top - download
⟦aa23b56fe⟧ Wang Wps File
Length: 69695 (0x1103f)
Types: Wang Wps File
Notes: CPS/TCM/005 (4-4.3.3+4.4+
Names: »2472A «
Derivation
└─⟦5bcf9c7c7⟧ Bits:30006165 8" Wang WCS floppy, CR 0230A
└─ ⟦this⟧ »2472A «
WangText
=…00……00……00……00……14……0a……00……00……14……0b……14……00……14……01……13……09……13……0f……13……00……13… …12……08……12……09……12……0c……12……0d……12……01……12……02……11……08……11……0d……11……0e……11……00……11……05……10……0a……10……0f……10……00……10……06……0f……0b……0f……0c……0f……02……0f……05……0e……0b……0e……00……0e……05……0e……06……0d……09……86…1 …02… …02… …02…
2472A/ktd …02…CPS/TCM/005
…02…KJA/830912…02……02…
CAMPS SITE LEVEL MAINTENANCE MANUAL
…02…Issue 1…02…CAMPS
4 C̲O̲R̲R̲E̲C̲T̲I̲V̲E̲ ̲M̲A̲I̲N̲T̲E̲N̲A̲N̲C̲E̲
4.1 I̲N̲T̲R̲O̲D̲U̲C̲T̲I̲O̲N̲
The objective of corrective maintenance is to detect
whenever an error has occurred, perform the necessary
repair, and bring the system back to normal operation.
This is achieved by using the structured troubleshooting
procedures.
An overview of the corrective maintenance tasks is
given in Table 4.1-1.
The tasks are briefly explained below.
The error printout on the maintenance position printer
will provide an entry point to a particular troubleshooting
procedure and by following the descriptions outlined,
the error will be isolated to a particular module.
This is then interchanged with a spare module. A verification
test is performed before reloading the application
programs and bringing the system back to normal operation.
The structure of Chapter 4 is as follows:
- Section 4.2 describes a hardware (H/W) breakdown
of the CAMPS system into 5 sub-systems. Each of
the sub-systems is a logically separated unit which
is the first step in the error isolation.
This section gives an overview of the H/W included
in each of the logical sub-systems in which the
Off-line Troubleshooting Tree is divided.
Table 4.1-1
An Overview of the Corrective Maintenance Tasks
- Section 4.3 contains the troubleshooting procedures
in which the strategy of tracing a detected error
to a module is described. The troubleshooting procedures
are described by a System Troubleshooting Tree
and an Off-line Troubleshooting Tree.
The System Troubleshooting Tree contains the relation
between the error report printed on the maintenance
position printer and the first step (entry point)
in the Off-line Troubleshooting Tree.
The Off-line Troubleshooting Tree contains a step-by-step
description of the test procedures necessary to
be executed when tracing a detected error to an
H/W module.
- Section 4.4 describes the replacement procedures
for modules/crates/units mounted in the racks.
These procedures should be followed after the troubleshooting
procedures have isolated the error to a particular
module/unit/crate.
- Section 4.5 describes the controls, indicators,
switch settings, idle indication, and input/output
(I/O) addresses of the modules within the CAMPS
system and is considered as a reference to the
troubleshooting procedures and replacement procedures.
- Section 4.6 describes the task of the on-line error
reporting programs, and the steps of troubleshooting
when an on-line error report is printed on the
maintenance position printer.
- Section 4.7 provides a description of activating
commands, printouts, and interpretation of error
codes for each of the off-line maintenance & diagnostic
(M&D) test programs.
The off-line M&D test sequences are used in the
off-line troubleshooting procedures.
- Section 4.8 provides for each of the Built-in-Test
(BIT) programs a description of the activating
procedures and results.
The BIT programs are used in offline troubleshooting
procedures.
4.2 S̲Y̲S̲T̲E̲M̲ ̲B̲R̲E̲A̲K̲D̲O̲W̲N̲
The CAMPS site equipment is broken down into logically
separated subsystems.
Section 4.2 shows the H/W modules included in each
of these subsystems.
The Offline Troubleshooting Tree (Section 4.3.3) is
also based on these subsystems.
The relationship between section 4.2 and 4.3.3 is as
follows:
S̲u̲b̲s̲y̲s̲t̲e̲m̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲S̲e̲c̲t̲i̲o̲n̲ ̲4̲.̲2̲ ̲ ̲ ̲ ̲ ̲S̲e̲c̲t̲i̲o̲n̲ ̲4̲.̲3̲.̲3̲
Processor Unit (PU) 4.2.1 Step 1000-2000
Channel Unit (CU) 4.2.2 Step 2000-3000
Watchdog Unit (WD) 4.2.3 Step 3000-4000
TDX Unit 4.2.4 Step 4000-5000
D̲i̲s̲t̲r̲i̲b̲u̲t̲i̲o̲n̲ ̲E̲q̲u̲i̲p̲m̲e̲n̲t̲ ̲ ̲ ̲ ̲4̲.̲2̲.̲5̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲S̲t̲e̲p̲ ̲5̲0̲0̲0̲-̲6̲0̲0̲0̲
4.2.1 P̲r̲o̲c̲e̲s̲s̲o̲r̲ ̲U̲n̲i̲t̲ ̲S̲u̲b̲s̲y̲s̲t̲e̲m̲ ̲(̲P̲U̲)̲.
The Processor Unit Subsystem consists of:
a) Online Processor Unit (PU) which performs the operational
processing.
b) Standby PU/offline PU. The Processor Unit that
is not online is standby if not taken offline for
repair or test of hardware modules, or for loading
and checking of new software.
The H/W elements included in each of the PUs are shown
in Figure 4.2.1-1
Further information about the PU Subsystem structure
and interface to the Channel Unit, Watchdog and TDX
Subsystem are provided in:
CAMPS System Description Manual, Doc.No. CPS/SDM/001.
CAMPS H/W Assembly Breakdown, Doc.No. CPS/SDS/017
Figure 4.2.1-1
Processor Unit Subsystem
4.2.2 C̲h̲a̲n̲n̲e̲l̲ ̲U̲n̲i̲t̲ ̲S̲u̲b̲s̲y̲s̲t̲e̲m̲ ̲(̲C̲U̲)̲
The Channel Unit Subsystem provides access by the PUs:
a) Three disks via disk controllers. Two of the disks
form a "mirrored pair". The third disk has a removable
disk pack.
b) Two floppy disks via a floppy disk controller.
c) The computer system CCIS and SCARS via Line Termination
Units (LTUs).
d) Local and remote NICS TARE network nodes via LTUs.
The H/W elements included in the CU Subsystem are shown
in Figure 4.2.2-1
Further information about the CU Subsystem structure
and interface to the Processor Unit, External Lines
and disks are provided in:
CAMPS System Description Manual, Doc.No. CPS/SDM/001.
CAMPS H/W Assembly Breakdown, Doc.No. CPS/SDS/017
4.2.3 W̲a̲t̲c̲h̲d̲o̲g̲ ̲S̲u̲b̲s̲y̲s̲t̲e̲m̲ ̲(̲W̲D̲)̲
It is possible via the Watchdog Subsystem to monitor
the CAMPS System. It contains the master clear (RESET)
for the system and permits the maintenance position
to communicate with the online PU and the standby PU/
offline PU.
The H/W elements included in the WD Subsystem are shown
in Figure 4.2.3-1 along with the Configuration Control
Adapters (CCAs) and the BSM-Xs which are connected
to the WD via the Configuration Control Bus (CCB).
Further information about the WD Subsystem structure
and interface to the Processor Units and maintenance
position are provided in:
CAMPS System Description Manual Doc.No. CPS/SDM/001
CAMPS H/W Assembly Breakdown, Doc.No. CPS/SDS/017.…86…1
…02… …02… …02… …02…
Figure 4.2.3-1
Watchdog Subsystem
4.2.4 T̲D̲X̲ ̲S̲u̲b̲s̲y̲s̲t̲e̲m̲
The TDX Subsystem provides communication between the
PUs and the distribution equipment (refer to section
4.2.5).
The H/W elements included in the TDX Subsystem are
shown in Figure 4.2.4-1.
