
the knock out into the filterbox and tighten it
from the inside by the inner nut (see ATBB drawing
152).
c) Mount the 1.1/2" steel tube in the reducing bushing.
d) Mount the 48 mm metallic conduit to the steel
tube and tighten it by the clamps.
c) Mount the 1.1/2" steel tube by means of the two
nuts to the cable duct and connect the metallic
conduit by clamps (see ATBB drawing 152).
6.13.2 R̲i̲g̲h̲t̲ ̲H̲a̲n̲d̲ ̲R̲e̲a̲r̲ ̲T̲o̲p̲ ̲P̲e̲n̲e̲t̲r̲a̲t̲i̲o̲n̲
Repeat step 6.7.1 for the right hand top penetration.
6.13.3 A̲u̲x̲.̲ ̲C̲o̲n̲n̲e̲c̲t̲i̲o̲n̲s̲ ̲a̲n̲d̲ ̲M̲o̲d̲e̲m̲ ̲C̲a̲b̲l̲e̲
a) The aux. connections (W38-41) and the modem cable
(W21) are pulled through the right hand penetration
and into the filter box (see ATBB drawing 155).
b) The modem cable is terminated by a cannon plug
and connected to J40 in the filter box. For pin
assignment, see ATBB page 5.4.
c) The aux. connections are terminated by host nation
and connected in the filterbox according to ATBB
drawing 155.
6.13.4 R̲i̲g̲h̲t̲ ̲H̲a̲n̲d̲ ̲F̲r̲o̲n̲t̲ ̲P̲e̲n̲e̲t̲r̲a̲t̲i̲o̲n̲
C̲A̲U̲T̲I̲O̲N̲: Before terminating the external power
cable, assure that the switched power
outlet is disconnected or in condition
OFF.
a) Mount the 3/4" 45…0e…o…0f… fitting in the J-box according
to ATBB drawing 152.
b) Connect the 3/4" metallic conduit between the J-box
and the power line filter.
c) The external 220V cable coming from the switched
power outlet and the seperate insulated ground
wire are pulled through the conduit into the power
line filter.
d) For access to the PLF, remove the metallic cover
fastened by 4 screws during transportation. The
remaining 26 screws are shipped attached to inside
wall of the PLF. The cables and the ground wire
are dismantled and terminated with cable shoes.
For details of the connection to the terminal board
see ATBB drawing 152.
e) Measure with an Ohm-meter that no short circuit
exists between the safety ground (cabinet) and
the line in the PLF.
f) When the cables have been properly connected, the
metallic lid of the PLF is reinstalled by the 30
screws.
6.13.5 U̲s̲e̲r̲ ̲T̲e̲r̲m̲i̲n̲a̲l̲ ̲C̲a̲b̲l̲e̲s̲/̲L̲e̲f̲t̲ ̲H̲a̲n̲d̲ ̲R̲e̲a̲r̲ ̲P̲e̲n̲e̲t̲r̲a̲t̲i̲o̲n̲
a) The 4 opto cables (W22-23 and W30-31) are pulled
through the left hand penetration, through the
filter box into the rack trays and out to the front
of the adapter crate through the cable channel
assembly, see ATBB drawing 155.
b) The opto cables are terminated by special opto
connectors and connected to the opto T/R:
W22 VDU 2 Opto T/R A1A7A5
W23 VDU 3 - A1A7A6
W30 MSP 10 - A1A7A7
W31 MSP 11 - A1A7A8
See ATBB drawing 155.
6.14 M̲O̲U̲N̲T̲I̲N̲G̲ ̲O̲F̲ ̲M̲O̲D̲U̲L̲E̲S̲
a) For correct physical positioning of the separately
packed modules, refer to the enclosed packing list.
The packing list states the serial No. of the unit,
the crate assy No., the slot No. in the crate and
the address of the physical position in the system.
b) The modules are slided into the print guide and
when the edge connector of the print has entered
the connector of the motherboard, the modules are
fastened by the fixing screw on the front of the
modules.
6.15 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲D̲E̲L̲T̲A̲ ̲V̲D̲U̲
6.15.1 P̲o̲w̲e̲r̲ ̲P̲l̲u̲g̲ ̲C̲o̲n̲n̲e̲c̲t̲i̲o̲n̲s̲
Power plug connections must be exchanged to fit host
nation provided power outlets.