Further information about the TDC Subsystem structure
and interface to the Processor Units and Distribution
Equipment are provided in:
CAMPS System Description Manual, Doc.No. CPS/SDM/001
CAMPS H/W Assembly Breakdown, Doc.No. CPS/SDS/017
Figure 4.2.4-1
TDX Subsystem
4.2.5 D̲i̲s̲t̲r̲i̲b̲u̲t̲i̲o̲n̲ ̲E̲q̲u̲i̲p̲m̲e̲n̲t̲ ̲S̲u̲b̲s̲y̲s̲t̲e̲m̲
The Distribution Equipment Subsystem provides the communication
between the TDX Subsystem and the surroundings, i.e.:
a) Local Visual Display Units (VDUs)
b) Local Medium Speed Printers (MSPs)
c) Low Speed Telegraph Lines (Tape Relay Centers,
Point-to-Point connections, Teleprinters and
Low Speed TAREs)
d) Remote Terminals via Statistical Multiplexers
e) Optical Character Reader (OCR)
f) Paper Tape Reader/Puncher (PTR/PTP)
The H/W elements included in the Distribution Equipment
Subsystem are shown in Figure 4.2.5-1.
Further information about the Distribution Equipment
Subsystem Structure and interface to the TDX Subsystem
and the connected peripherals are provided in:
CAMPS System Description Manual, Doc.No. CPS/SDM/001
CAMPS H/W Assembly Breakdown, Doc.No. CPS/SDS/017
Figure 4.2.5-1
Distribution Equipment Element
4.3 T̲R̲O̲U̲B̲L̲E̲S̲H̲O̲O̲T̲I̲N̲G̲ ̲T̲R̲E̲E̲S̲
4.3.1 T̲r̲o̲u̲b̲l̲e̲s̲h̲o̲o̲t̲i̲n̲g̲ ̲T̲r̲e̲e̲s̲,̲ ̲O̲v̲e̲r̲v̲i̲e̲w̲
The troubleshooting procedures of the CAMPS equipment
are described by two troubleshooting trees:
- System Troubleshooting Tree (refer to Section 4.3.2)
- Offline Troubleshooting Tree (refer to Section
4.3.3)
An overview of the main actions in the troubleshooting
procedures of the CAMPS equipment are presented in
Figure 4.3.1-1. An explanation of the Figure is given
below:
a) in Figure 4.3.1-1:
The troubleshooting of the CAMPS equipment starts
when an Error Report is printed at the maintenance
position (All the possible error reports are listed
in Appendix A) or if any deviation is deleted.
b) in Figure 4.3.1-1:
The System Troubleshooting Tree identifies the
first step in the troubleshooting procedure.
If a H/W error report is printed at the maintenance
position the next step in the troubleshooting procedure
is an identification of the first step (the Entry
Point) in the Offline Troubleshooting Tree. The
relation between the Error Report and the first
step in the Offline Troubleshooting Tree is presented
in Figure 4.3.2-1.
A H/W error report is generated by software modules
(ex: device handles) that are controlling a physical
device.
If a S/W error report is printed at the maintenance
position the further procedures are described in
Section 5.
A S/W error report is generated when one or more
errors are detected during the execution of a process
either by the process itself, by an accessed process
or by the central processing element.
If a deviation is detected in the equipment and
no error report is generated then the system troubleshooting
tree contains information about the strategy in
the troubleshooting procedures.
c) in Figure 4.3.1-1:
The Offline Troubleshooting Tree describes the
step-by-step procedures to be executed in order
to delete a H/W error from the CAMPS equipment.
d) in Figure 4.3.1-1:
Section 5.5 describes the procedures to be executed
from the moment of receiving a S/W error and to
the moment when the S/W error is deleted.
e) in Figure 4.3.1-1.
After the error is deleted the CAMPS system is
brought back to normal operation. This is done
by using the commands and procedures described
in the "MAINTENANCE POSITION OPERATION MANUAL".
f) in Figure 4.3.1-1.
When the system is brought back to normal operation,
the paperwork including logbook and Failure Reports
is completed (refer to Section 6).
…86…1 …02… …02… …02… …02…
Figure 4.3.1-1
TYPICAL REPAIR SEQUENCE…86…1 …02… …02… …02… …02…
her inds`ttes skema, er skrevet p> sidste side…01…printes p> hvidt papir u̲d̲e̲n̲
̲h̲o̲v̲e̲d̲
nedfotograferes derefter
Table 4.3.2-1
System Troubleshooting Tree - Overview…86…1 …02… …02… …02… …02…
4.3.2 T̲h̲e̲ ̲S̲y̲s̲t̲e̲m̲ ̲T̲r̲o̲u̲b̲l̲e̲s̲h̲o̲o̲t̲i̲n̲g̲ ̲T̲r̲e̲e̲
The SYSTEM TROUBLESHOOTING TREE presents:
a) the relation between the on line error report printed
at the maintenance position and the troubleshooting
procedure (refer to table 4.3.2-1).
b) the strategy in the troubleshooting procedures
when a deviation is detected.
a) T̲h̲e̲ ̲r̲e̲l̲a̲t̲i̲o̲n̲ ̲b̲e̲t̲w̲e̲e̲n̲ ̲t̲h̲e̲ ̲o̲n̲ ̲l̲i̲n̲e̲ ̲e̲r̲r̲o̲r̲ ̲r̲e̲p̲o̲r̲t̲ ̲a̲n̲d̲
t̲r̲o̲u̲b̲l̲e̲s̲h̲o̲o̲t̲i̲n̲g̲ ̲p̲r̲o̲c̲e̲d̲u̲r̲e̲s̲.
The on line error reports are presented in the
"REPORT-ID" column in table 4.3.2-1.
The first step in the troubleshooting procedure
is presented in the "ENTRYPOINT" column.
An example in the use of table 4.3.2-1 is given
below.
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
EXAMPLE:
The following error report is printed at the maintenance
position:
The REP-ID is: FMS019
The table 4.3.2-1 presents the first step to be
executed in the OFFLINE TROUBLESHOOTING TREE.
The first step is: 2000
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
b) Strategy in the troubleshooting procedures.
In case there is detected a deviation or an irregularity
in the CAMPS equipment and n̲o̲ error report is printed
at the maintenance position the following guide
provides the information about the troubleshooting
procedures to be executed.
Deviation Entry Point in Remarks
the trouble-
shooting tree
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲
Irregularity Step 6000 This situation in-
in the com- dicates an error
munication in the Maint.Pos.
between the VDU-Adapter Crate
-
Maint.Pos. WD - PU.
and the Cen-
tral Equipment.
Irregularity Step 6000 This situation in-
in connected dicates an error
peripheral in the TDX/CU crate
equipment or the peripheral.
Irregularity This situation is
in the Signal caused by a bad
or Power Di- connector or a
stribution in disconnected
the CAMPS Cen- wire/cable.
tral Equipment
Signal and Power
diagrams are provided
in the H/W Assembly
Breakdown Doc.No.
CPS/SDS/017 which
identifies all parts
of the CAMPS Central
Equipment by identification
code.
Deviation Entry Point in Remarks
the trouble-
shooting tree
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲
Not possible 3000 This situation
to CONTROL/ASSIGN appears when
a device in executing the
the Central Equip- commands described
ment in the Maintenance
Position Operation
Manual (Doc.No. CPS/OPM/009)
The "STATUS" of 3000 This situation
a device is: appears when
ERROR reading the STATUS
on the Maintenance
Position VDU. The
STATUS is contained
in some of the menus
in the FORMAT AREA
on the Maintenance
Position VDU.
Unreported See App. C. Identify the point
error in a of the system
part of the using Appendix C
CAMPS Central and execute all
Equipment. the test procedures
specified in the
referenced steps
of the offline troubleshooting
tree.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲
(This page is intentionally left blank)…86…1 …02… …02… …02… …02…
4.3.3 T̲h̲e̲ ̲O̲f̲f̲l̲i̲n̲e̲ ̲T̲r̲o̲u̲b̲l̲e̲s̲h̲o̲o̲t̲i̲n̲g̲ ̲T̲r̲e̲e̲.̲
The Offline Troubleshooting Tree specifies a method
to isolate a detected H/W error to a module.
Section 4.3.3.1 - 4.3.3.5 contains the Step-by-step
procedures to be executed when a H/W error is isolated
to a module.
Section 4.3.3 provides the following information about
the Offline Troubleshooting Tree:
a) An overview of the Offline Troubleshooting
Tree.
b) The structure of the Offline Troubleshooting
Tree.
c) The mode of the system before the Offline
Troubleshooting procedures can be executed.
a) A̲n̲ ̲o̲v̲e̲r̲v̲i̲e̲w̲ ̲o̲f̲ ̲t̲h̲e̲ ̲O̲f̲f̲l̲i̲n̲e̲ ̲T̲r̲o̲u̲b̲l̲e̲s̲h̲o̲o̲t̲i̲n̲g̲
̲T̲r̲e̲e̲
There is a Fold-Out in Appendix C which
shows the relation between the Offline
Troubleshooting Tree and the CAMPS system.
The Appendix C specifies for each module
in the CAMPS configuration the offline
test sequence in the Offline Troubleshooting
Tree which tests the module. The testsequences
are identified by: "STEP".
Note that there is only one test sequence
per type of modules. (An example is
the LTU test sequence STEP 2500 - 2600).
The test sequence makes it possible
to test all modules in the CAMPS system.
Appendix C specifies also the relation
between the on line error reports and
the part of the CAMPS system which the
error reports relate. The on line error
reports are identified by: "REP-ID".
The Appendix C can be used during the troubleshooting
of the CAMPS system to illustrate which part of the
CAMPS equipment:
- the online error report relate.
- the steps in the offline troubleshooting tree test.
The following example illustrates the use of Appendix
C.
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
E̲X̲A̲M̲P̲L̲E̲:̲
The following error report is printed at the maintenance
position:
This error report indicates that there is an error
in the LTUX-S module No: 11; i.e. the LTUX-S module
situated in slot 3 in the TDX crate # 1. (refer to
Appendix A).
The Fold-Out in Appendix C shows the relation between
the error report (indicated by REP-ID) and the first
step in the Offline Troubleshooting Tree. (indicated
by STEP).
The REP-ID in this example is TMS010. This REP-ID
is presented in the LTUX module in the TDX crate
in Appendix C.
The STEP presented in the LTUX module in Appendix
C shows the ENTRY POINT in the offline Troubleshooting
Tree.
The ENTRY POINT is: 4300.
* * * * * * * * * * * * * * * * * * * * * * * * * *
*
Figure 4.3.3-1
THE STRUCTURE OF A TEST STEP…86…1 …02… …02… …02… …02…
b) T̲h̲e̲ ̲s̲t̲r̲u̲c̲t̲u̲r̲e̲ ̲o̲f̲ ̲t̲h̲e̲ ̲O̲f̲f̲l̲i̲n̲e̲ ̲T̲r̲o̲u̲b̲l̲e̲s̲h̲o̲o̲t̲i̲n̲g̲ ̲T̲r̲e̲e̲
The offline troubleshooting procedures are described
in step-by-step procedures, i.e. each step contains
a test. The result of this test specifies the next
step and so on until the error is traced to a faulty
module.
The structure of a test step is presented in Figure
4.3.3-1.
An explanation of the Figure is given below:
Each step is surrounded by two lines of asterisks:
One line above the contents of the step and one
line below.
The test step is presented in a three column format:
STEP
PROCEDURE
DESCRIPTION/ACTION
- S̲T̲E̲P̲:̲ (refer to the column a) in Figure 4.3.3-1).
Each test is identified by a step number.
The step consists of a 4 digit number: X…0f…1…0e…, X…0f…2…0e…,
X…0f…3…0e…, X…0f…4…0e….
X…0f…1…0e… specifies the subsystem in which the test is
executed, i.e.
X…0f…1…0e… STEP SUBSYSTEM SECTION
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 1000-2000 PU 4.3.3.1
2 2000-3000 CU 4.3.3.2
3 3000-4000 WD 4.3.3.3
4 4000-5000 TDX 4.3.3.4
5 5000-6000 DIST.EQUIPMT 4.3.3.5
6̲ ̲ ̲ ̲ ̲6̲0̲0̲0̲-̲7̲0̲0̲0̲ ̲ ̲ ̲ ̲P̲E̲R̲I̲P̲H̲E̲R̲A̲L̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲4̲.̲3̲.̲3̲.̲6̲ ̲ ̲ ̲ ̲
This information is also included in the overview of
offline troubleshooting tree in appendix C.
X…0f…2…0e… specifies the actual test sequence in the subsystem
(refer to Appendix C).
X…0f…3…0e… X…0f…4…0e… specifies the step within the test. The testsequence
is in step of 5, i.e. the first step is 05, the
second step is 10, etc.
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
An example of a step number is: 2510
X…0f…1…0e… = 2: CU Subsystem
X…0f…2…0e… = 5: Test of LTU module (2500-2600)
(refer to Appendix C)
X…0f…3…0e…X…0f…4…0e… = 10: The step is the second step in the
LTU test sequence.
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
- P̲R̲O̲C̲E̲D̲U̲R̲E̲ (refer to the column b) in Figure
4.3.3-1).
The activating procedure of the test is specified
in the PROCEDURE column.
Some of the tests use the following character:
# ̲. The character identifies the module in test.
The exact identification of the module is specified
in Error Report printed at the maintenance position
in the "UNIT NO" column. A detailed description
of the possible "UNIT NO" parameters is given in
Section A.2 (refer to Appendix A).
The following types of activating procedures are
used:
1) An activation of an automatic test sequence. This
type is always activated by a command entered from
the maintenance position VDU.
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
An example is: TEST ALL (CR)
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
2) A manually activated test on a module.
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
An example is: Press the MC button on the front
of the MAP module.
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
3) Visual Test:
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
An example is: Check that the POWER LED is "ON"
on all the modules in the CU crate.
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
- O̲B̲S̲E̲R̲V̲A̲T̲I̲O̲N̲/̲A̲C̲T̲I̲O̲N̲:̲ (refer to the column C in
Figure 4.3.3-1)
In the OBSERVATION/ACTION column are listed all
possible results of the test activated in the PROCEDURE
column. Each result is marked with an "o", and
contains a specification of the next step in the
troubleshooting procedure.
The correct option (marked with an "o") is selected
in the following way:
When a test is activated and finished the result
of the test is compared with the different results
listed in the OBSERVATION/ACTION column. The option
which is identical with the actual result of the
test contains a specification of the next step
in the troubleshooting procedure, which may be
one of the following types:
1) A̲c̲t̲i̲v̲a̲t̲i̲o̲n̲ ̲o̲f̲ ̲a̲n̲o̲t̲h̲e̲r̲ ̲t̲e̲s̲t̲.̲
The following mnemonics are used to define the
next step in the troubleshooting tree.
CONTINUE: Proceed with the next step in the
test sequence.
GO TO: Jump to another specified step in
the test sequence.
REPEAT: Repeat the same step to check if
an action has removed the error.
2) M̲a̲n̲u̲a̲l̲ ̲a̲c̲t̲i̲o̲n̲: The action is described.
An example of the contents of a OBSERVATION/ACTION
column is shown in Figure 4.3.3-2.
The example is explained below:
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
E̲X̲A̲M̲P̲L̲E̲:̲
Step 2005 tests if it is possible to enable the FD
Ctrl. or not.
There are 3 different results each depending on the
kind of error in the system.
If the result of the command entered in the "PROCEDURE"
column is:
"FFFF"
" "
then it is possible to enable the FD Ctrl. and the
next step to be executed in step 2010.
If the result of the command entered in the "PROCEDURE"
column is:
"MAP STATUS A[[["
then it is not possible to enable the FD Ctrl. (unexpected
result) and the next step to be executed is step 2015.
If it was not possible to enter the command in the
"PROCEDURE" column, then there is an error in the PU
Subsystem, and the next step to be executed is step
1000.
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *…86…1 …02… …02… …02… …02…
Figure 4.3.3-2
An example of the contents …01…of the OBSERVATION/ACTION column
c) T̲h̲e̲ ̲"̲T̲E̲S̲T̲"̲ ̲m̲o̲d̲e̲ ̲o̲f̲ ̲t̲h̲e̲ ̲s̲y̲s̲t̲e̲m̲.̲
The part of the CAMPS equipment which is tested
by the Offline Troubleshooting Procecures has to
be taken Offline before the tests begin.
It is, therefore, necessary to close down the Standby
PU, and the part of the CAMPS' equipment, which
will be involved in the Offline tests, before the
Offline troubleshooting starts. It is specified
in the Offline Troubleshooting Tree when it is
necessary to close down a part of the CAMPS equipment.