P̲O̲W̲E̲R̲ ̲C̲O̲R̲D̲ ̲F̲R̲O̲M̲ ̲D̲E̲L̲T̲A̲ 3̲-̲P̲I̲N̲N̲E̲D̲ ̲P̲L̲U̲G̲
Brown Phase
Blue Neutral
Green/Yellow Ground
6.15.2 T̲e̲r̲m̲i̲n̲a̲t̲i̲o̲n̲ ̲o̲f̲ ̲O̲p̲t̲o̲ ̲C̲a̲b̲l̲e̲s̲
a) Before termination of the opto cable, a rubber
tubing, size 8 x 12 x 250mm, must be mounted on
the cable, see ATBB drawing 157.
b) To get access to the OPTO T/R located inside the
VDU, unlock the two snappers on the rear and lift
the terminal access cover of the VDU.
c) The opto fibres are to be pulled through the rear
waveguide (port 3) into the VDU, see ATBB drawing
157.
d) The two fibres must be terminated with special
opto connectors, ref doc. No. 4.
e) In case of opto splicing this will be done by mounting
of an adapter between the two male connectors,
using the same kind of male connectors as for the
terminals.
f) Before connecting the two fibres to the Optical
modem board in the VDU, the black receiver cable
with the opto connector must be checked for supplying
sufficient light emission.
The transmitter of the opto T/R in the adapter
crate is used as source for the opto fibre (black
cable connected to transmitter).
g) Connect the black fibre in the VDU-end to the 11XE
fiber optic power meter and verify that the optical
power output does no exceed -34.6dBm.
h) In case the light emission exceeds - 34.6 dBm,
the cable will be terminated with a new pair of
OPTO connectors. It still outside tolerance the
cable will be marked as Bad and a new cable must
be installed.
i) To get access to the optical modem board located
inside the VDU, unlock the two snappers on the
rear and lift the terminal access cover of the
VDU.
j) The white fibre must be connected to the transmitter
jack ("out") and the black fibre to the receiver
jack ("in") (see ATBB drawing 157).
k) The opto cable must be permanently marked with
cable No during the termination procedure.
6.15.3 M̲o̲u̲n̲t̲i̲n̲g̲ ̲o̲f̲ ̲K̲e̲y̲b̲o̲a̲r̲d̲ ̲a̲n̲d̲ ̲K̲e̲y̲s̲
a) The keyboard cable is connected to the female cannon
plug located on the (front view) lower right hand
front of the terminal. The connector is secured
by the two front screws.
b) Remove the two keys placed on the inside of the
terminal access cover and insert the keys in the
key-lock on front of the terminal.
6.16 I̲N̲S̲T̲A̲L̲L̲A̲T̲I̲O̲N̲ ̲O̲F̲ ̲T̲R̲A̲C̲O̲R̲ ̲M̲S̲P̲
6.16.1 P̲o̲w̲e̲r̲ ̲P̲l̲u̲g̲ ̲C̲o̲n̲n̲e̲c̲t̲i̲o̲n̲s̲
Repeat step 6.15.1 for the MSP.
6.16.2 T̲e̲r̲m̲i̲n̲a̲t̲i̲o̲n̲ ̲o̲f̲ ̲O̲p̲t̲o̲ ̲C̲a̲b̲l̲e̲s̲
a) Before termination of the opto cable, a rubber
tubing size 8x12x250 mm must be mounted on the
cable, see ATBB drawing 157.
b) Install the fibres through the rear connector entry
hole, route through the optical cable entry hole
and connect the while fibre to the transmitter
("output") and the black fibre to the receiver
("input"), see ATBB drawing 157.
c) Repeat step 6.15.2 items c) through f).
d) To get access to the optical modem board located
inside the printer, unlock the two snappers in
front of the printer and lift the cover of the
printer.
h) The opto cable must be permanently marked with
cable number during the termination procedure.
i) Install the paper and the ribbon according to the
instructions in the operator's manual.
j) Remount the Piston spring between the lid and the
bottom, by rotating it clockwise into the screw
thread in bottom of the Printer. The Piston is
connected to the lid by the two Philips screws
and the hinge mounted in the lid.
k) Remove the two keys placed on the outside of the
lid and insert the keys in the key-lock on front
of the terminal.
6.17 P̲O̲W̲E̲R̲ ̲U̲P̲ ̲A̲N̲D̲ ̲C̲H̲E̲C̲K̲ ̲O̲U̲T̲
1) T̲U̲R̲N̲ ̲O̲N̲:̲ The switched power outlet and the
right hand mains switch in the bottom
of the rack.
C̲H̲E̲C̲K̲: Green "Power ON" lamp above switch
is lit.
2) T̲U̲R̲N̲ ̲O̲N̲: Power switch on adapter power supply,
left hand part of the rear of the
adapter crate.
C̲H̲E̲C̲K̲:̲ "Power On" lamps lit on the 4 opto
T/R and the L/L adapter.
3) T̲U̲R̲N̲ ̲O̲N̲:̲ Remove the front panel of the stat.
mux.