The close down procedures are described in section
5.3.6 in the "MAINTENANCE POSITION OPERATION MANUAL"
Doc. No. CPS/OPM/005.
4.4 R̲E̲P̲L̲A̲C̲E̲M̲E̲N̲T̲ ̲P̲R̲O̲C̲E̲D̲U̲R̲E̲S̲
This section describes the replacement procedures of
the modules, units, and crates mounted in the CAMPS
racks.
The replacement procedures of the peripherals and racks
are described in the peripheral manuals.
For the replacement of power distribution panels, signal
and power cables refer to the "INSTALLATION MANUAL".
After failure localization, normal system operation
is restored by replacement of the failed module/crate/unit.
The replacement is accomplished by different procedures
dependent on which type of assembly the module/crate/
unit is mounted in.
The different replacement procedures apply to module/crate
mounted in the following sections:
P̲r̲o̲c̲e̲s̲s̲o̲r̲ ̲U̲n̲i̲t̲ ̲S̲u̲b̲s̲y̲s̲t̲e̲m̲ ̲(̲S̲e̲c̲t̲i̲o̲n̲ ̲4̲.̲4̲.̲1̲)̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲I̲T̲E̲M̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲S̲E̲C̲T̲I̲O̲N̲ ̲ ̲ ̲
CCA CR8089M 4.4.1.1
CPU/CACHE CR8003M 4.4.1.1
FAN ̲UNIT CR8105M 4.4.1.4
MAP CR8020M 4.4.1.1
MBT CR8055M 4.4.1.1
MIA CR8071M 4.4.1.1
POW SUPP CR8050M 4.4.1.2
PU ̲Crate CR8125M 4.4.1.3
RAM 512K CR8016M 4.4.1.1
STI CR8021M 4.4.1.1
TIA CR8073M 4.4.1.1
THERMOSTAT TRAFAG 4.4.1.5
TSP CR8142M 4.4.1.1
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
C̲h̲a̲n̲n̲e̲l̲ ̲U̲n̲i̲t̲ ̲S̲u̲b̲s̲y̲s̲t̲e̲m̲ ̲(̲S̲e̲c̲t̲i̲o̲n̲ ̲4̲.̲4̲.̲2̲)̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲I̲T̲E̲M̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲S̲E̲C̲T̲I̲O̲N̲ ̲ ̲ ̲
CIA-A/B CR8081M 4.4.2.1
CCA CR8089M 4.4.1.1
CUCP CR8042M 4.4.2.1
CU CRATE CR8125M 4.4.1.3
DCA CR8084M 4.4.2.1
DISK CTRL CR8044M 4.4.2.1
DISK DRIVE MMD 4.4.2.4
DISK DRIVE SMD 4.4.2.5
FAN UNIT CR8105M 4.4.1.4
FD DRIVE FD 4.4.2.6
LIA-N CR8082M 4.4.2.1
LTU CR8066M 4.4.2.1
MBT CR8055M 4.4.2.1
POW ̲SUPP CR8050M 4.4.2.1
SFA CR8087M 4.4.2.1
ST FD CTRL CR8047M 4.4.2.1
THERMOSTAT TRAFAG 4.4.1.5
TSP CR8142M 4.4.1.1
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
W̲a̲t̲c̲h̲d̲o̲g̲ ̲U̲n̲i̲t̲ ̲S̲u̲b̲s̲y̲s̲t̲e̲m̲ ̲(̲S̲e̲c̲t̲i̲o̲n̲ ̲4̲.̲4̲.̲3̲)̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲I̲T̲E̲M̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲S̲E̲C̲T̲I̲O̲N̲ ̲ ̲ ̲
CCBA CR8091M 4.4.3.1
WCA CR8076M 4.4.3.1
WPU (LTU) CR8066M 4.4.3.1
WD CRATE CR8115M 4.4.3.2
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
T̲D̲X̲ ̲&̲ ̲D̲i̲s̲t̲.̲E̲q̲u̲i̲p̲.̲A̲d̲a̲p̲t̲e̲r̲ ̲S̲u̲b̲s̲y̲s̲t̲e̲m̲ ̲(̲S̲e̲c̲t̲i̲o̲n̲ ̲4̲.̲4̲.̲4̲)̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲I̲T̲E̲M̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲S̲E̲C̲T̲I̲O̲N̲ ̲ ̲ ̲
ADAP POW SUPP CR1102S 4.4.4.1
BACK PANEL CR1100S 4.4.4.1
BSM-X CR1074S 4.4.4.1
FAN UNIT CR8105S 4.4.4.3
LTUX-S CR1060S 4.4.4.1
L/L ADAP 4 CH CR80109 4.4.4.1
L/L ADAP 1 CH CR80110 4.4.4.1
OPTO T/R CR80108 4.4.4.1
OUTLETS CR2510 4.4.4.4
POW SUPP CR8022S 4.4.4.1
TDX CRATE CR1081S 4.4.4.2
TDX CTRL CR1070S 4.4.4.1
THERMOSTAT TRAFAG 4.4.1.5
TSP CR1103S 4.4.4.1
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
M̲a̲i̲n̲s̲ ̲S̲w̲i̲t̲c̲h̲ ̲(̲S̲e̲c̲t̲i̲o̲n̲ ̲4̲.̲4̲.̲5̲)̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲I̲T̲E̲M̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲S̲E̲C̲T̲I̲O̲N̲ ̲ ̲ ̲
Mains Switch CR8108 4.4.5.1
F̲r̲e̲q̲u̲e̲n̲c̲y̲ ̲S̲t̲a̲b̲i̲l̲i̲z̲e̲r̲ ̲(̲S̲e̲c̲t̲i̲o̲n̲ ̲4̲.̲4̲.̲6̲)̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲I̲T̲E̲M̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲S̲E̲C̲T̲I̲O̲N̲ ̲ ̲ ̲
Frequency Stabilizer 4.4.6-1
R̲a̲c̲k̲ ̲(̲S̲e̲c̲t̲i̲o̲n̲ ̲4̲.̲4̲.̲7̲)̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲I̲T̲E̲M̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲S̲E̲C̲T̲I̲O̲N̲ ̲ ̲ ̲
Gasket 4.4.7-1
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…86…1 …02…
…02… …02…
4.4.1 P̲r̲o̲c̲e̲s̲s̲o̲r̲ ̲U̲n̲i̲t̲
4.4.1.1 P̲U̲ ̲M̲o̲d̲u̲l̲e̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲
The following module replacement procedures are described:
- CCA - RAM
- CPU/CACHE - STI
- MAP - TIA
- MIA - TSP
- MBT
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 Do the PU Close-down procedure (refer to the
"MAINTENANCE POSITION OPERATION MANUAL" Doc.
No. CPS/OPM/005)
2 Open the applicable doors to the PU crate
3 Turn power "OFF" on the two power supplies
mounted in the PU assembly
4 Unscrew the module fingerscrews. Disconnect
the cable(s) from the module, if any. Remove
the actual module from the crate
5 Verify that switch settings and strap settings
in the spare module are correct (refer to sec.
4.5)
6 Insert the spare module in the crate. Connect
the cables to the module, if any. Tighten the
module finger screws
7 Turn power "ON" on the two power supplies mounted
in the PU assembly.
8 Check the LEDs on the front of the module (refer
to sec. 4.5)
9 Close the doors to the PU crate
10 Do the PU Start-up procedure (refer to the
"MAINTENANCE POSITION OPERATION MANUAL Doc.
No. CPS/OPM/005)
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
4.4.1.2 P̲U̲ ̲P̲o̲w̲e̲r̲ ̲S̲u̲p̲p̲l̲y̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲
The following module replacement procedure is described:
- Power Supply
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 Do the PU Close-down procedure (refer to the
"MAINTENANCE POSITION OPERATION MANUAL" Doc.
No. CPS/OPM/005)
2 Open the applicable doors to the PU crate
3 Turn power "OFF" on the two power supplies
mounted in the PU assembly
4 Turn power "OFF" on the mains switches in the
power panels A and B at the rear of the PU
crate (refer to sec. 4.5)
5 Unscrew the module fingerscrews. Remove the
actual module from the crate
6 Insert the spare module in the crate. Tighten
on the finger screws
7 Turn power "ON" on the mains switches in power
panels A and B at the rear of the PU crate
(refer to sec. 4.5)
8 Turn power "ON" on the two power supplies mounted
in the PU assembly.
9 Check the LEDs on the front of the module in
the PU crate (refer to sec. 4.5)
10 Close the doors to the PU crate
11 Do the PU start-up procedure (refer to the
"MAINTENANCE POSITION OPERATION MANUAL" Doc.
No. CPS/OPM/005)
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
4.4.1.3 P̲U̲ ̲C̲r̲a̲t̲e̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲s̲
The following replacement procedure is described:
- PU Crate
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 Open the doors to the actual PU crate
2 Verify that the identification labels of the
crate cables and modules are correct (refer
to CAMPS H/W ASSEMBLY BREAKDOWN Doc. No. CPS/SDS/017)
3 Do the PU Close-down procedure (refer to the
"MAINTENANCE POSITION OPERATION MANUAL" Doc.
No. CPS/OPM/005)
4 Turn power "OFF" on the two power supplies
in the PU crate
5 Turn power "OFF" on the mains switches in the
power panels A and B at the rear of the PU
crate (refer to sec 4.5)
6 Unscrew the four 6 mm screws on the fan unit
(refer to sec. 4.5). Turn power "OFF" on the
two switches placed at the rear of the fan
unit (refer to sec. 4.5)
7 Disconnect the two power cables from the fan
unit
8 Remove the fan unit
9 Disconnect all cables from the modules in the
PU crate
10 Unscrew the module fingerscrews from the modules.
Remove all the modules from the crate
11 Unscrew the crate screws. Remove the crate
12 Insert the spare PU crate. Screw the crate
screws
13 Insert the modules in correct slot numbers
in the crate. (Refer to H/W ASSEMBLY BREAKDOWN
Doc. No. CPS/SDS/017). Tighten the module fingerscrews
(cont'd)
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
(cont'd)
14 Connect the cables to the correct modules in
the crate. (Refer to Doc. No. CPS/SDS/017).
15 Insert the fan unit
16 Connect the two power cables to the fan unit.
Turn power "ON" on the two swithes placed at
the rear of the fan unit (refer to sec. 4.5)
17 Check the lamps on the front of the fan (refer
to sec. 4.5)
18 Tighten the fan unit fingerscrews
19 Turn power "ON" on the mains switches in the
power panels A and B at the rear of the PU
crate (refer to sec. 4.5)
20 Turn power "ON" on the two power supplies in
the PU crate.
21 Check the LEDs on the front of the modules
in the PU crate (refer to sec. 4.5)
22 Close the doors to the PU crate
23 Do the PU Start-up procedure (refer to the
"MAINTENANCE POSITION OPERATION MANUAL" Doc.
No. CPS/OPM/005)
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
4.4.1.4 P̲U̲ ̲F̲a̲n̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲
The following module replacement procedure is described:
- Fan Unit
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
* IMPORTANT
*
* It is important that the replacement time of the
*
* fan does not exceed 3 minutes, otherwise the rack
*
* temperature may increase to a critical level.
*
* Therefore, read this replacement procedure
*
* before the actual replacement of the fan takes
*
* place.
*
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 Open the applicable doors to the actual rack
2 Place the spare fan near the rack
3 Unscrew the fan unit fingerscrews (refer to
sec. 4.5)
4 Turn power "OFF" on the two switches placed
at the rear of the fan unit (refer to sec.
4.5)
5 Disconnect the two power cables from the fan
unit.
6 Remove the fan unit
7 Insert the spare fan unit
8 Connect the two power cables to the fan unit.
9 Turn power "ON" on the two switches placed
at rear of the fan unit (refer to sec. 4.5)
10 Check the LEDs on the front of the fan (refer
to sec. 4.5)
11 Tighten the fan unit fingerscrews
12 Close the doors to the rack
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
4.4.1.5 T̲h̲e̲r̲m̲o̲s̲t̲a̲t̲
4.4.1.5.1 T̲h̲e̲r̲m̲o̲s̲t̲a̲t̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲
̲P̲r̲o̲c̲e̲d̲u̲r̲e̲s̲
The following replacement procedure is described
- Termostat
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 Open the doors to the actual crate
2 Disconnect the termostat - TSP cable from the
TSP
(refer to (a) in figure 4.4.1.5.1-1)
3 Unscrew the two screw situated on the front
of the thermostat (refer to (b) in figure 4.4.1.5.1-1).
Remove the front cover.
4 Unscrew the screw situated in the cover of
the the thermostat (refer to (c) in figure
4.4.1.5.1-1)
5 Remove the termostat including the temperature
sensor. Be carefull not to damage the temperature
sensor when cutting the plastic tie wrappers
(refer to (a) in figure 4.4.1.5.1-2).
6 Insert the spare thermostat including the spare
temperature sensor. The temperature sensor
is tightened by plastic tie wrappers.
7 Tighten the thermostat and the cover
8 Connect the termostat - TSP cable to the TSP
9 Close the doors to the crate.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…86…1 …02… …02… …02… …02…
Figure 4.4.1.5.1-1
Thermostat Removal Procedure
Figure 4.4.1.5.1-2…01…Temperature Sensor Removed
4.4.2 C̲h̲a̲n̲n̲e̲l̲ ̲U̲n̲i̲t̲
4.4.2.1 C̲U̲ ̲M̲o̲d̲u̲l̲e̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲
The following module replacement procedures are described:
- CIA - LIA-N
- CCA - LTU
- CUCP - MBT
- DCA - SFA
- DISK CTRL - ST. FD. CTRL
- TSP
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
* IMPORTANT
*
* Replacement of modules in the Channel Unit
*
* is executed without switch-off of the connected
*
* power supply.
*
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 Open the doors to the CU crate
2 Unscrew the module fingerscrews. Disconnect
the cable(s) from the module, if any. Remove
the actual module from the crate
3 Verify that switch settings in the spare module
are correct (refer to sec. 4.5)
4 Insert the spare module in the crate. Connect
the cable(s) to the module, if any. Tighten
the module finger screws
5 Check the LEDs on the front of the module (refer
to sec. 4.5)
6 Close the doors to the PU crate
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
4.4.2.2 C̲U̲ ̲P̲o̲w̲e̲r̲ ̲S̲u̲p̲p̲l̲y̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲
The following module replacement procedure is described:
- Power Supply
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 Open the doors to the CU crate
2 Turn power "OFF" on the actual power supply
3 Unscrew the module fingerscrews. Remove the
actual power supply from the crate
4 Insert the spare module in the crate. Tighten
the finger screws
5 Turn power "ON" on the actual power supply
mounted in the CU assembly.
6 Check the LEDs on the front of the module (refer
to sec. 4.5)
7 Close the doors to the CU crate
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
4.4.2.3 C̲U̲ ̲C̲r̲a̲t̲e̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲s̲
The following replacement procedure is described:
- CU Crate
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
* IMPORTANT
*
* It is necessary to close down the CAMPS system
*
* before replacing the Channel Unit (CU) crate.
*
* (Refer to the MAINTENANCE POSITION OPERATION
*
* MANUAL Doc. No. CPS/OPM/005)
*
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 Open the doors to the actual CU crate
2 Verify that the identification labels of the
crate cables and modules are correct (refer
to CAMPS H/W ASSEMBLY BREAKDOWN Doc. No. CPS/SDS/017)
3 Do the CAMPS System Close-down procedure (refer
to the "MAINTENANCE POSITION OPERATION MANUAL"Doc.
No. CPS/OPM/005)
4 Turn power "OFF" on the two power supplies
in the PU crate
5 Turn power "OFF" on the mains switches in the
power panels A and B at the rear of the CU
crate (refer to sec 4.5)
6 Unscrew the fan unit fingerscrews (refer to
sec. 4.5). Turn power "OFF" on the two switches
placed at the rear of the fan unit (refer to
sec. 4.5)
7 Disconnect the two power cables from the fan
unit
8 Remove the fan unit
9 Disconnect all cables from the modules in the
CU crate
10 Unscrew the module fingerscrews from the modules.
Remove all the modules from the crate
(cont'd)
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
(cont'd)
11 Unscrew the crate screws. Remove the crate
12 Insert the spare CU crate. Tighten the crate
screws
13 Insert the modules in correct slot numbers
in the crate. (Refer to CAMPS H/W ASSEMBLY
BREKDOWN Doc. No. CPS/SDS/017).Tighten the
fingerscrews
14 Connect the cables to the correct modules in
the crate
15 Insert the fan unit
16 Connect the two power cables to the fan unit.
Turn power "ON" on the two swithes placed at
the rear of the fan unit (refer to sec. 4.5)
17 Check the lamps on the front of the fan (refer
to sec. 4.5)
18 Tighten the fan unit fingerscrews
19 Turn power "ON" on the mains switches in the
power panels A and B at the rear of the CU
crate (refer to sec. 4.5)
20 Turn power "ON" on the two power supplies in
the CU crate.