Turn on the power switch located on
front of the stat.mux to the left
hand side.
C̲H̲E̲C̲K̲:̲ Fan in stat.mux is running. Lamp for
fuse not lit. "AT" lamp on indicator
panel lit.
6.18 T̲E̲S̲T̲ ̲O̲F̲ ̲D̲E̲L̲T̲A̲ ̲V̲D̲U̲
a) Connect the power plug to the wall outlet.
b) Turn on the "power on/off" switch located on the
lower right front of the terminal.
c) Operate the keylock switch to the ON position (turn
right) (right hand front panel).
d) Immediately after power up the terminal executes
a series of system diagnostics. If all are working
properly, the power-up menu will be displayed on
the screen within 10 seconds.
e) Adjust the intensity and focus until the characters
are clear and bright. Do not advance the intensity
too far or the display area may be highlighted.
f) Adjust the audible alarm for the desired sound
level (control shift and the G key).
g) When all terminals have been switched on and locally
tested, the transmitter of the optical modem board
in the VDU, the white opto cable, and the opto
connection to the adaptor crate must be checked
for supplying sufficient light emission.
h) Connect one by one all the while fibres terminated
in the opto T/R located in the adaptor crate to
the 11XE fibre optic power meter and check that
the optical power output does not exceed -34.6dBm.
6.19 T̲E̲S̲T̲ ̲O̲F̲ ̲T̲R̲A̲C̲O̲R̲ ̲M̲S̲P̲
a) Connect the power plug to the wall outlet.
b) Turn on the power switch located on the rear right
hand side.
Verify that the power lamp on the front panel lights.
c) Operate the key-lock switch to the ON position
(left hand side in front).
d) Depress the "line feed" button on the TCM front
panel and verify that line feed of paper occurs.
e) Press the test button for not more than 4 sec.
Verify that all lamps on the printer lights.
f) Press the test button for at least 5 sec. Verify
that the following is printed:
NO ERRORS IN ROM
NO ERRORS IN RAM
66 LINES BARBERPOLE PATTERN
g) Repeat step 6.15 item g) and h) for test of transmitter
and opto connections.
6.20 O̲P̲E̲R̲A̲T̲I̲O̲N̲A̲L̲ ̲T̲E̲S̲T̲ ̲O̲F̲ ̲U̲S̲E̲R̲ ̲T̲E̲R̲M̲I̲N̲A̲L̲S̲
6.20.1 T̲e̲s̲t̲ ̲o̲f̲ ̲C̲r̲y̲p̲t̲o̲/̲A̲n̲a̲l̲o̲g̲ ̲L̲i̲n̲e̲
a) Press the test switch in the stat. mux. on both
the main site and the remote site.
b) Check that no inbound error is registrated on either
stat. mux.
6.20.2 T̲e̲s̲t̲ ̲o̲f̲ ̲V̲D̲U̲
a) Assure that the required terminal functions and
characteristics are correctly stored by checking
the contents of the configuration menu.
Correct CAMPS Application contents to be:
DEL/BS - N̲ PRT CR DLY -
0̲
ECHO - N̲ PRT LF AFT CR -
N̲
CR-XOFF - N̲ PRT PROT DATA -
N̲
XMT SO SEQ - N̲ PRT BSY -
N̲
MEM RELEASED - Y̲ PRT BUSY-HIGH -
N̲
LEFT MARGIN - 0̲0̲ PRT FF -
N̲
BAUDOT - N PRT BUF (0,1,2,3) -
0̲
WRU?X̲7̲2̲7̲0̲ WHATRU? CAMPS CLK 0̲0̲0̲0̲0̲0̲
I/O HOST PTR
CHAR 7̲ 7̲
PARITY E̲ E̲
STOP BITS C̲ C̲
BAUD RATE G̲ G̲
b) The terminal is logged on to the system
according to procedures stated in the
Operator's Manual.
c) Messages are sent/rec. between the terminal
and the main site.
6.20.3 T̲e̲s̲t̲ ̲o̲f̲ ̲M̲S̲P̲
Arrange to have one or more messages sent to the MSP
and verify message contents with the transmitting station.
Verify during print out that the key-lock switch stops
the printing and that no part of the message is lost
when it is turned on again.
6.21 I̲N̲V̲E̲N̲T̲O̲R̲Y̲ ̲C̲H̲E̲C̲K̲
a) As a final step of the installation
procedure, the CR installation team
will conduct an inventory check of the
delivered Remote Tare equipment to verify
that the equipment is complete.
b) This inventory inspection will be witnessed
by the customer.
c) The inventory is performed in accordance
with the updated inventory list prepared
by CR.
d) The results are recorded on the inventory
list and signed by both parties.