21 Check the LEDs on the front of the modules
in the CU crate (refer to sec. 4.5)
22 Close the doors to the CU crate
23 Do the CAMPS System Start-up procedure (refer
to the "MAINTENANCE POSITION OPERATION MANUAL"
Doc. No. CPS/OPM/005)
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
4.4.2.4 M̲M̲D̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲
The following replacement procedure is described:
- MMD Disk Drive
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
* WARNING
*
* The MMD will contain classified data.
*
* It is only to be transported under escort as
*
* is to be treated NATO Secret material.
*
* If the failed MMD is shipped without escort
*
* then the sealed head unit must be removed.
*
* The removal procedure of the sealed head unit is
*
* described in the MMD H/W Maintenance Manual
*
* Section 2D "Mini Module Removal"
*
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 Disconnect drive from AC power by unplugging
power card from AC source.
2 Extend drive fully to maintenance position.
3 At top of drive, take out all head screws and
remove top cover.
4 Disconnect I/O cable from card assemblies of
the logic chassis. Remove I/O cable mounted
and detach I/O cables from drive.
5 Reinstall top cover with cable mounts attached
to inside of top cover.
6 At bottom of drive, loosen screws securing
bottom cover. Slide cover such that the screw
heads can pass through cover slots. Remove
bottom cover by dropping straight down as shown
on Fig. 4.4.2.4-1
NOTE: Two different methods of locking the
drive motor are shown on Fig. 4.4.2.4-2. For
new drives (having a motor lock plate), perform
step 7 and proceed to step 12. For old drives,
perform step 8 and proceed to step 12.
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
(cont'd)
7 Lock drive motor on new units by turning motor
shipping lock screw fully clockwise with a
5/32" allen wrench. This lowers motor lock
plate until it gets clear of the self-locking
nut.
8 Lock drive motor on old units by loosening
motor shipping lock screw (see Fig. 4.4.2.5-2),
rotating motor so that motor mount plate contacts
screw, and then fasten screw.
9 Lock actuator by rotating actuator shipping
lock at underside of MMD module to ON position
(see Fig. 4.4.2.4-3).
10 Lock spindle by loosening attaching screws
on spindle lock ground spring as in Fig. 4.4.2.4-4.
Slide spindle lock and ground spring forward
and rotate the spindle pulley so that the spindle
lock notch locks the pin on spindle pulley.
11 Tighten attaching screws to hold spindle lock
and ground spring in the LOCK position.
12 Replace bottom cover.
Remove MMD module as follows:
13 Pull drive out to its fully extended position.
14 Loosen and lower slide assembly catch on each
J bracket
CAUTION: Two people are needed to lift disk
drive off slide assemblies.
15 Lift drive slightly and slide forward until
J bracket clears J bracket catch at rear of
each slide rail.
16 Lift drive straight up and remove.
17 Push slide assemblies to fully closed position
by pressing full extension lock and pushing
slide assembly. Use a string of nylon etc to
secure the slice assembly from moving during
transport.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
Figure 4.4.2.4-1…01…Cover Removal
4.4.2.4-2…01…Drive Motor Lock Screw
Figure 4.4.2.4-3…01…Actuator Shipping Lock
Figure 4.4.2.4-4…01…Spindle Lock and Ground Spring
4.4.2.5 S̲M̲D̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲
The following replacement procedure is described:
- SMD Disk Drive
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
* WARNING
*
* The SMD disk pack will contain classified data.
*
* It is not to be shipped with the SMD disk
*
* drive.
*
*
*
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 Remove any disk pack from drive.
2 Disconnect drive from AC power by unplugging
power card from AC source.
3 The I/O cables connected at the rear of unit
can be disconnected when the cable clamp is
removed. When the I/O cables are removed, the
cable clamp must be reinstalled.
4 Release lock located under the front of SMD
module at the righthand side (Refer to Figure
4.4.2.5-1).
5 Pull drive out to its fully extended position
by pressing full extension releases (see Fig.
4.4.2.5-2).
6 Loosen nuts securing quick-disconnect catches
and slide catches towards front of drive.
CAUTION: Two people are required to lift drive
off slice assemblies.
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
(cont'd)
7 Carefully lift drive (with quick-disconnects
attached to drives base assembly) from slide
and place on a solid support).
8 Open top cover. Look at the rear of case assembly
to determine how case is secured. If latches
are secured by socket head screws, loosen them.
CAUTION: Lift up case only one inch during
next step.
9 Release case as follows:
a) Depress the release catches
and lift up case slightly,
or
b) Depress the socked head
screws and lift up case
slightly.
(cont'd)
Figure 4.4.2.5-1
SMD Front
Figure 4.4.2.5-2
Slide Assembly Parts Location
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
(cont'd)
10 After case has been released and raised about
an inch, swing hinged rear panel of case outwards
to clear the rear of the actuator assembly.
11 Pivot case upwards and towards the front until
it rests on case support arm.
12 Ensure all fitted internal shipping hardware
is adjusted correctly and secure (refer to
Fig. 4.4.2.5-3):
a. Stock lock bracket. Attach
caution tag with cord.
Drape cord to outside of
unit to ensure visibility
when top cover is closed.
b. Rear vibration isolator
lockout screw. Attach caution
tag by cord or tape.
c. Logic chassis logging screw
is secure at the lower
magnet point. Logic chassis
is secured at the top front
of the logic frame.
d. Plastic spindle cover is
in place in the pack cafity.
e. Heads are in the retracted
position. Insert carriage
locking pin when present.
Tape across pin and ring
to prevent the pin from
unseating during shipment.
Also secure one caution
tag to the locking pin
ring.
In the absence of a locking
pin, tie heads and actuator
in the retracted position
using double strand nylon
cord. use caution in placing
cord between heads and
carriage. Tie at rear of
the magnet assembly and
attach caution tag.
13. Close top cover as described in the following
steps.
(cont'd)
Figure 4.4.2.5-3
SMD Locks
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
(cont'd)
14 Pivot case towards rear and downwards, and,
as it is being lowered, swing hinged rear panel
of case outwards so it clears actuator. Do
n̲o̲t̲ completely close case.
15 When case is about one inch from touching frame,
swing hinged rear panel inwards until it reaches
its end of travel.
16 While holding hinged rear palen, lower case
assembly to its fully closed position.
17 Ensure that latches catch. If socket head screws
are used, tighten them.
18 Push slide assemblies to fully closed position
by pressing on full extension lreleases and
pushing in slide assemblies. Use a string of
nylon etc. to secure the slide assembly from
moving during shipment.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
4.4.2.6 F̲l̲o̲p̲p̲y̲ ̲D̲i̲s̲k̲ ̲S̲t̲a̲t̲i̲o̲n̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲
The following replacement procedure is described:
- Floppy Disk Station
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
* WARNING
*
* The FD disk pack will contain classified data.
*
* It is not to be shipped with the FD drive
*
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 Open the doors to the rack
B
2 Turn power "OFF" on the FD power supply
3 Unscrew the four 6 x 6mm screws holding both
the cabinet and the front panel. Disconnect
the cables from the Floppy Disk station
4 Remove the Floppy Disk Station
5 Insert the spare Floppy Disk Station
6 Tighten the four 6 x 6mm screws on the front
of the Floppy Disk Station
7 Connect the cables to the Floppy Disk Station
8 Close the doors to the rack B
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
4.4.3 W̲a̲t̲c̲h̲d̲o̲g̲ ̲U̲n̲i̲t̲
4.4.3.1 W̲D̲ ̲M̲o̲d̲u̲l̲e̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲
The following module replacement procedures are described:
- CCBA
- WCA
- WPU (LTU)
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
* IMPORTANT
*
* Replacement of modules in the Watchdog Processor
*
* does not affect the operation of the remaining
*
* CAMPS equipment.
*
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 Open the doors to the WD crate
2 Turn power "OFF" on the power supply mounted
in the WD assembly (rear of crate)
3 Unscrew the module fingerscrews. Disconnect
the cables from the module, if any. Remove
the actual module from the crate
4 Verify that switch settings on the spare module
are correct (refer to sec. 4.5)
5 Insert the spare module in the crate. Connect
the cables to the modules, if any. Tighten
the module finger screws
6 Turn power "ON" on the power supply mounted
in the WD assembly.
7 Check the LEDs on the front of the module (refer
to sec. 4.5)
8 Close the doors to the WD crate
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
4.4.3.2 W̲D̲ ̲C̲r̲a̲t̲e̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲
The following replacement procedure is described:
- WD Crate
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
* IMPORTANT
*
* Replacement of the Watchdog Crate does not
*
* affect the operation of the remaining
*
* CAMPS equipment.
*
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 Open the doors to the WD crate
2 Verify that the identification labels of the
crate cables and modules are correct (refer
to CAMPS H/W ASSEMBLY BREAKDOWN Doc. No. CPS/SDS/017)
3 Turn power "OFF" on the WD power supply
4 Disconnect all cables from the modules in the
crate
5 Unscrew the module fingerscrews from the modules.
Remove all the modules from the crate
6 Unscrew the crate screws. Remove the crate
7 Insert the spare crate. Tighten the crate screws
8 Insert the modules in correct slot numbers
in the crate. Refer to CAMPS H/W ASSEMBLY BREAKDOWN
Doc. No. CPS/SDS/017). Tighten the module finger
screws
9 Connect the cables to the correct modules in
the crate. (Refer to Doc. No. CPS/SDS/017)
10 Turn power "ON" on the power supply in the
WD crate.
11 Check the LEDs on the front of the modules
in the crate (refer to sec. 4.5)
12 Close the doors to the WD crate
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
4.4.4 T̲D̲X̲/̲A̲d̲a̲p̲t̲e̲r̲ ̲U̲n̲i̲t̲
4.4.4.1 T̲D̲X̲/̲A̲d̲a̲p̲t̲e̲r̲ ̲M̲o̲d̲u̲l̲e̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲
The following module replacement procedures are described:
- BSM-X - OPTO T/R
- LTUX-S - Power Supply
- L/L Adapter 4 CH - TDX CTRL
- L/L Adapter 1 CH - TSP
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 Users connected to the TDX/Adapter will be
requested to cease operation
2 When all users connected to the TDX/Adapter
in question have ceased operation, the two
power supplies in the TDX/Adapter are turned
"OFF"
3 Unscrew the module fingerscrews. Disconnect
the cable(s) from the module, if any. Remove
the actual module from the crate
4 Verify that switch settings on the spare module
are correct (refer to sec. 4.5)
5 Insert the spare module in the crate. Connect
the cable(s) to the module, if any. Tighten
the module finger screws
6 Turn power "ON" on the power supply mounted
in the TDX assembly.
7 Check the LEDs on the front of the module (refer
to sec. 4.5)
8 Close the doors to the TDX/Adapter Crate
9 All users connected to the TDX/Adapter in question
are notified to resume operation
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
4.4.4.2 T̲D̲X̲/̲A̲d̲a̲p̲t̲e̲r̲ ̲C̲r̲a̲t̲e̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲
The following replacement procedure is described:
- TDX/Adapter Crate
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 Open the doors to the actual TDX/Adapter crate
2 Verify that the identification labels of the
crate cables and modules are correct (refer
to CAMPS H/W ASSEMBLY BREAKDOWN Doc. No. CPS/SDS/017).
3 Users connected to the TDX/Adapter will be
requested to cease operation
4 When all users connected to the TDX/Adapter
in question have ceased operation, the three
power supplies switches in the TDX/Adapter
crate are turned "OFF"
5 Disconnect all cables from the modules in the
crate
6 Unscrew the module fingerscrews from the modules.
Remove all the modules from the crate
7 Unscrew the crate screws. Remove the crate
8 Insert the spare crate. Tighten the crate screws
9 Insert the modules in correct slot numbers
in the crate. (Refer to CAMPS H/W ASSEMBLY
BREAKDOWN Doc. No. CPS/SDS/017). Tighten the
module finger screws
10 Connect the cables to the correct modules in
the crate
11 Turn power "ON" on the three power supplies
in the TDX/Adapter crate.
12 Check the LEDs on the front of the modules
in the crate (refer to sec. 4.5)
13 Close the doors to the TDX/Adapter crate
14 All users connected to the TDX/Adapter in question
are notified to resume operation
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
4.4.4.3 T̲D̲X̲ ̲F̲a̲n̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲
The following module replacement procedure is described:
- Fan Unit
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
* IMPORTANT
*
* It is important that the replacement time of the
*
* fan does not exceed 3 minutes, otherwise the rack
*
* temperature may increase to a critical
*
* level.(40…0e…o…0f…C).
*
* Therefore, read this replacement procedure
*
* before the actual replacement of the fan takes
*
* place.
*
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 Open the applicable doors to the actual rack
2 Verify that a spare fan is situated on the
floor near the rack
3 Unscrew the fan unit screws on the front
4 Turn power "OFF" on the switch placed on the
rear of the fan unit (refer to sec. 4.5)
5 Disconnect the fan power cable from the power
distribution panel
6 Remove the fan unit
7 Insert the spare fan unit
8 Connect the fan power cable to the power distribution
panel
9 Turn power "ON" on the switch placed at rear
of the fan unit (refer to sec. 4.5)
10 Tighten the fan unit screws
11 Close the doors to the rack
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
4.4.4.4 T̲D̲X̲ ̲O̲u̲t̲l̲e̲t̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲
The following replacement procedure is described:
- TDX outlet.
S̲t̲e̲p̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 Open the applicable doors to the actual TDX
rack
2 Turn power "OFF" on the power supplies situated
in the TDX crate which is connected to the
outlet via the BSM-X module.
3 Turn power "OFF" on the TDX Ctrl. connected
to the actual TDX Bus.
4 Turn power "OFF" on the PU connected to the
actual TDX Bus.
5 Disconnect the BSM-X-Outlet cable from the
outlet
6 Unscrew and remove the TDX-Bus cables from
the TDX outlet without shortcircuiting the
cores.
7 Remove the TDX outlet. Refer to figure 4.4.4.4-1.
8 Mount the spare TDX outlet
9 Tighten the TDX-Bus cables to the TDX outlet.
(Refer to CAMPS H/W ASSEMBLY BREAKDOWN Doc.
No. CPS/SDS/017).
Do not shortcircuit the cores
10 Connect the BSM-X-outlet cable to the outlet
11 Turn power "ON" on the actual PU, the TDX Ctrl.
and the TDX crate.
12 Close the doors to the TDX rack.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…86…1 …02… …02… …02… …02…
Figure 4.4.4.4-1
TDX Outlet
4.4.5 M̲a̲i̲n̲s̲ ̲S̲w̲i̲t̲c̲h̲
4.4.5.1 M̲a̲i̲n̲s̲ ̲S̲w̲i̲t̲c̲h̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲s̲
S̲t̲e̲p̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 Turn power "OFF" on the actual circuit breaker
on the CAMPS Power Distribution Board (PDB)
2 Open the doors to the actual rack
3 Turn power "OFF" on the two switches placed
at the front of the mains switch
4 Disconnect the power cables on the rear side
of the mains switch
5 Disconnect the ground wire on the rear side
of the mains switch
6 Loosen the four 6 mm front screws and pull out
the mains switch from the front of the rack
7 Insert the spare main switch in the front of
the rack and tighten the four 6 mm front screws
8 Check that the two switches at the front of
the unit are turned "OFF"
9 Connect the ground wire to the rear side of
the mains switch
10 Connect the power cables to the rear side of
the mains switch
11 Turn power "ON" on the actual circuit breaker
on the CAMPS Power Distribution Board (PDB)
12 Check that no fuses in the CAMPS PDB are blown
due to a short circuit in the installation
13 Turn the power switches on the front of the
mains switch "ON" one by one and check that
the "POWER ON" lamp lits
14 Check that the fans are running and the power
LEDs in the modules are "ON"
15 Close the door to the rack.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…86…1 …02… …02… …02… …02…
4.4.6 F̲r̲e̲q̲u̲e̲n̲c̲y̲ ̲S̲t̲a̲b̲i̲l̲i̲z̲e̲r
4.4.6.1 F̲r̲e̲q̲u̲e̲n̲c̲y̲ ̲S̲t̲a̲b̲i̲l̲i̲z̲e̲r̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲
S̲t̲e̲p̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 Turn power "OFF" on the actual circuit breaker
on the CAMPS Power Distribution Board (PDB)
2 Open the doors to the frequency stabilizer
rack
3 Turn power "OFF" on the switch placed at the
front of the frequency stabilizer
4 Disconnect the power cables on the rear side
of the frequency stabilizer
5 Disconnect the ground wire on the rear side
of the frequency stabilizer
6 Loosen the eight 6 mm front screws and pull
out the frequency stabilizer from the front
of the rack
7 Insert the spare frequency stabilizer the front
of the rack and tighten the eight 6 mm front
screws
8 Check that the two switches at the front of
the unit are turned "OFF"
9 Connect the ground wire to the rear side of
the frequency stabilizer
10 Connect the power cables to the rear side of
the frequency stabilizer
11 Turn power "ON" on the actual circuit breaker
on the CAMPS Power Distribution Board (PDB)
12 Check that no fuses in the CAMPS PDB are blown
due to a short circuit in the installation
13 Turn the power switch on the front of the frequency
stabilizer "ON" and check that the "POWER ON"
lamp lits and the "FAULT" lamp turns "OFF"
in about 5 sec.
14 Close the door to the rack.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…86…1 …02… …02… …02… …02…
4.4.7 R̲a̲c̲k̲
4.4.7.1 G̲a̲s̲k̲e̲t̲ ̲R̲e̲p̲l̲a̲c̲e̲m̲e̲n̲t̲ ̲P̲r̲o̲c̲e̲d̲u̲r̲e̲
The following replacement procedure is described
Gasket (refer to figure 4.4.8.1-1)
NOTE:
If by accident parts of the gaskets are damaged during
transportation, these parts must be replaced to ensure
a correct shielding.
S̲t̲e̲p̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲A̲c̲t̲i̲o̲n̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
1 The damaged part of the gasket are cut by a
knife and removed.
2 Clean the mounting surface of old glue, if
necessary with a lacquer thinner (acetone or
tri-chlorethylene)
3 Cut and trim the gasket strip with scissors
4 Peel off the protective paper backing
5 Be sure that the strip is in correct position
and then press down firmly.
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲…86…1 …02… …02… …02… …02…
Figure 4.4.8.1-1
Rack Gasket
4.6 O̲N̲L̲I̲N̲E̲ ̲E̲R̲R̲O̲R̲ ̲R̲E̲P̲O̲R̲T̲I̲N̲G̲
The task of the online error reporting is to report
whenever an error is detected. The report is printed
on the maintenance position line printer.
All the possible error reports are listed in Appendix
A.
When an online error report is printed on the maintenance
position line printer, it is possible via the System
Troubleshooting Tree (section 4.3.2) to identify the
entry point in the Offline Troubleshooting Tree (section
4.3.3).
The system troubleshooting Tree describes the relations
between the error reports and the entry points in the
Offline Troubleshooting Tree.
The Offline Troubleshooting Tree describes the test
procedures necessary when tracing an error to a module.
4.8 B̲U̲I̲L̲T̲-̲I̲N̲-̲T̲E̲S̲T̲ ̲(̲B̲I̲T̲)̲ ̲P̲R̲O̲G̲R̲A̲M̲S̲ ̲
Section 4.8 describes the
- Purpose
- Characteristic
- Operation
of the Built-In-Test (BIT) programs.
a) P̲u̲r̲p̲o̲s̲e̲
The purpose of a BIT program is to test the basic
functions in the module.
b) C̲h̲a̲r̲a̲c̲t̲e̲r̲i̲s̲t̲i̲c̲s̲
The test programs are characterized as Built-In-Test
programs. This means that it is an internal test
in the module and that the test program is stored
in the firmware of the module.
The execution time of the test is 5-10 sec.. A
"TEST" LED situated on the front of each module
is turned "ON" during the test.
If the "TEST" LED turns "OFF" after 5-10 sec. then
the test is successfully finished. If the "TEST"
LED remains "ON" then it indicates that the Built-In-Test
(BIT) detected an error in the module.
c) O̲p̲e̲r̲a̲t̲i̲o̲n̲
The BIT program is always executed during the power
up.
In the MAP module it is furthermore possible to
activate the BIT program manually or by a software
command.
A summary of the modules containing a BIT program
and the step(s) describing the input/output to/from
the test programs are listed below:
CPU/CACHE
DISK CTRL
LTU step 1
LTUX
STI
WPU (LTU)
TDX CTRL
MAP steps 2 - 7
1 The operation of
the BIT programs
in the following
modules:
CPU/CACHE
DISK CTRL
LTU
LTUX
STI
WPU (LTU)
TDX CTRL
is described.
The BIT is activated The "TEST" LED turns
by turning power on "ON" during the
test.
to the module.
- If the test succeeds:
The "TEST" LED
turns out after
app. 5-10 sec.
- If the test fails:
The "TEST" LED
remains "ON"
and the faulty
module should
be replaced.
2 The operation of
the BIT program
in the
MAP module is described:
There are five different
methods (described
in the steps 3-7)
to activate a BIT
test in the MAP
module.
3 The BIT is activated The "TEST" LED turns
"ON"
by turning power to during the test.
the module.
- If the test succeeds:
The "TEST" LED
turns "OFF" after
app. 5-10 sec.
and either a)
or b) is printed
on the maintenance
position.
a)
[7 MAP/BIT OK
*
(MAP in MAINTENANCE
MODE)
b)
[7 MAP/BIT OK
DAMOS BOOTLOADER
VS....
CPU (No)
(MAP in NORMAL
mode)
- If the test fails:
The "TEST" LED
remains "ON"
and the following
output is printed
on the maintenance
position:
]7 XX XX....
(XX = don't care)
4 M̲a̲n̲u̲a̲l̲l̲y̲ ̲a̲c̲t̲i̲v̲a̲t̲e̲d̲ ̲B̲I̲T̲:̲ The same output
as in step 3
Press the "MC" button
5 BIT activated by a The same output
as
watchdog command in step 3.a
Type:
MACL (CR)
6 BIT activated by a The same output
as
bootloader command. in step 3a.
Type:
OC D[[[ [ (CR)
7 BIT activated by a The same output
as
maintenance command. in step 3b.
Type:
M-9[ D[[[ [[[[ (CR)
[[[[
kan bruges - m>ske
* * * * * * * * * * * * * * * * * * * * * * * * * *
* * * IMPORTANT
*
*
*
* If there is no communication between the main-
*
* tenance position VDU and the Central Equipment,
*
* then the troubleshooting procedure starts in step
*
* 3000.
*
* GO TO step 3000
*
* * * * * * * * * * * * * * * * * * * * * * * * * *
* *
̲ ̲ ̲R̲E̲P̲O̲R̲T̲-̲I̲D̲ ̲ ̲ ̲C̲R̲A̲T̲E̲/̲U̲N̲I̲T̲ ̲ ̲ ̲E̲N̲T̲R̲Y̲P̲O̲I̲N̲T̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲
CCB001 PU GO TO step 3000
CCB002 PU No action
CCB003 PU GO TO step 3000
CCB004 PU No action
CCB005- PU GO TO step 3000
CCB008
CCB009 CU GO TO step 3000
CCB010 CU No action
CCB011- CU GO TO step 3000
CCB014
CCB015 CU No action
CCB016 TDX GO TO step 3000
CCB017 TDX No action
CCB018 TDX GO TO step 3000
CCB019 TDX No action
CCB020 TDX GO TO step 3000
CCB021 TDX No action
CCB022- TDX GO TO step 3000
CCB026
CCB027 TDX No action
FMS001- CU GO TO step 2000
FMS036
GIE S/W GO TO section 5
GQU S/W GO TO section 5
GTE S/W GO TO section 5
MAP001 PU GO TO step 6000
PER001- DIST. GO TO step 6000
PER005 EQUIPM.
PER006- SCARS GO TO step 2000
PER013 CCIS
NICS
TARE
PGE S/W GO TO section 5
PSE S/W GO TO section 5
QEL S/W GO TO section 5
TMS001- TDX GO TO step 4000
TMS013
TMS014- TDX GO TO step 6000
TMS018
WD001- PU GO TO step 6000
WD002
̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲ ̲